6.3 Soft Starter Programming I/O Data Structure
The Soft Starter Programming I/O Data Structure allows the user to upload (read) and
download (write) soft starter parameter values over the network.
CAUTION
Do not change the default values of the Advanced parameters (parameter group
20). Changing these values may cause unpredictable behaviour in the soft starter.
Outputs
Master > Slave output bytes are structured as follows.
Byte
Bits
Details
3
0 to 7
Parameter number to read/write
4
0
Reserved
1
1 = Read parameter
2
1 = Write parameter
3 to 7
Reserved
5
0 to 7
High byte parameter value to write to soft starter/ zero data values
for read
6
0 to 7
Low byte parameter value to write to soft starter/ zero data values
for read
Inputs
Slave > Master input bytes are structured as follows.
Byte
Bits
Details
6
0 to 7
Echo parameter number
7
0
1 = Invalid parameter number
1
1 = Invalid parameter value
2 to 7
Reserved
8
0 to 7
High byte parameter value read from soft starter
9
0 to 7
Low byte parameter value read from soft starter
6.4 Trip Codes
Trip Code Description
0
No trip
1
Excess start time
2
Motor overload
3
Motor thermistor
4
Current imbalance
5
Frequency
6
Phase sequence
7
Instantaneous overcurrent
8
Power loss
9
Undercurrent
10
Heatsink overtemperature
11
Motor connection
12
Input A trip
Instructions