6.2.1
Filter replacement
Cut off the power and shut off the oil.
Remove the pump cover with the aid of a 4 mm Allen key. If necessary a
screwdriver may be used between the cover and the housing to carefully
pry the cover loose. Replace the old i lter by a new one. Replace the cover,
tighten lightly.
Do not forget to replace the gasket.
Open the oil supply and switch on the power.
6.2.2
One-pipe system
Conversion to one-pipe system
Remove the return plug (8), plug the return line (9) with the metal plug (7) G 1/4”.
6.2.3
Two-pipe system
Conversion to two-pipe system
Remove the metal plug (7) G ¼”, i t the return plug (8) in the return line (9).
Return plug are not included in products with one-pipe system, separately
sold.
6.2.4
Solenoid valve
4
7
8
5
1
6
9
3
3
2