Beretta CIAO GREEN R.S.I Скачать руководство пользователя страница 7

7

ENGLISH

6.  Carry on with the sequence until only water leaks out of the manual 

air vent valve, and the air 

fl

 ow has stopped. Close the manual air vent 

valve.

7.  

Check the system pressure level is correct (the ideal level is 1 bar).

8.  

Turn off the system 

fi

 lling tap.

9.  

Turn on the gas tap and ignite the boiler.

3.11 Flue gas discharge and air suction

Observe local legislation regarding 

fl

 ue gas discharge.

Flue gases are discharged from a centrifugal fan located inside the combus-
tion chamber and the 

control board

 constantly checks that this is working 

correctly. The boiler is supplied without the 

fl

 ue gas discharge/air suction kit, 

since it is possible to use the accessories for appliance with a forced draught 
sealed chamber that better adapts to the installation characteristics. 
For 

fl

 ue gas extraction and the restoration of boiler combustion air, it is essen-

tial to only use certi

fi

 ed piping. Connection must be carried out correctly as in-

dicated in the instructions supplied as standard with the 

fl

 ue gas accessories. 

Multiple appliances can be connected to a single smoke pipe provided that 
each is a sealed chamber-type appliance. The boiler is a Type C appliance 
(sealed chamber), and must therefore have a safe connection to the 

fl

 ue 

gas discharge pipe and to the combustion air suction pipe; these both carry 
their contents outside, and are essential for the operation of the appliance.

POSSIBLE OUTLET CONFIGURATIONS (FIG. 24)
B23P/B53P

 Suction indoors and discharge outdoors

C13-C13x

 Discharge via concentric wall outlet. The pipes may leave the 

boiler independently, but the outlets must be concentric or suf

fi

 ciently close 

together to be subjected to similar wind conditions (within 50 cm)

C23 

Discharge via concentric outlet in common smoke pipe (suction and 

discharge in the same pipe)

C33-C33x 

Discharge via concentric roof outlet. Outlets as for C13

C43-C43x

 Discharge and suction in common separate smoke pipes, but 

subjected to similar wind conditions

C53-C53x

 Separate discharge and suction lines on wall or roof and in areas 

with different pressures. The discharge and suction lines must never be 
positioned on opposite walls

C63-C63x

 Discharge and suction lines using pipes marketed and certi

fi

 ed 

separately (1856/1)

C83-C83x

 Discharge via single or common smoke pipe and wall suction line

C93-C93x

 Discharge on roof (similar to C33) and air suction from a single 

existing smoke pipe

“FORCED OPEN” INSTALLATION (TYPE B23P/B53P)
Flue gas discharge pipe ø 80 mm (

fi

 g. 20)

The 

fl

 ue gas discharge pipe can be directed to the most suitable direction 

according to installation requirements. For installation, follow the instruc-
tions supplied with the kit. In this con

fi

 guration, the boiler is connected to 

the 

fl

 ue gas discharge pipe (ø 80 mm) through an adaptor (ø 60-80 mm).

  The B23P/B53P con

fi

 guration is forbitten in case of installation in 

pressurised collective chimney (3CEp).

  In this case, the combustion air is picked up from the boiler instal-

lation room (which must be a suitable technical room with proper 
ventilation).

 Uninsulated 

fl

 ue discharge outlet pipes are potential sources of danger.

 Arrange 

the 

fl

 ue gas discharge pipe so it slopes by 1% towards the boiler.

  The boiler automatically adapts the purging to the type of installation 

and the length of the pipe.

maximum length* of the 

fl

 ue gas

discharge pipe ø 80 mm

pressure drop

45° bend

90° bend

 70 m

1 m

1,5 m

*“Straight length” means without bends, drainage terminals or joints.

“SEALED” INSTALLATION (TYPE C)

The boiler must be connected to concentric or twin 

fl

 ue gas discharge pipes 

and air suction pipes, both leading outdoors. The boiler must not be oper-
ated without them.

Concentric pipes (ø 60-100 mm) (

fi

 g.21)

The concentric pipes can be placed in the most suitable direction according 
to installation requirements, complying with the maximum lengths indicated 
in the table.

