60HZ Models
Output Capacity
5 - 25.0 KVA
Maximum Number of Modules
The inverter cabinet supports a maximum of 5 inverter modules
Nominal Bypass AC Input
120 VAC
208, 220, 240, 480VAC
# of Bypass AC Phases
1
2
Bypass AC Input Wiring
L, N, PE
L1, L2, PE
Nominal DC Input
120VDC
DC Input Range
-15%, +20%
Reflected DC Ripple, 120VDC
< 2mV reverse smoothing
< 5% RMS
Nominal AC Output Voltage
120VAC
120VAC
Optional AC Output Voltage
120/240VAC
120/240VAC
Output Voltage Regulation
+/- 5% for all combinations of line, load and temperature
Output Power Factor
0.7 lagging to 0.8 leading
Output Voltage Waveform
PWM sine-wave
Output Crest Factor
2:8:1
Output Voltage Distortion
< 3.5% @ 100% rated linear load
Output Overcurrent Protection
Electronic current limiting
Overload Rating (Inverters)
200% for approx. 75 cycles (1.25 seconds)
Overload Rating (Static Bypass)
500% for 100ms
System Operating Efficiency
> 89% (typical)
Frequency Stability
+/- 0.1% free running, +/- 3% when AC present
Module Capacity
5.0kVA/4.0kW
Static Switch Transfer Time
< 2ms
Cooling
Temperature controlled fans
Maintenance Bypass Switch
Standard make-before-break mechanically interlocked switch provided on all models
Remote Alarming
(1) Form-C Summary Alarm, Optional Relay Card (8 Alarms)
LED indicators (Inverter Modules)
Output present, fault, overload, AC synchronized, parallel operation
LED indicators (Static Bypass Switch)
Power flow diagram, normal, fault, ac present, dc present, overload, load on bypass, load on
inverter
Metering
(4) segment LCD display switchable between output voltage and current
Cabinet Dimensions (H x W x D)
84” (2134 mm) x 23.6” (600 mm) x 23.6” (600 mm)
Radio Interference
EN 55022, class B
Altitude
6000 ft (1800 m), 13, 000 ft. (4000 m) at 30°C
Operating Temperature
-5 to +40° C
Operating Humidity
0-95% non-condensing
Module Data
5.0kVA
Power Rating
5000VA/4000W
Nominal Input Current 120 VDC
38.0A
Maximum Input Current 120VDC
44A
Output Current NOM 120VAC
41.6A