6.4 Cable End Installation
Allow a minimum of 1.9cm between the roof and the bottom of
the micro inverter. Also allow 1.3cm between the back of the PV
module and the top of the micro inverter.
WARNING
You must install the micro inverter under the module, out of rain
and sun. Do not mount the micro inverter in a position that
allows long-term exposure to direct sunlight or in a vertical
orientation that allows water to collect in the DC connect recess.
WARNING
If this micro inverter is installed in Australia, Electrical
Installation & Maintenance shall be conducted by licensed
electrician and shall comply with Australia National Rules.
NOTICE
During installation, if the arrays are mono-crystalline or
polycrystalline solar cells, the array should be floating. If the
arrays are thin-film cells, the PV negative pole should be
grounded.
NOTICE
Strip cable jacket 18mm~25mm
Disassemble the Seal, Clamp Ring, Nut, then Insert through the cable
Insert each wires into the holes
Push he cable to the end. Gently try to pull out the cable. It should not be
pulled out
Screw the sealing nut into body tightly with a force of 25 Kgf.cm
Note:
2
2
Wire size: 14AWG (2.08mm ) stardard / 12AWG (3.33mm ) optional
Max current: 15A for 14AWG, 20A for 12AWG
Recommended sealing nut torque: 25Kgf.cm (2.5N.m)
Recommended installation temperature: 20
℃
(60
F
) upward
Avoid oil and gasoline
Waterproof rate: IP67
Cable color: Live: Brown / Black, Neutral: Blue / White, Grounding: Yellow / Green