 Arrange 

the 

fl

 ue gas discharge pipe so it slopes by 1% towards the 

boiler.

 

Non-insulated outlet pipes are potential sources of danger.

 

The boiler automatically adapts the purging to the type of installation 
and the length of the pipe. 

 

Do not obstruct or choke the combustion air suction pipe in any way.

For installation, follow the instructions supplied with the kit.

Horizontal

straight length *

concentric pipe ø 60-100 mm

pressure drop

45° bend

90° bend

5,85 m

1,3 m

1,6 m

*“Straight length” means without bends, drainage terminals or joints.

Vertical

straight length *

concentric pipe ø 60-100 mm

pressure drop

45° bend

90° bend

6,85 m

1,3 m

1,6 m

*“Straight length” means without bends, drainage terminals or joints.

If the boiler must be installed with drainage below, use the special elbow (kit 
available on request – see Parts Catalogue).
In this type of installation, the inner pipe of the elbow must be cut at the 
point shown in 

fi

 g. 22 to allow the elbow itself to be inserted more easily into 

the 

fl

 ue gas discharge on the boiler.

Concentric pipes (ø 80-125)

For this con

fi

 guration, the special adaptor kit must be 

fi

 tted. The concentric 

pipes can face in the direction most suitable for installation requirements. 
For installation, follow the instructions supplied with the speci

fi

 c condensing 

boilers kits.

straight length *

concentric pipe ø 80-125 mm

pressure drop

45° bend

90° bend

 15,3 m

1,0 m

1,5 m

*“Straight length” means without bends, drainage terminals or joints.

Twin pipes (ø 80 mm) (

fi

 g. 23)

The twin pipes can face in the direction most suited to the installation re-
quirements. For installation, follow the instructions supplied with the spe-
ci

fi

 c accessory kit for condensing boilers.

To use the combustion air suction pipe, one of the two inlets (A and B) must 
be selected. Remove the closure plug which is 

fi

 xed using screws, and use 

the speci

fi

 c adaptor relating to the inlet selected (C air inlet adaptor ø 80 - D 

air inlet adaptor from ø 60 to ø 80) available as an accessory.

 Arrange 

the 

fl

 ue gas discharge pipe so it slopes by 1% towards the 

boiler.

 

The boiler automatically adapts the purging to the type of installation and 
the length of the pipes. Do not obstruct or choke the pipes in any way.

 

Refer to the graphs to 

fi

 nd the maximum lengths of the single pipe.

 

The use of longer pipes reduces the boiler output.

maximum straight length *

twin pipes ø 80 mm

pressure drop

45° bend

90° bend

 45+45 m

1,0 m

1,5 m

*“Straight length” means without bends, drainage terminals or joints.

PRESSURISED COLLECTIVE CHIMNEY 3CEP

  3CEp installations are available only with the dedicated accessory 

(optional).

  The B23P/B53P con

fi

 guration is forbitten in case of installation in 

pressurised collective chimney.

 

Maximum pressure of  the pressurised collective chimney must not 
exceed the 35 Pascal.

  Maintenance in case of pressurised collective chimney must be 

performed as indicated in the speci

fi

 c chapter “Maintenance in-

structions”.

  For 3CEp installations with dedicated accessory, it is necessary 

change the setting of minimum fan speed according the accessory 
instructions. 

Содержание CIAO GREEN R.S.I

Страница 1: ...S FELHASZN L I K ZIK NYV DE HANDBUCH F R DIE MONTAGE UND BENUTZUNG SL NAVODILA ZA VGRADITEV PRIKLJU ITEV IN UPORABO HR PRIRU NIK ZA MONTA U I KORI TENJE SRB PRIRU NIK ZA MONTA U I KORI ENJE MANUAL DE...

Страница 2: ...uintes Directivas Directiva de g s 2009 142 CE Directiva de Rendimentos 92 42 CEE Directiva de Compatibilidade Electromagn tica 2004 108 CE Directiva Baixa tens o 2006 95 CE Regula o 677 para caldeira...

Страница 3: ...m naponu 2006 95 CE Norme za kondenzacijske kotlove 677 stoga nosi oznaku CE 0694 0694CL6033 Kotao Ciao Green R S I je usagla en sa osnovnim zahtevima slede ih direktiva Direktivom za plinske ure aje...

