15

Sair

If it is memorized with the SAIR radio function, the partial opening width 
is adjusted through the second channel of the transmitter. The TCA 
automatic closure has no effect on the partial opening.
Partial opening is allowed only if the door is completely closed 
The value is expressed in centimetres.

3-250-(5)

PMo

Adjustment of amperometric sensor sensitivity during normal speed in 
opening*
1: maximum sensibility - 99: minimum sensibility 

1-99-(10%)

PMC

Adjustment of amperometric sensor sensitivity during normal speed in 
closing*
1: maximum sensibility - 99: minim sensibility 

1-99-(10%)

TLS

*UJTBDUJWBUFEXJUI"69QBSBNFUFS

The activation time of the service light is adjusted.

1-240-(60s)

SPIN

It regulates the tension belt release when the operator arrives to the me-
chanical stop in closing

0-20-(3)

AUX1

It selects the operating mode of the AUX 1 output:
0: Open gate indicator light. The light is off when the door is closed, flashes 
with moving door and is on with open door. 
See wire diagram.
1: Second radio channel. The output is controlled by the radio channel of 
the built-in receiver (see RADIO Menu).
2: Service light.  The contact closes for the time preset with TLS parame-
ter. The countdown starts at the inception of the opening operation.
3: Area light.  The contact closes in the opening phase and remains closed 
for the entire TCA time. It opens only with closed door. 

0-3-(3)

* ATTENTION: A wrong formulation of these parameters can be dangerous. 
Respect the regulations in force! 

LOGICS (

LOGI

)

MENU

FUNCTION

DEAFULT

MEMO

TCA

Enables or disables automatic closing
On: automatic closing enabled
Off: automatic closing disabled

(OFF)

IBL

Enables or disables multi-flat function.
On: multi-flat function enabled. The step-by-step and perdestrian 
commands have no effect during the opening phase.
Off: multi-flat function disabled.

(OFF)

IBCA

During the TCA phase, the PP controls are enabled or disabled.
On: PP controls are disabled.
Off: PP controls are enabled.

(OFF)

SCL

The rapid closure is enabled or disabled. It can be activated only if 
TCA:ON
On: enabled rapid closure. With open gate, the photocell activation causes 
the automatic closure after 3 s. 
If the photocell is activated during the opening phase, the operation is 
completed and closure starts after 3s 
Off: disabled rapid closure.

(OFF)

PP

5IFPQFSBUJOHNPEFPGi111VTICVUUPOwBOEPGUIFUSBOTNJUUFSBSF

selected.
On: Operation : OPEN > CLOSE > OPEN >
Off: Operation: OPEN > STOP > CLOSE > STOP >

(OFF)

PRE

Forewarning flashing light enabled or disabled.
On: enabled forewarning flashing light. The flashing light is activated 3 s 
before the starting of the motor.
Off: disabled forewarning flashing light.

(OFF)

Содержание CP.J4 ESA

Страница 1: ...L8542920 04 2011 rev 0 CP J4 ESA UNIONE NAZIONALE COSTRUTTORI AUTOMATISMI PER CANCELLI PORTE SERRANDE ED AFFINI...

Страница 2: ...00mA max 24Vac dc SCA Service Light R A D I O F1 T A COM P P STOP PHOT OPEN CLOSE BAR BAR SCA SCA BLINK BLINK 24V 24V N L F2 1AT 230V F2 2AT 115V MOT L1 AUX N1 L1 N1 0V OUT ENC M M ENC ANT ANT SHIELD...

Страница 3: ...BLINK BLINK 24V 24V 8K2 4 2 3 SCA AUX1 0 BAR BAR SCA SCA BLINK BLINK 24V 24V SCA 24Vac 3W max 24Vac 1A max AUX1 1 II CH RADIO BAR BAR SCA SCA BLINK BLINK 24V 24V AUX1 2 SERVICE ZONE LIGHT Service Lig...

Страница 4: ...ssential characteristics of the product unchanged the manufacturer reserves himself the right to bring any change of technical constructive or commercial character without undertaking himself to updat...

Страница 5: ...push button Normally Open contact A timer clock can be connected for openings according to timeframes PHOT Photocell Input photocell is activated in the closing phase STOP STOP STOP button input N C...

Страница 6: ...red values in the programming menus described below The parameters menu allows you to assign a numerical value to a function in the same way as a regulating trimmer The logic menu allows you to activa...

Страница 7: ...ion of the opening operation 3 Area light The contact closes in the opening phase and remains closed for the entire TCA time It opens only with closed door 0 3 3 ATTENTION A wrong formulation of these...

Страница 8: ...BWJOHT GVODUJPO JT BDUJWBUFE PS EFBDUJWBUFE On Enabled energy savings After around 10 sec of non operation the po wer supply is cut off from the accessory output and the system switches to stand by Of...

Страница 9: ...paragraph SELF LEARNING PASSWORD CODE It allows to type in an access protection code to the programming of the control unit A four character alphanumeric code can be typed in by using the numbers fro...

Страница 10: ...ring the door leaf stoke If the error occurs during self learning of the radio transmitters this means that the memory of the receiver is no longer able to receive other transmitters or the transmitte...