41
Bentone
NO.
F
AUL
T
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
POSSIBLE SOLUTION
18
SAFETY
RELA
Y
F
AUL
T
RED
Replace the control unit. Contact reseller/distributor
19
FUEL
V
AL
VE OPEN
RED
Check fuel valve cabling.
The valves may not be fully closed.
20
FLAME LOSS
RED
Visually inspect the flame detector and confirm that the main flame
was
lit during start-up. Check the fuel supply system.
21
WELDED SAFETY
RELA
Y
RED
Replace the control unit. Contact reseller/distributor
.
22
SELF TEST
RED
Replace the control unit. Contact reseller/distributor
.
23
ROM ERROR
RED
Replace the control unit. Contact reseller/distributor
.
24
FLAME LOSS DURING
OPERA
TION
RED
Check the cabling. Check the flame detector
. Check the fuel supply
system.
25
RAM ERROR
RED
Replace the control unit. Contact reseller/distributor
.
26
INTERNAL
F
AUL
T
RED
Replace the control unit. Contact reseller/distributor
.
27
NOT
USED
28
NOT
USED
29
AMBIENT
TEMPERA
TURE
RED
Ambient temperature below -40 °C or above 70 °C
30
ROM ERROR
RED
Replace the control unit. Contact reseller/distributor
.
31
IONISA
TION
SHOR
T
-CIRCUIT
RED
Possible external short-circuit between terminals 23 and 24. Contact
reseller/distributor if the fault persists.
32
TIME LIMIT
EXCEEDED FOR
CONTROL
MODE
RED
30-minute activation time passed.
33
ST
ANDBY
F
ALSE FLAME
RED
False flame detected in Standby mode.
34
NOT
USED
RED
35
INTERNAL
RESET
RED
Internal software reset of control unit. Contact reseller/distributor if
the fault persists.
36
SOFTW
ARE RESET
RED
Internal software reset of control unit. Contact reseller/distributor if
the fault persists.
37
W
AITING
TIME
INPUTS
RED
The system was unable to perform airflow sensor test and/or valve
closure test. Check the cabling. Check the air sensor and/or fuel
valve switch.
38
INTERNAL
RESET
RED
Internal software reset of control unit. Contact reseller/distributor if
the fault persists.
39
SOFTW
ARE RESET
RED
Internal software reset of control unit. Contact reseller/distributor if
the fault persists.
40
HARDW
ARE RESET
RED
Replace the control unit. Contact reseller/distributor if the fault
persists.
41
HARDW
ARE RESET
RED
Replace the control unit. Contact reseller/distributor if the fault
persists.
Содержание BG 300 M-J/K-IP40
Страница 17: ...17 Bentone 172 515 08 2018 01 02 4 8 Gas nozzle Natural gas Propan Biogas UV detector 2 5 8 0 ...
Страница 36: ...36 Bentone 11 2 Wiring diagram BG300 BP JK IP 40 ...
Страница 46: ...14 EU Declaration of conformity Bentone Gasburners ...
Страница 49: ......
Страница 50: ......
Страница 51: ......
Страница 52: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com ...