Страница 4: ...Der Wasserkreis 153 Elektrische Schema 155 Verf gbarer Pumpekraftaufwand 160 Navodila za vgraditelja uporabo 83 91 Sestavni deli kotla 151 Hidravli na napeljava 153 Elektri na shema 155 Prese ni tlak...

Страница 5: ...obstruct the condensate drainage point 2 DESCRIPTION Ciao Green R S I is a Type C wall mounted condensing boiler capable of operating under different conditions through a series of jumpers on the ele...

Страница 6: ...pe is the one suitable for the appliance the piping is clean The gas pipe must be installed outdoors If the pipe goes through the wall it must go through the central opening in the lower part of the t...

Страница 7: ...e drop 45 bend 90 bend 70 m 1 m 1 5 m Straight length means without bends drainage terminals or joints SEALED INSTALLATION TYPE C The boiler must be connected to concentric or twin flue gas discharge...

Страница 8: ...he boiler switches on and the boiler status indicator LED lights up with a fixed green light The digital di splay shows the hot water system temperature the icon to indicate the hot water supply and t...

Страница 9: ...green LEDs and flue gas meter 2 500 Once the cleaning operation has been completed using the special kit sup plied as an accessory the total hour meter will need to be reset to zero as follows switch...

Страница 10: ...external storage tank with thermostat enabled jumper inserted management of an external storage tank with pro be jumpers not inserted fig 37 The boiler foresees jumpers JP5 and JP8 inserted as standar...

Страница 11: ...below 78 C Insert the analyser probe in the ports provided in the air distribution box after removing the screws from the cover fig 40 Press the combustion analysis button a second time to reach the...

Страница 12: ...e appliance and close the gas by the gas cock on the boiler before carrying out any maintenance and cleaning jobs on the boiler Do not clean the appliance or any latter part with flammable substances...

Страница 13: ...mode by turning the mode selector fig 27 within the area marked and the boiler provides hot water for heating and if connected to an external storage tank supplies hot water for DHW If there is a heat...

Страница 14: ...rost 4a LIGHT SIGNALS AND FAULTS To restore operation deactivate alarms Faults A 01 02 03 Position the function selector to OFF wait 5 6 seconds then set it to the required position summer mode or win...

Страница 15: ...return line probe overtemperature Temporary then definitive Outlet return line probe differential alarm Definitive lockout Cleaning the primary heat exchanger A09 flashing 0 5 on 0 5 off flashing 0 5...

Страница 16: ...ressure drops on flue with burner on 2 10 Pressure drops on flue with burner off 0 06 Heating operation Pressure maximum temperature bar 3 90 Minimum pressure for standard operation bar 0 25 0 45 Sele...

Страница 17: ...ss than ppm 180 20 CO2 9 0 9 5 NOx s a lower than ppm 30 20 Flue gas temperature C 65 58 Check performed with concentric pipe 60 100 length 0 85m water temperature 80 60 C DESCRIPTION Methane gas G20...

Страница 18: ...icherheits oder Regelvorrichtungen ohne Genehmigung oder Anweisung des Herstellers zu ver ndern Ziehen l sen und verdrehen Sie nicht die aus dem Kessel austretenden Kabel auch wenn dieser vom Stromver...

Страница 19: ...ehr gut fest 3 5 Kondensatabf hrung Die Anlage muss so gebaut sein dass das vom Kessel produzierte Kon denswasser nicht gefrieren kann z B durch Anbringen einer W rmeiso lierung Wir empfehlen die Inst...

Страница 20: ...LATION BAUART B23P B53P Abgasf hrung 80 mm Abb 20 Die jeweilige Ausrichtung der Abgasf hrung hat nach den installationsspe zifischen Anforderungen zu erfolgen Beachten Sie bei der Installation die in...

Страница 21: ...eschlossenem externem Boiler aktiv Dreht man den Wahlschalter auf das Symbol Sommer Abb 28 wird die herk mm liche Funktion nur Bereitstellung von Brauchwarmwasser aktiviert der Kessel liefert Wasser z...

