Turn the power and gas feeding to the boiler back on.

Replacing the burner insulating panel

 

ƒ

Unscrew the ignition/detection electrode fixing screws and remove it.

 

ƒ

Remove the burner insulating panel (

A

) by inserting a blade underneath 

the surface (as shown in the figure).

 

ƒ

Remove any fixing glue residue.

 

ƒ

Replace the insulating panel.

 

ƒ

The new insulating panel does not need to be fixed in place with glue as 

its geometry ensures perfect coupling with the heat exchanger flange.

 

ƒ

Reassemble the ignition / detection electrode using the previously 

removed screws and replacing the relative seal.

A

B

C

A

4.1  Programmable parameters

A list of the programmable parameters is given below: USER (level always available) and INSTALLER (access with password 18); for a detailed 

explanation of the parameters, refer to paragraph 

“4.2 Parameters description”

.

 

b

Some information might not be available depending on the access level, machine status or system configuration

.

Parameters

Value

Password 

level

Value set in

the factory

Personalised 

values

min

max

CONFIGURATION

301

HYDRAULIC CONFIG.

0

4

INSTALLER

2

306

MIN FAN SPEED

1.200

3.600

INSTALLER

see technical data table

307

MAX FAN SPEED

3.700 

9.999

INSTALLER

see technical data table

308

SLOW IGNITION ADJUSTMENT

MIN

MAX

INSTALLER

see technical data table

309

MAX CH FAN SPEED

MIN 

MAX

INSTALLER

see technical data table

310

RANGE RATED

MIN 

MAX_CH

INSTALLER

see technical data table

311

AUX OUTPUT

2

INSTALLER

0

312

FLUE GAS COUNTER RESET

0

1

INSTALLER 

0

HEATING

405

SET PUMP

NOT APPLICABLE ON THIS MODEL

408

OT+ CASCADE

NOT APPLICABLE ON THIS MODEL

409

SCREED HEATER

1

INSTALLER

if boiler in OFF 

and LT systems

0

410

HEATING OFF

0 min

20 min

INSTALLER

3 min

411

RESET HEATING TIMES

0  

1

INSTALLER

0

415

MAIN LT ZONE

1

INSTALLER

0

416

MAX TEMP (MAIN ZONE)

MIN TEMP (MAIN ZONE) 

HT: 80.5 - LT: 45.0

INSTALLER

HT: 80.5 - LT: 45.0

417

MIN TEMP (MAIN ZONE)

20 

MAX TEMP (MAIN ZONE)

INSTALLER

HT: 40 - LT: 20

418

THERMOREGULATION (MAIN ZONE) 0 

1

INSTALLER

if ext. probe present

0

419

CURVE SLOPE (MAIN ZONE)

HT: 1.0 - LT: 0.2

HT: 3.0 - LT: 0.8 

INSTALLER

only if 418 = 1

HT: 2.0 - LT: 0.4

420

NIGHT-TIME COMP. (MAIN ZONE)

0  

1

0

432

BUILDING TYPE

5 min

20 min

5 min

433

EXTERNAL PROBE REACTIVITY

0

255

20

DHW

0

508

MIN DHW TEMP.

37.5 °C

49.0 °C

INSTALLER

37.5°C

509

MAX DHW TEMP.

49.0 °C

60.0 °C

INSTALLER

60.0°C

511

SPEC. DHW FUNCTIONS

0

5

INSTALLER

0

USER PARAMETERS

INSTALLER PARAMETERS

Parameters

Value

Password 

level

Value set in

the factory

Personalised 

values

min

max

SETTINGS

004

MEASUREMENT UNIT

0

1

USER 

0

006

BUZZER

0

1

USER 

1

Cleaning th siphon

Remove the siphon as described below:

 

ƒ

Switch off the electrical supply by turning the system’s main switch to “Off.

 

ƒ

Disconnect the degassing pipe (see figure below)

 

ƒ

Disconnect the condensate drain pipe coming from the exchanger (see 

figure below).

 

ƒ

Remove the clip securing the siphon to its manifold (see figure below).

 

ƒ

Remove the siphon from its seat.

 

ƒ

Wash the siphon by circulating water from the connection with the 

hose nozzle. IN NO CASE USE METAL OR POINTED TOOLS TO 

REMOVE DEPOSITS OR RESIDUES INSIDE AS THEY COULD 

DAMAGE ITS COMPONENTS.

 

b

Do not remove the safety shutter and its sealing gasket as their 

presence is intended to prevent the escape of burnt gases into the 

environment in the event of no condensation.

 

ƒ

O

nce the operations have been completed, reassemble the components 

by operating in the reverse order to what is described, checking the correct 

positioning and integrity of the sealing OR, and replace it if necessary.

 

b

At the end of the cleaning sequence, fill the siphon with water (see 

paragraph ”3.2 First commessioning”) before starting the boiler again.

