26
Bentone BG700M,800M,950M
General
7. Determination of gas volume for the
installation
Speciications on natural gas, town gas and biogas vary. For more exact
information please contact the gas distributor.
7.1 Example how to calculate the gas volume (natural gas)
If the barometer height, pressure and temperature of the gas deviate con-
siderably from the normal values this must be taken into account as follows:
f
=
273+t
.
1013,25
273
B+P
u
t
=
Temperature of the gas at the gas meter (15°C)
B
=
Barometer height (945 mbar)
P
u
=
Pressure of the gas at the gas meter (15,0 mbar)
f
=
273+15
.
1013,25
273
945+15
f
=
11,1
The gas volume read on the gas meter actually reads1,11
.
12,9 = 14,4 m
3
/h.
Net caloriic value
Gas quality
kWh/Nm
3
kJ/Nm
3
kcal/Nm
3
Natural gas
10,3
37 144
8 865
Propane
26,0
93 647
22 350
Butane
34,3
123 571
29 492
V
=
Gas volume Nm
3
/h
Q
=
Boiler output 120 kW
H
u
=
Caloriic value of the gas A. 37 144 kJ/Nm
3
, B. 10.3 kWh/Nm
3
η
=
Expected eficiency 90%
Ex. A
v=
Q .3 600
=
120 . 3 600
≈
12,9 Nm
3
/h
H
u
·
η
37 144 . 0,90
Ex. B
v=
120
≈
12,9 Nm
3
/h
10,3 · 0,90
Содержание BG 700
Страница 2: ......
Страница 20: ...20 Bentone BG700M 800M 950M General 5 1 Wiring diagram LFL1...
Страница 40: ......
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 44: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...