Страница 22: ...ingeschaltet Endg ltige St rabschaltung Alarm des Wasserdruckw chters A04 eingeschaltet eingeschaltet Endg ltige St rabschaltung Defekt am NTC F hler f r Brauchwas serkreis nur bei Anschluss an einen...

Страница 23: ...rtige Freigabe Alarmverlaufsteuerung P2 0 Nicht ndern Soll Vorlauftemperatur Tshift KT 20 min Soll Au entemperatur Wird die Taste P1 auf dem Display f r mindestens 10 Sekunden gedr ckt gehalten aktivi...

Страница 24: ...ximalwertes 2 w hrend der Einstellung des Mindestwertes 3 w hrend der Einstellung des Maximalwertes f r die Heizung 4 w hrend der Einstellung Langsamz ndung Beenden Sie den Vorgang durch Entfernen der...

Страница 25: ...Wassertemperatur den maximalen Grenzwert von ca 90 C erreicht eingeschaltet 5 WARTUNG Zur Gew hrleistung der Funktions und Leistungseigenschaften des Pro duktes sowie der Einhaltung der geltendes ges...

Страница 26: ...im Laufe des Tages oder der Woche zu steuern 2a Z NDEN DES GER TES Bei jeder Stromzufuhr erscheint am Display eine Reihe von Informationen darunter der Wert des Z hlers des Abgasf hlers C XX siehe Abs...

Страница 27: ...h lt bis die Wassertemperatur 55 C erreicht hat W hrend des Frostschutzzyklusses erscheint auf der Digital anzeige das Symbol Abb 35 Ausschalten ber l ngere Zeitr ume Stellen Sie bei l ngerer Abwesenh...

Страница 28: ...ler Tempor r dann endg ltig Differenzialalarm bei R cklauf Vorlauff hler Endg ltige St rabschaltung Reinigung des Prim rw rmetauschers A09 Blinkzeichen 0 5 eingeschaltet 0 5 ausgeschaltet Blinkzeichen...

Страница 29: ...i gez ndetem Brenner 2 10 Verluste am Kamin bei ausgeschaltetem Brenner 0 06 Heizbetrieb Druck H chsttemperatur bar 3 90 Mindestdruck f r Standard Betrieb bar 0 25 0 45 Auswahlbereich der Temperatur H...

Страница 30: ...G20 CO Gehalt ohne Luft bei maximaler minimaler Leistung unter ppm 180 20 CO2 9 0 9 5 Unteres NOx s a ppm 30 20 Abgastemperatur C 65 58 Nachweis mit konzentrischem Rohr 60 100 L nge 0 85 m Wassertemp...

Страница 31: ...ia Antihielo indica que est activo el ciclo antihielo 65 Temperatura calefacci n agua sanitaria o anomal a de funciona miento PT PAINEL DE COMANDO 1 Led de sinaliza o do estado da caldeira 2 Display d...

Страница 32: ...gezeigt Heizbetrieb Brauchwasserbetrieb 65 Heizwasser Brauchwassertemperatur oder Betriebsst rung SL NADZORNA PLO A 1 Led lu ka statusa kotla 2 Digitalni prikazovalnik temperature delovanja in kod nep...

Страница 33: ...en teploty topn vody 4 Nastaven teploty u itkov vody 5 Hydrometr Digit ln ukazatel 2 popis symbol Pln n za zen tento symbol je z rove signalizov n s poru chov m k dem A 04 Regulace teploty ukazuje v s...

Страница 34: ...ition transformer 15 Detection electrode 16 Delivery NTC sensor 17 Ignition electrode 18 Burner 19 Expansion tank 20 Return NTC sensor 21 Gas nozzle 22 Gas valve 23 Siphon ES Elementos funcionales de...

Страница 35: ...nje 18 Plamenik 19 Ekspanzijska posuda 20 Osjetnik NTC povrata 21 Mlaznica plina 22 Plinski ventil 23 Sifon SRB Funkcionalni delovi kotla 1 Ventil za pra njenje 2 Elektromotorni trokraki ventil 3 Sigu...