 

b

At the end of the siphon maintenance operations, it is recommended 

to bring the boiler to condensing mode for a few minutes and to check 

for leaks from the entire condensate evacuation line. 

Содержание 20183151

Страница 1: ...C 5 0 8 Ciao EN INSTALLER AND USER MANUAL RO MANUAL DE INSTALARE I UTILIZARE...

Страница 2: ...at requirements of the system and in fact it is possible to set the range rated parameter as shown in the specific paragraph After setting the desired output report the value in the table on the back...

Страница 3: ...to harm hu man health and without employing procedures or methods which may damage the environment At the end of its life the product should be not be di sposed of as solid urban waste but rather it...

Страница 4: ...Hz 230 50 230 50 Protection level IP X5D X5D Stop loss W 30 32 Losses at the flue with burner off burner on 0 09 2 80 0 08 2 26 Heating operation Maximum pressure bar 3 3 Minimum pressure for standard...

Страница 5: ...Countries contained in the data plate regardless of the present translation language NOTE with reference to the Delegated Regulation EU No 811 2013 the information in the table can be used for comple...

Страница 6: ...ipe and pick up of combustion air from outside It does not require an air intake point in the installation area The appliance can be installed indoors fig A or outdoors but in a partially protected pl...

Страница 7: ...Ifremovingthesidepanels putthembackintheirinitialposition referring to the adhesive label on its wall b If the front panel is damaged it must be replaced b The noise absorbing panels inside the front...

Страница 8: ...length that can be installed ONLY with class H1 discharge pipes The 50 or 60 or 80 configurations contain Lab test data In the event of installations that differ from the indications in the standard...

Страница 9: ...REQUEST FROM OT CHRONOTHERMOSTAT In this case the delivery setpoint is calculated by chronohermostat on the basis of the external temperature value and the difference between the real ambient temperat...

Страница 10: ...Combustion control sequence 1 4 5 2 3 Installer manual QR fumes adaptor 90 80 70 60 50 40 30 20 10 Temperatura di mandata C Temperatura esterna C 20 15 10 5 0 5 10 15 20 RIDUZIONE NOTTURNA PARALLELA C...

Страница 11: ...minimum fan speed 307 maximum fan speed 308 slow ignition 309 maximum fan speed for heating table 3 MAX NO FAN ROTATIONS METHANE GAS G20 LPG G31 25C f CH DHW 7 000 8 700 6 900 8 500 rpm 30C f CH DHW 7...

Страница 12: ...s 2 sec Res If the correct operating conditions have been restored the boiler will start up again automatically In the presence of a remote control a maximum of 5 consecutive unlocking attempts are av...

Страница 13: ...the heat exchanger with a soft bristled brush DO NOT USE METAL BRUSHES THAT COULD DAMAGE THE COM PONENTS Clean the spaces between the coils using a 0 4 mm thick blade also available in a kit Vacuum a...

Страница 14: ...P MAIN ZONE HT 80 5 LT 45 0 INSTALLER HT 80 5 LT 45 0 417 MIN TEMP MAIN ZONE 20 MAXTEMP MAINZONE INSTALLER HT 40 LT 20 418 THERMOREGULATION MAIN ZONE 0 1 INSTALLER ifext probepresent 0 419 CURVE SLOPE...

Страница 15: ...point value that can be set range 20 C 80 5 C default 80 5 C for high temperature systems range 20 C 45 C default 45 C for low temperature systems NB the value of 416 cannot be lower than 417 417 This...

Страница 16: ...r make sure it is active and adjusted 20 C Bring the boiler to WINTER or SUMMER mode 6 1 Operating status Pressing key 1 the operating type switches cyclically between OFF SUMMER WINTER and then OFF a...

Страница 17: ...output then maintained until the delivery water temperature reaches 35 C the display shows AF1 DHW anti freeze this function is activated if the temperature meas ured by the domestic hot water probe d...

Страница 18: ...clusiv unor persoane calificate profesional a Produc torul nu i asum r spunderea pentru eventualele daune cauzate de nerespectarea indica iilor de mai sus i sau a normelor n vigoare n anumite sec iuni...

Страница 19: ...colectare corespunz toare b De eurile trebuie s fie eliminate f r riscuri pentru s n tatea uman i f r a recurge la proceduri sau la metode care ar putea cauza daune de mediu La sf r itul ciclului de...

Страница 20: ...X5D Pierderi la oprire W 30 32 Pierderi la co cu arz torul stins arz torul aprins 0 09 2 80 0 08 2 26 Func ionare pentru circuitul de nc lzire Presiune maxim bari 3 3 Presiune minim pentru func ionar...

Страница 21: ...punere n func iune NOT conform regulamentului delegat UE nr 811 2013 datele reprezentate n tabel pot fi utilizate pentru completarea fi ei produsului i etichetare n cazul produ selor pentru nc lzirea...

Страница 22: ...er n spa iul de instalare 2 central de tip C13 C13x C33 C33x C43 C43x C53 C53x C63 C63x C83 C83x C93 C93x aparat cu carcas etan cu conduct de evacuare a gazelor arse i aspirare a aerului de ardere din...

