background image

7

No. Description

Range

Default

Unit

7

type of thermocouple

1 - 5

-

(S, R, K, J, B)

8

external CJC

0 - 1

0

1 = CJC input B

9

toto

1 - 3

0

(°C, °F, K)

type 1:

Thermocouple

No. Description

Range

Default

Unit

7

typ of resistor

1

1

1 = Pt100

8

wiring type

2 - 3

2

2/3-wire

9

temperature unit

1 - 3

1

(°C, °F, K)

typ 2: Resistor

No. Description

Range

Default

Unit

7

signal type

1 - 6

-

0-20mV, 0-50mV, 0-5V,

(change internal Jumpers accordingly)

0-10V, 0-20mA, 4-20mA

8

value for zeropoint

+/- 1999

0

-

9

value for full scale

+/- 1999

0

-

Typ 3: Linear

Input

We reserve the right to make any changes without notice

Operating Instructions TM100 V1.0 (c) 2007 bentrup Industriesteuerungen, D-35463 Fernwald

Accuracy

0.1% refered to full scale

Operating temperature range

-15 to 55°C

Storage temperature range

-25 to 85°C

Batterie lifetime

about 2 years (Alkaline)

Batterie lifetime (rechargable)

about 6 months (NiMh)

Loading time

about 6 hours

Maximum loading cycles

>100

Charging power supply

9V AC, 500mA

Technical Data

No. Description

Range

Default

Unit

7

Carbon

0-9,99

3,01

mol amount * 100

8

Hydrogen

0-19,99

8,02

mol amount * 100

9

non combustables

0-9,99

0,01

percent %

Note: For simple calculation of these 3 values an easy to use EXCEL-worksheet can be
downloaded at www.bentrup.de, service, TM100. This allows to calculate the required
data out of the providers gas specifications (percentage of various combustables).

Typ 4: Circone-

Oxide-Probe

Содержание TM 100

Страница 1: ...TM 100 Operating Instructions Thermocomputer TM100 B A max grad on off inst charging B A ...

Страница 2: ...ow 11 Charging socket rechargable option only Introduction 1 Safety Notes 1 Setup 1 Displaying Temperatures 2 Maximum Values 2 Absolute Maximums 2 Temperature Gradient 2 Cold Junction Temp Battery Voltage 3 TM100 O2 3 Changing Combustion Composites 4 Charging 4 Replacing Batteries 4 Opening TM100 4 Messages Display Codes 5 Error Messages 5 Configuration 6 Parameterlist 6 Technical Data 7 3 4 6 8 1...

Страница 3: ...d this booklet carefully to become familiar with the various features and options of your new instrument Only connect the proper type of thermocouple to the TM100 to avoid damage of kiln and load due to wrong temperature indication When receiving TM100 and sensor as a package it is configured properly Never put your TM100 on top of a kiln Carefully insert the thermocouple plug into the socket 1 TM...

Страница 4: ...ed when replacing batteries There it is an valuable indication in case of warranty disputes damage of kiln bricks etc The current increase of temperature gradient is a value of interest especially when firing gas kilns manually The value is shown in centigrade Celsius per hour positive on increasing temperatures or negative when kiln temperature drops Sudden changes in temperatures very large or v...

Страница 5: ... uses a highly complex combustion formula to calculate all relevant atmosphere parameters oxygen O2 carbon monoxide CO carbon dioxide CO2 air gas ratio lambda To enable the TM100 this calculation some parameters of the combustable need to be entered in the configuration menue The temperature signal of the probe is connected to input A the O2 signal is lead to input B Due to physical laws an oxygen...

Страница 6: ...ks The LED goes off of the battery is fully charged New NiMh type rechargable batteries achieve their maximum capacity lasts for a couple of month s operation after the 3rd loading cycle Depending on usage the supplied batteries last up for years Use size AA Mignon batteries only Replace batteries once the experation date is elapsed although they provide power to avoid chemicals to poor out Carefu...

Страница 7: ...em inside the TM100 Contact us for assistance Error C1 internal check failed no further data acquisition Points to an internal problem of the signal converter Error C2 internal check found values to be inaccurate Might be caused by exceeding temperature range when water entered or electronic damage Error D1 hardware damage Contact us for repair Error D5 TM100 calibration data invalid loss of calib...

Страница 8: ...er no P x while x stands for the parameter number Use keys 6 and 7 to adjust the selected parameter To choose another parameter use keys 4 or 5 again To save changes press and hold key 9 until display reads SET To cancel changes press and hold key 8 until display reads CAn Cancel 6 Configuration inst inst 9 A A 4 B B 5 or A A 4 B B 5 previous next parameter max max 6 grad grad 7 decrease resp incr...

Страница 9: ... 0 c 2007 bentrup Industriesteuerungen D 35463 Fernwald Accuracy 0 1 refered to full scale Operating temperature range 15 to 55 C Storage temperature range 25 to 85 C Batterie lifetime about 2 years Alkaline Batterie lifetime rechargable about 6 months NiMh Loading time about 6 hours Maximum loading cycles 100 Charging power supply 9V AC 500mA Technical Data No Description Range Default Unit 7 Car...

Отзывы: