16
Figure 15
Initials
Jumper N.
Description
S1
J11 (1-2)
Flow temp. probe
(HT)
SB
J11 (3-4)
Water tank temp.
Probe
S2
J11 (5-6)
Flow temp. probe
(LT)
SE
J11 (7-8)
External temp. Probe
T2
J12 (9-10)
Room thermostat
(HT)
T2
J12 (11-12)
Room thermostat
(LT)
AI
J12 (13-14)
0-10V analogic
device
CR
J12 (15-17)
Remote control
AL
J8 (18-19)
Alarm signal
VM
J9 (20-22)
Mixer valve
P4
J10 (23-24)
LT system circulator
P1
J10 (25-26) HT system circulator
P2
J10 (27-28)
Hot water circulator
Correspondence table for all sensors
Measured temperatures (°C) - Resistive values of the sensors (
Ω
).
T (°C) R (°
Ω
) T (°C) R (°
Ω
) T (°C) R (°
Ω
) T (°C) R (°
Ω
) T (°C) R (°
Ω
) T (°C) R (°
Ω
) T (°C) R (°
Ω
)
- 20
67739
- 1
28481
18
13062
37
6470
56
3426
75
1925
94
1137
- 19
64571
0
27279
19
12565
38
6247
57
3319
76
1870
95
1108
- 18
61568
1
26135
20
12090
39
6033
58
3216
77
1817
96
1079
- 17
58719
2
25044
21
11634
40
5828
59
3116
78
1766
97
1051
- 16
56016
3
24004
22
11199
41
5630
60
3021
79
1717
98
1024
- 15
53452
4
23014
23
10781
42
5440
61
2928
80
1669
99
998
- 14
51018
5
22069
24
10382
43
5258
62
2839
81
1622
100
973
- 13
48707
6
21168
25
9999
44
5082
63
2753
82
1577
101
948
- 12
46513
7
20309
26
9633
45
4913
64
2669
83
1534
102
925
- 11
44429
8
19489
27
9281
46
4751
65
2589
84
1491
103
901
- 10
42449
9
18706
28
8945
47
4595
66
2512
85
1451
104
879
- 9
40568
10
17959
29
8622
48
4444
67
2437
86
1411
105
857
- 8
38780
11
17245
30
8313
49
4300
68
2365
87
1373
106
836
- 7
37079
12
16563
31
8016
50
4161
69
2296
88
1336
107
815
- 6
35463
13
15912
32
7731
51
4026
70
2229
89
1300
108
796
- 5
33925
14
15289
33
7458
52
3897
71
2164
90
1266
109
776
- 4
32461
15
14694
34
7196
53
3773
72
2101
91
1232
110
757
- 3
31069
16
14126
35
6944
54
3653
73
2040
92
1199
- 2
29743
17
13582
36
6702
55
3538
74
1982
93
1168
6 .2 .6 Frost protection
The heating unit electronic control includes a frost
protection function. When the flow temperature sinks
to below a minimum value, the burners start working at
minimum power according to the procedure used to set
the functional parameters.
The frost protection mode is activated even if the external
probe (supplied with the appliance) is not connected to the
boiler: parameters 14 (related to the Ch1 high temperature
system) and 22 (Ch2 low temperature system) are in fact in
default and set in weather function.
Should one not want to connect the probe, the boiler must
be made to work at a fixed point to avoid problems. The
parameter 14 and 22 settings may only be altered by a
Technical Assistance Centre authorized by
B
.
b
Power and fuel gas supply must be activated and
the water system at a correct pressure for the frost
protection system to function.
Glycol can be used as an additive for the system (up to a
maximum of 50%) there where considered necessary by
the person responsible for the project, keeping in mind that
this substantially reduces efficiency as it alters the specific
heat of the fluid.
Furthermore several parts of the system could be damaged
by altering the pH.