9
Bentone
1.1.1
Electrical specification EN 60335-2-102
The burner meets Electrical enclosure class IP20
Type
BG 300
Motor
180W 230V 1.3A 50Hz
Recommended main fuse
motor
C10A
Operating supply
230V 2.1A 50Hz
Sound
82 dBA ± 0.5 dBA
1.1.1
Working area
BG 300
G20,G31 50-200 kW
BG 300
G30 65-200 kW
G25 50-180 kW
-1
0
1
2
3
4
40
60
80
100
120
140
160
180
200
220
kW
G20, G31
mbar
-1
0
1
2
3
4
40
60
80
100
120
140
160
180
200
220
kW
G30, G25
mbar
!
Do not exceed the
working area
Measures according to EN 3746:2010
Option 1 The burner’s noise level can be reduced by equipping a sound
damper. Installation must not affect the air supply to the burner.
Option 2 The burner’s noise level can be reduced by connecting the burner’s
air intake to an air duct with a suitable purge point. Installation must
not affect the air supply to the burner.
Содержание BG 300 M-J/K-IP40
Страница 17: ...17 Bentone 172 515 08 2018 01 02 4 8 Gas nozzle Natural gas Propan Biogas UV detector 2 5 8 0 ...
Страница 36: ...36 Bentone 11 2 Wiring diagram BG300 BP JK IP 40 ...
Страница 46: ...14 EU Declaration of conformity Bentone Gasburners ...
Страница 49: ......
Страница 50: ......
Страница 51: ......
Страница 52: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com ...