15
Sair
If it is memorized with the SAIR radio function, the partial opening width
is adjusted through the second channel of the transmitter. The TCA
automatic closure has no effect on the partial opening.
Partial opening is allowed only if the door is completely closed
The value is expressed in centimetres.
3-250-(5)
PMo
Adjustment of amperometric sensor sensitivity during normal speed in
opening*
1: maximum sensibility - 99: minimum sensibility
1-99-(10%)
PMC
Adjustment of amperometric sensor sensitivity during normal speed in
closing*
1: maximum sensibility - 99: minim sensibility
1-99-(10%)
TLS
*UJTBDUJWBUFEXJUI"69QBSBNFUFS
The activation time of the service light is adjusted.
1-240-(60s)
SPIN
It regulates the tension belt release when the operator arrives to the me-
chanical stop in closing
0-20-(3)
AUX1
It selects the operating mode of the AUX 1 output:
0: Open gate indicator light. The light is off when the door is closed, flashes
with moving door and is on with open door.
See wire diagram.
1: Second radio channel. The output is controlled by the radio channel of
the built-in receiver (see RADIO Menu).
2: Service light. The contact closes for the time preset with TLS parame-
ter. The countdown starts at the inception of the opening operation.
3: Area light. The contact closes in the opening phase and remains closed
for the entire TCA time. It opens only with closed door.
0-3-(3)
* ATTENTION: A wrong formulation of these parameters can be dangerous.
Respect the regulations in force!
LOGICS (
LOGI
)
MENU
FUNCTION
DEAFULT
MEMO
TCA
Enables or disables automatic closing
On: automatic closing enabled
Off: automatic closing disabled
(OFF)
IBL
Enables or disables multi-flat function.
On: multi-flat function enabled. The step-by-step and perdestrian
commands have no effect during the opening phase.
Off: multi-flat function disabled.
(OFF)
IBCA
During the TCA phase, the PP controls are enabled or disabled.
On: PP controls are disabled.
Off: PP controls are enabled.
(OFF)
SCL
The rapid closure is enabled or disabled. It can be activated only if
TCA:ON
On: enabled rapid closure. With open gate, the photocell activation causes
the automatic closure after 3 s.
If the photocell is activated during the opening phase, the operation is
completed and closure starts after 3s
Off: disabled rapid closure.
(OFF)
PP
5IFPQFSBUJOHNPEFPGi111VTICVUUPOwBOEPGUIFUSBOTNJUUFSBSF
selected.
On: Operation : OPEN > CLOSE > OPEN >
Off: Operation: OPEN > STOP > CLOSE > STOP >
(OFF)
PRE
Forewarning flashing light enabled or disabled.
On: enabled forewarning flashing light. The flashing light is activated 3 s
before the starting of the motor.
Off: disabled forewarning flashing light.
(OFF)