8
Bentone
2.5
Basic settings - HVO/XTL
Measurements according to EN 15036-1:2006
Alt.1 The noise level of the burner can be reduced by equipping the burner
with silencer. Installation must be done so it does not prevent air supply
to the burner.
Alt.2 The burner’s noise level can be reduced by connecting the burner’s air
intake to the air duct that opens into an appropriate location. Installation
must be done so it does not prevent air supply to the burner.
B 30 A2.2
Main supply
1)
230V, 1~, 2.6/3.1A, 50Hz, IP20
Max fuse rating
8A
El
min
preheater excluded
1.30A, 281W
El
max
preheater excluded
1.40A, 297W
P
SB
0
NO
X
-class
4
NO
X
(GCV) preheater excluded 119mg/kWh
Noise level
82dBA
1)
Max operating current, see data plate.
2.6
Technical specification
0
20
40
60
80
100
0
2
4
6
8
10
55
85,2
115
144
175
160303-600
kW
Air settings
Nozzle assembly
Scale
1
Burner output
Air
2
<
˚
1
Scale nozzle assembly and air damper without damper motor.
2
Settings air damper with damper motor.
Flame signal
When operating at high power or low air excess and HVO/XTL is used as fuel,
the flame signal may deteriorate (blue flame), the signal lamp in the reset
button flashes green.
By lowering the air velocity or changing the flame detector to QRC1 A1, the
flame signal can be improved.
Содержание B 30 A2.2
Страница 18: ...18 Bentone 165 105 03 2 4 8 Handling and lifting instruction The lifting aid are available as spare parts...
Страница 42: ......
Страница 43: ......
Страница 44: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone com...