Profibus Card
Data Structures
6.2 Soft Starter Monitoring I/O Data Structure
Master > Slave output bytes are structured as follows.
Byte 2
Operating data request (Data request numbers 1 to 16)
Slave > Master input bytes, in response to an operating data request, are structured as
follows:
Byte 2
Echo data request number
Byte 3
Bits 7 to 1
Reserved
Bit 0 = 1: Invalid data request number
Byte 4
Data value (high byte)
Byte 5
Data value (low byte)
NOTE
An invalid data request number will result in the invalid data request number bit
being set = 1.
Data values are defined as follows:
Data
Request
Number
Description
Bits
Details
0
Reserved
1
Product information 0 to 7
Reserved
8 to 15 Product type code:
12 = basic model
13 = advanced model
2
Starter state
0 to 3
1 = Ready
2 = Starting
3 = Running
4 = Stopping (including braking)
5 = Not ready (restart delay, restart temperature
check, run simulation, reset input is open)
6 = Tripped
7 = Programming mode
8 = Jog forward
9 = Jog reverse
4
0 = Negative phase sequence
1 = Positive phase sequence (only valid if
bit 6 = 1)
5
1 = Current exceeds FLC
6
0 = Uninitialised
1 = Initialised
7
1 = Communication error between device and
soft starter
8 to 15 See
Trip Codes
on page 9
Instructions
7