Under these conditions the detector will notify the alarm condition when the predetermined fixed temperature is reached.
In the event of the thermistor detecting a fast rate of change of temperature, the sensitivity of the CO detector is enhanched.

WIRING

The detector circuits requires a positive and negative supply and these are wired to terminals L1 and L on the base
(Polarity insensitive). Base terminal L2 is connected to base terminal L1 when the detector is fitted to provide continuity
monitoring through the detector. Base terminals L2 and L provide outputs to the next detector or EOL device.
In case of alarm the detector comunicate the state to control device by sinking from the supply leads an extra current
according to the figure 

3

, for restoring from an alarm condition the power has to be removed for 2-5 seconds.

A drive is provided for a remote indicator connected between and terminal R, therefore at a detector where
remote indicator is connected, the polarity of the supply must be known.

MAINTENANCE

The lenght of time between service for each detector will depend upon the environment into which they are installed.
It is recommended to Inspect, test and clean the detector at least annually.
The detector must be removed for service replacement at least  every 5 years.

R

L.R.

E.O.L.

L2

L

R

L2

L

L1

L1

R

L2

L

L1

Fig. 2 

Connection diagram.

Fig. 3 

Alarm load.

Fig. 4 

Fit the detector unit onto the MUB base (as per figure ) then twist clockwise.

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

0

2

4

6

8

10

12

14

16

18

20

22

24

26

28

30

32

34

Detector voltage (V)

C

u

rr

e

n

(m

A

)

+

 The  Manufacturer reserves the right to change the technical specifications of this product without prior notice.

Содержание 601CH

Страница 1: ...do di carbonio a contatto con l elettrodo riesca ad essere ossidato In questo modo la quantità di monossido trasferito nella cella è direttamente proporzionale alla concentrazione esterna ed indipendente dalla velocità dell aria Rivelatore termovelocimetrico conforme alle normative EN54 5 A1R Il rivelatore 601CH è dotato di due termistori a coefficiente di temperatura negativo uno esposto all aria...

Страница 2: ...sibile collegare un indicatore di segnalazione remota tra il morsetto R ed il morsetto positivo pertanto è importante conoscere la polarità dei morsetti nel rivelatore dove viene collegato l indicatore remoto MANUTENZIONE La lunghezza dell intervallo di tempo tra due manutenzioni successive per ogni rivelatore dipende dall ambiente nel quale esso è installato E raccomandata una ispezione test e pu...

Страница 3: ...re that all carbon monoxide in the area proximate to the sensing electrode is continuosly oxidised This means that the rate of transport of carbon monoxide to the cell is directly proportional to the external concentration and independent of air speed Rate of Rise Thermal detector according to standards EN54 7 A1R In the 601CH detector two negative tempearture coefficient thermistors are used one ...

Страница 4: ...r restoring from an alarm condition the power has to be removed for 2 5 seconds A drive is provided for a remote indicator connected between supply and terminal R therefore at a detector where remote indicator is connected the polarity of the supply must be known MAINTENANCE The lenght of time between service for each detector will depend upon the environment into which they are installed It is re...

Страница 5: ...ment d air DÉTECTION THERMOVÉLOSYMÉTRIQUE EN ACCORD AVEC LA NORME EN54 7 A1R Le détecteur 601CH utilise 2 sondes de température la première est exposée à l air ambiant et l autre thermiquement décalé à intérieur du boîtier du détecteur Si la température de l air autour du détecteur varie rapidement une différence sera établie entre les 2 sondes et le relais d alarme sera switcher Si la température...

Страница 6: ...ité votre installation serait Hors Norme MAINTENANCE Le délai entre 2 maintenances pour chaque détecteur dépendra de l environnement dans lequel il a été installé Toutefois il est recommandé d inspecter tester et nettoyer le détecteur une fois par an Le détecteur doit être faire l objet d une maintenance de reconditionnement tous les 5 ans Fig 2 Principe Câblage Le fabriquant se réserve le droit d...

Страница 7: ......

Страница 8: ...ISTISBL3601CH 0 0 010305 P7 0 ...

Отзывы: