![Bentone B45-2 RME Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/bentone/b45-2-rme/b45-2-rme_installation-and-maintenance-instruction_2735554016.webp)
16
Bentone B45-2 RME
For installers
4. BASIC SETTINGS
4.1
Examples of basic setting
The nozzle effect is calculated for two-stage burners with two nozzles
(separately for each nozzle).
Nozzle selection in accordance with the table. (See technical data)
Nozzle selection is based on the selected pump pressure and the desired effect.
According to the nozzle table, this provides the following nozzle.
Burner output
Max. 500 kW
Min. 200 kW
Estimated nozzle output min. load
200 kW/10,4 kWh/kg*= 20 kg/h
Estimated nozzle output max. load
(500kW-200 kW)/10,4 kWh/kg*= 30 kg/h
Selected pump pressure
25 bar
Nozzle min. load
3.50 gph
Nozzle max. load
5.00 gph
Power in min. load
20.61 kg/h => 20.61 kg/h x 10 kWh/kg*
= 206 kW
Power in max. load
20.61 kg/h + 29.44 kg/h => 50.05 kg/h x
10 kWh/kg* = 501 kW
* ≈10,4 kwh/kg
Basic settings
The setting value for maximum load 500 kW and minimum load 200 kW
according to the basic settings tables. For the correct procedure when
implementing settings, see 4.2 Nozzle assembly control, brake plate B45-2
and 4.3 Air setting B45-2
Damper motor 2-stage (see technical data ...)
Effects and nozzle selection from example
Nozzle assembly
Stage 2 = 25
Damper motor
Closed = 0°
Blue cam
Min. load = 45°
Orange cam
MV max. load = 60°
Black cam
Max. load = 90°
Red cam
Black cam for MV (solenoid valve) max. load shall be placed between the
cams for min. and max. load. The positions of MV max. load are determined
by the boiler's characteristics when switching between stages. By default,
the black cam is placed between the orange and red cams.
Basic settings should only be seen as setting values to get burner to start
and establish a lame. Once the burner has started and established a lame,
it will be necessary to adjust the settings so that they are adapted to the
installation in question and the fuel used at the time.
Содержание B45-2 RME
Страница 2: ...2 Bentone B45 2 RME ...
Страница 25: ...25 Bentone B45 2 RME For installers ...
Страница 30: ...30 Bentone B45 2 RME For installers 7 ELECTRICAL EQUIPMENT 7 1 Wiring diagram LMO24 255 ...
Страница 35: ...9 DECLARATION OF CONFIRMITY ...
Страница 36: ......
Страница 38: ......
Страница 39: ...M A C R M M ...
Страница 40: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com ...