Страница 23: ...omponentele interne ndep rta i carcasa dup cum se indic n figur b Dac scoate i panourile laterale pune i le napoi n pozi ia ini ial referindu v la eticheta adeziv de pe peretele s u b Eventuala deteri...

Страница 24: ...51 255 431 7 600 9 300 24 57 285 465 7 700 9 400 27 63 315 500 modelul B 7 400 8 700 0 7 35 190 7 500 8 800 4 17 85 256 7 600 8 900 7 23 115 300 7 700 9 000 10 29 145 340 7 800 9 100 13 35 175 380 7 9...

Страница 25: ...IT 3 4 Setarea termoregl rii Reglarea termic func ioneaz numai cu sonda extern conectat i este activ numai pentru func ia NC LZIRE Pentru activarea TERMOREGL RII proceda i n felul urm tor seta i param...

Страница 26: ...loare de referin de alimentare n ap de 20 C ulterior cresc nd conform tabelului de mai jos ZI OR TEMPERATUR 1 0 20 C 6 22 C 12 24 C 18 26 C 2 0 28 C 12 30 C 3 0 32 C 4 0 35 C 5 0 35 C 6 0 30 C 7 0 25...

Страница 27: ...tur de 95 C arz torul se opre te Reaprinde rea va avea loc atunci c nd aceast temperatur va cobor sub 75 C b Func ia de analiz a arderii este efectuat n mod normal cu vana cu trei c i setat pe nc lzi...

Страница 28: ...unc ionarea n modul de nc lzire alimenta i centrala seta i parametrul 310 Gama nominal Range rated Seta i valoarea maxim de nc lzire rot min i confirma i 0 0 7 rpm 0 0 7 rpm confirmare rpm MAX nregist...

Страница 29: ...bar presiune ridicat veri ca i instala ia semnalizare 4 NTRE INERE I CUR ARE ntre inerea periodic este o obliga ie prev zut de normele n vigoare i este esen ial pentru siguran a randamentul i durata...

Страница 30: ...t continua i cu procedurile de cur are a arz torului Cur a i arz torul cu o perie cu peri moi av nd grij s nu deteriora i panoul izolator i electrodul NU UTILIZA I PERII METALICE CARE POT DETERIORA CO...

Страница 31: ...zactiva avertizarea sonor 0 avertizor sonor buzzer OPRIT 1 avertizor sonor buzzer PORNIT 301 Pentru a seta tipul de con gura ie hidraulic a centralei 0 DOAR NC LZIRE 1 ACM INSTANTANEE FLUXOSTAT 2 ACM...

Страница 32: ...ntru a seta valoarea de referin maxim ce se poate seta pentru nc lzire interval 20 C 80 5 C implicit 80 5 C pentru instala ii cu temperatur ridicat interval 20 C 45 C implicit 45 C pentru instala ii c...

Страница 33: ...3 Ciclul de evacuare a aerului Ulterior interfa a trece la afi area st rii active n acel moment b Regla i termostatul de mediu la temperatura dorit 20 C sau dac instala ia este dotat cu un cronotermos...

Страница 34: ...men inut p n c nd temperatura apei de alimentare ajunge la 55 C pe ecran se afi eaz AF2 antiblocare circulator Pompa de circula ie se activeaz la fiecare 24 de ore timp de 30 de secunde 6 7 Oprirea p...

Страница 35: ...ei c i 4 Traductor presiune 5 By pass automat 6 Sond ap cald menajer 7 Sond tur 8 Termostat limit 9 Schimb tor principal 10 Sond retur 11 Supap inferioar de aerisire 12 Vas de expansiune 13 Pomp de ci...

Страница 36: ...a este deja dotat cu o pomp de circula ie cu conexiuni hidraulice i electrice a c rei performan util disponibil este indicat pe grafic Func ia anti blocare este activ numai c nd centrala termic este a...

Страница 37: ...r on primary circuit S M Temperature flow sensor on primary circuit S F Flue gas sensor T L A Water limit thermostat T P Pressure transducer S S Domestic hot water circuit temperature return sensor F...

Страница 38: ...85 vertical vertical 90 bend 80 125 80 125 14 12 1 1 5 130 curba 90 80 125 adaptor from 60 100 to 80 125 adaptor de la 60 100 la 80 125 adaptor vertical connection 80 100 adaptor vertical conexiune 8...

Страница 39: ...tabelul pentru ac iuni mai imediate bar rpm C 1 88 8 sau or sau or Actions Sequence password entry points 1 7 parameter choice points 8 10 modify and confirm parameter points 11 12a exit without savin...

Страница 40: ...813 2013 Reglementare delegat UE nr 814 2013 CIAO boiler complies with basic requirements of the following Di rectives Regulation UE 2016 426 Efficiency directive Article 7 2 and Annex III of directi...

Отзывы: