background image

171 305 36  09-01

GENERAL INSTRUCTIONS

General rules

The installation of an oil burner should 

be carried out in accordance with local 

regulations. The installer of the burner 

must therefore be aware of all regula-

tions relating to oil and combustion.

Only oil suitable for the burner should 

be used and then in combination with 

a suitable oil fi lter before the oil pump 

of the burner.

If the burner is replacing an existing 

burner make sure that the oil fi lter is 

replaced or cleaned. The installation 

must only be undertaken by expe-

rienced personnel. Care should be 

taken by the installer to ensure that no 

electrical cables or fuel/gas pipes are 

trapped or damaged during installation 

or service/maintenance.

Installation instructions

General installation instructions ac-

company the burner and should be 

left in a prominent place adjacent to 

the burner.

Adjustment of burner

The burner is from the factory pre-set 

to an average value that must then 

be adjusted to the boiler in question. 

All burner adjustments must be 

made in accordance with the boiler 

manufacturer´s instructions.These 

must include the checking of fl ue gas 

temperatures, average water tem-

perature and CO

2

 or O

2

 concentration. 

To adjust the combustion device, start 

by increasing the air volume and the 

nozzle assembly somewhat.When the 

burner starts it is  burning with excess 

air and smoke number 0. Reduce the 

nozzle assembly adjustment until 

soot occurs, and then increase the 

adjustment to make the soot disap-

pear again. Then the volume of air 

is reduced until soot occurs and in-

creased again to reach a combustion 

free of soot.

By this procedure an optimum adjust-

ment is obtained. If larger nozzles are 

used the preadjustment of both the 

air volume and the nozzle assembly 

must be increased.

A whistling sound may be heard 

which can be eliminated or reduced 

as follows: Increase the nozzle as-

sembly adjustment somewhat. The 

CO

2

-content and consequently the air 

volume will then be reduced.

Oil supply

The oil line should be dimensioned 

in accordance with the pump 

manufacturer´s instruction. In the 

suction line to the burner a fi lter should 

be mounted to prevent any particles 

in the oil from reaching the burner. 

If the installation consists of several 

burners each one should have its own 

suction line from the tank or a circula-

tion system should be used. 

The temperature in the oil line should 

be kept as constant as possible. Avoid 

exposing the line to excessive cold 

which may cause blockages of paraffi n 

deposits.

The oil pipe and electric cable should 

be  fi tted  so  that  the  burner  can  be 

placed on the fl oor for inspection of 

the combustion device.

Condensation in chimney

A modern burner works with less ex-

cess air and often also with smaller 

nozzles than older models. This 

increases the effi ciency but also the 

risk of condensation in the chimney. 

The risk increases if the area of the 

chimney fl ue is too large. The tempera-

ture of the fl ue gases should exceed 

60°C measured 0,5 metres from the 

chimney top.

Measures to raise the temperature:

Insulate the chimney in cold attics

Install a tube in the chimney

Install a draught regulator (dilutes the 

fl ue gases during operation and dries 

them up during standstill)

Increase the oil quantity

Raise the fl ue gas temperature by re-

moving turbulators, if any, in the boiler.

Pump adjustment

See separate description.

Maintenance

The boiler/burner should be examined 

regularly for any signs of malfunction 

or oil leakage.

Содержание B30A2.2H

Страница 1: ...Providing sustainable energy solutions worldwide 178 066 52 1 2016 04 18 Installation and maintenance instruction B30A2 2H B30A2 2HL...

Страница 2: ......

Страница 3: ...Cover inspection glass 10 Switch I II 11 Switch I 0 12 Fan wheel 13 Motor 14 Nozzle assembly adjustment 15 Blast tube 16 Photo cell 17 Adjustment device 18 Indication air damper 19 Connecting pipe St...

Страница 4: ...range and nozzles recommended The net calori c value of 11 86 kWh kg for light oil has been used 188 415 B 372 108 108 220 303 281 160 190 108 35 Recommended nozzle Because of different boiler types e...

Страница 5: ...e an optimum adjust ment is obtained If larger nozzles are used the preadjustment of both the air volume and the nozzle assembly must be increased A whistling sound may be heard which can be eliminate...

Страница 6: ...e an optimum adjust ment is obtained If larger nozzles are used the preadjustment of both the air volume and the nozzle assembly must be increased A whistling sound may be heard which can be eliminate...

Страница 7: ...ge Set the operating switch S2 on low capacity I Loosen the screw A and turn the damper to the position wan ted Tighten the screw A again Second stage Set the operating switch S2 on high capacity II S...

Страница 8: ...at the main switch and cut off the oil supply Open the cover and disconnect the connecting pipes by loosening screw A and nut B Service of burner head 171 305 47 09 01 1 Loosen or swing out the burne...

Страница 9: ...l burner control LMO24 255 Wiring diagram ELECTRIC EQUIPMENT 1 3 1N 50 60 Hz 230 V If the boiler is not equipped with wired contacts connect the enclosed contacts to terminals X4 and X6 in accordance...

Страница 10: ...on till the prepurge period expires and the solenoid valve 1 opens 2 2 Solenoid valve 1 opens Oil mist is formed and ignited The photocell indicates a ame 3 The safety time expires a If no ame is est...

Страница 11: ...the problem by pressing and holding the reset button for 3 seconds The number of ashes below is repeated with a pause in between 2 ashes No ame signal when safety time expires 4 ashes False light dur...

Страница 12: ...length in metres at a nozzle capacity of 9 5 Gph Max permissible pres sure at the suction and pressure side is 2 0 bar Components 1 Nozzle outlet G 1 8 Stage 2 2 Pressure gauge port G 1 8 3 Nozzle out...

Страница 13: ...it is assured by a bleed at on the piston In one pipe operation a high pressure connection must be loosened until the air is evacuated from the system Cut Off The solenoid valves of the A2L pump are o...

Страница 14: ...93 9 71 115 99 10 24 121 104 10 73 127 109 3 00 9 98 118 102 10 59 126 108 11 16 132 114 11 71 139 119 3 50 11 65 138 119 12 35 146 126 13 03 154 133 13 66 162 139 4 00 13 31 158 136 14 12 167 144 14...

Страница 15: ...1 21 133 114 11 67 138 119 12 11 144 123 12 53 148 128 3 00 12 23 145 125 12 73 151 130 13 21 157 135 13 67 162 139 3 50 14 27 169 145 14 85 176 151 15 42 183 157 15 95 189 163 4 00 16 31 193 166 16 9...

Страница 16: ...of magnetic valve Burner fails to start Lamp not lit Motor runs Burner runs to lockout Fuse has blown Appliance thermostat has not reset Appliance overheat device has operated Control relay or photoce...

Страница 17: ...sont conformes aux normes et aux documents normatifs suivants et satisfont aux crit res applicables des directives CE suivantes Dokument EN 267 EN 60335 EU direktiv EU Directives EU Direktiven CE suiv...

Страница 18: ...he burner will not start Press the reset button on the relay Check that the thermostats are correctly adjusted Don t forget the room thermostat check that any fusesare intact and main switch is on If...

Страница 19: ......

Страница 20: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...

Отзывы: