15
Bentone B45-2 RME
For installers
A
A
3.8
Burner installation
1.
Separate the burner body and the l ange.
2.
Remove the brake plate from the oil pipe.
3.
Install the selected nozzle. (See Technical data)
4.
Install the brake plate on the oil pipe
5.
Remove the burner tube from the l ange.
6.
Install the l ange with gasket on the boiler.
7.
Install the burner tube on the l ange. Make sure that the hole in the
front of the burner tube pipe is pointing down. This allows any drops of
oil to l ow out.
8.
Insulate between the burner and boiler door to reduce radiated heat.
9.
Slide the burner body on the guides.
10. Lock the burner body using with the nut/nuts.
11. Connect the oil hoses to the pump.
12. Connect burner electrically.
3.9
Check oil line seals
Once the burner has been installed and commissioned, the seals of the
various coupling elements should be checked (A).
When a leak is detected, it is usually sufi cient to tighten the coupling
element that is leaking.
!
If the burner tube must be installed from the inside the boiler, it
must be possible to open the boiler or have a hinged l ange that
is designed so that it can be reconnected with the burner tube
installed.
!
Recommended thread sealer.
(Loctite 5188, 5400)
Содержание B45-2 RME
Страница 2: ...2 Bentone B45 2 RME ...
Страница 25: ...25 Bentone B45 2 RME For installers ...
Страница 30: ...30 Bentone B45 2 RME For installers 7 ELECTRICAL EQUIPMENT 7 1 Wiring diagram LMO24 255 ...
Страница 35: ...9 DECLARATION OF CONFIRMITY ...
Страница 36: ......
Страница 38: ......
Страница 39: ...M A C R M M ...
Страница 40: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com ...