14
Turn the power and gas feeding to the boiler back on.
Replacing the burner insulating panel
Unscrew the ignition/detection electrode fixing screws and remove it.
Remove the burner insulating panel (
A
) by inserting a blade underneath
the surface (as shown in the figure).
Remove any fixing glue residue.
Replace the insulating panel.
The new insulating panel does not need to be fixed in place with glue as
its geometry ensures perfect coupling with the heat exchanger flange.
Reassemble the ignition / detection electrode using the previously
removed screws and replacing the relative seal.
A
B
C
A
4.1 Programmable parameters
A list of the programmable parameters is given below: USER (level always available) and INSTALLER (access with password 18); for a detailed
explanation of the parameters, refer to paragraph
“4.2 Parameters description”
.
b
Some information might not be available depending on the access level, machine status or system configuration
.
Parameters
Value
Password
level
Value set in
the factory
Personalised
values
min
max
CONFIGURATION
301
HYDRAULIC CONFIG.
0
4
INSTALLER
2
306
MIN FAN SPEED
1.200
3.600
INSTALLER
see technical data table
307
MAX FAN SPEED
3.700
9.999
INSTALLER
see technical data table
308
SLOW IGNITION ADJUSTMENT
MIN
MAX
INSTALLER
see technical data table
309
MAX CH FAN SPEED
MIN
MAX
INSTALLER
see technical data table
310
RANGE RATED
MIN
MAX_CH
INSTALLER
see technical data table
311
AUX OUTPUT
0
2
INSTALLER
0
312
FLUE GAS COUNTER RESET
0
1
INSTALLER
0
HEATING
405
SET PUMP
NOT APPLICABLE ON THIS MODEL
408
OT+ CASCADE
NOT APPLICABLE ON THIS MODEL
409
SCREED HEATER
0
1
INSTALLER
if boiler in OFF
and LT systems
0
410
HEATING OFF
0 min
20 min
INSTALLER
3 min
411
RESET HEATING TIMES
0
1
INSTALLER
0
415
MAIN LT ZONE
0
1
INSTALLER
0
416
MAX TEMP (MAIN ZONE)
MIN TEMP (MAIN ZONE)
HT: 80.5 - LT: 45.0
INSTALLER
HT: 80.5 - LT: 45.0
417
MIN TEMP (MAIN ZONE)
20
MAX TEMP (MAIN ZONE)
INSTALLER
HT: 40 - LT: 20
418
THERMOREGULATION (MAIN ZONE) 0
1
INSTALLER
if ext. probe present
0
419
CURVE SLOPE (MAIN ZONE)
HT: 1.0 - LT: 0.2
HT: 3.0 - LT: 0.8
INSTALLER
only if 418 = 1
HT: 2.0 - LT: 0.4
420
NIGHT-TIME COMP. (MAIN ZONE)
0
1
0
432
BUILDING TYPE
5 min
20 min
5 min
433
EXTERNAL PROBE REACTIVITY
0
255
20
DHW
0
508
MIN DHW TEMP.
37.5 °C
49.0 °C
INSTALLER
37.5°C
509
MAX DHW TEMP.
49.0 °C
60.0 °C
INSTALLER
60.0°C
511
SPEC. DHW FUNCTIONS
0
5
INSTALLER
0
USER PARAMETERS
INSTALLER PARAMETERS
Parameters
Value
Password
level
Value set in
the factory
Personalised
values
min
max
SETTINGS
004
MEASUREMENT UNIT
0
1
USER
0
006
BUZZER
0
1
USER
1
Cleaning th siphon
Remove the siphon as described below:
Switch off the electrical supply by turning the system’s main switch to “Off.
Disconnect the degassing pipe (see figure below)
Disconnect the condensate drain pipe coming from the exchanger (see
figure below).
Remove the clip securing the siphon to its manifold (see figure below).
Remove the siphon from its seat.
Wash the siphon by circulating water from the connection with the
hose nozzle. IN NO CASE USE METAL OR POINTED TOOLS TO
REMOVE DEPOSITS OR RESIDUES INSIDE AS THEY COULD
DAMAGE ITS COMPONENTS.
b
Do not remove the safety shutter and its sealing gasket as their
presence is intended to prevent the escape of burnt gases into the
environment in the event of no condensation.
O
nce the operations have been completed, reassemble the components
by operating in the reverse order to what is described, checking the correct
positioning and integrity of the sealing OR, and replace it if necessary.
b
At the end of the cleaning sequence, fill the siphon with water (see
paragraph ”3.2 First commessioning”) before starting the boiler again.
b
At the end of the siphon maintenance operations, it is recommended
to bring the boiler to condensing mode for a few minutes and to check
for leaks from the entire condensate evacuation line.