Configuration
Profibus Card
5
Configuration
Import the latest .gsd file into your Master configuration tool. This file is available from your
supplier.
If your Master uses on-screen icons, two graphic bitmap files are available from the
website. SSPM_N.bmp indicates normal mode. SSPM_D.bmp indicates diagnostic mode.
5.1 Profibus Address
The network address for the card must be set via the soft starter (parameter 12G
Profibus
Address
). For details on how to configure the soft starter, see the soft starter user manual.
NOTE
The Profibus Card will read the network address from the soft starter when control
power is applied. If parameters are changed in the starter, control power must be
cycled for the new values to take effect.
5.2 Enabling Network Control
The soft starter will only accept commands from the Profibus Card if parameter 1A
Command Source
is set to 'Network'.
NOTE
If the reset input is active, the starter will not operate. If a reset switch is not
required, fit a link across terminals 10, 11 on the soft starter.
If the Profibus network fails, the device will leave data exchange mode after the network
watchdog timeout period has expired. This timeout period is set at the Master configuration
tool.
A Communication Timeout parameter in the GSD file sets how soon after this event the soft
starter will be forced into a trip state.
The user can adjust the Communication Timeout parameter in the GSD file to any setting
between 0 and 100 seconds. The default setting is 10 seconds.
NOTE
If the Communication Timeout parameter is set to 0, the current state of the soft
starter will remain unchanged on a network failure. This gives the user the option of
operating the soft starter via local control, but is NOT failsafe.