Страница 36: ...6 V lvula de desgasifica o inferior 7 Vaso de expans o 8 Sonda NTC retorno 9 Intercambiador prim rio 10 Sonda NTC alimenta o 11 V lvula de desgasifica o superior 12 Separador gua ar 13 V lvula de des...

Страница 37: ...resostat 15 Bojler isporu uje se na zahtjev SRB Hidrauli ni sistem A Izlaz iz bojlera B Povrat bojlera C Potis grejanja D Povrat grejanja E Ulaz hladne vode F Izlaz tople vode 1 Ventil za pra njenje 2...

Страница 38: ...F blu blu marrone marrone marrone blu 7 1 CN9 P A 2 3 1 bianco bianco TERM BOLL O POS viola viola SONDA BOLL rosso rosso t M4 3V 2 N 1 San 3 Risc nero san marrone risc blu 3 1 CN4 AKL JP1 JP2 JP3 JP4...

Страница 39: ...rimario J1 Conector de conexi n VIS MEDIUM Pantalla digital PT Diagrama el ctrico multifilar Blu Blu Marrom Marrone Preto Nero Vermelho Rosso Branco Bianco Violeta Viola Cinza Grigio Rosa Rosa Arancio...

Страница 40: ...ctor de leg tur VIS MEDIUM Display DE Feindr htiger Schaltplan Blau Blu Braun Marrone Schwarz Nero Rot Rosso Wei Bianco Violett Viola Grau Grigio Arancione orange Rosa rosa Giallo Gelb Verde Gr n A be...

Страница 41: ...h teplot JP8 zen vn j skladovac n dr e s aktivovan m termostatem jumper vlo en zen extern ch n dr se aktivovanou sondou jumper nen vlo en LED Led 1 zelen signalizaceprovozn ho stavu nebo stavu p echod...

Страница 42: ...ostat o POS T BOLL o POS 2 F r die Herstellung der Anschl sse von T B T Niedertemperaturthermostat A G allgemeiner Alarm fig 5 A T A 1 2 3 die wei e A Schaltbr cke die sich am Stecker CN11 12 polig be...

Страница 43: ...arcina rezidual pentru instala ia de nc lzire este reprezentat n func ie de debit n graficul 1 Dimensionarea tuburilor instala iei de nc lzire trebuie efectuat in ndu se cont de valoarea sarcinii rezi...

Страница 44: ...sti a vzd lenosti v mm wymiary w mm fig 9 boiler support plate F placa de soporte caldera F placa de suporte da caldeira F kaz n felfogat lemez F cadru de sus inere central F Halteplatte f r Heizkesse...

Страница 45: ...ONFIGURACIJE ISPUSTA MOGU E KONFIGURACIJE ODVODA MO N KONFIGURACE ODV D N SPALINOV CH PLYN C93 B A A rear outlet B max 50 A salida trasera B m x 50 A sa da traseira B m x 50 A h ts kivezet s B max 50...

Страница 46: ...A R A funkci func ie S A R A Funktion S A R A Funkcija S A R A Funkcija S A R A Sustav automatske regulacije ambijenta Funkcija S A R A Funkce S A R A Funkcja SAR Jumper not inserted external storage...

Страница 47: ...ulacioni vijak maksimalna snaga Se izovac roub maxim ln v kon ruba regulacji na maksimum Minimum output adjustment screw Tornillo de regulaci n potencia m nima Parafuso de regula o pot ncia m nima Sza...

Страница 48: ...RAPH 1 THERMOREGULATION CURVES B GRAPHIC 2 WEATHER COMPENSATION CURVE C GRAPHIC 3 PARALLEL NIGHT TIME REDUCTION D OUTSIDE TEMPERATURE C E DELIVERY TEMPERATURE C F DAY temperature curve G NIGHT tempera...

Страница 49: ...EMPERATURA C E TEMPERATURA NA ODVODU C F Klimatska krivulja DAN G Klimatska krivulja NO T80 potrebna vrijednost maksimalne temperature grijanja na standardnim instalacijama jumper pol 1 koji nije umet...

Страница 50: ......

Страница 51: ...Cod 20079711 04 14 Ed 1 Via Risorgimento 13 23900 Lecco LC Italy...

Отзывы: