RUN SELF-LEARNING  AND ANTI-CRUSHING  DEVICE SETTING 

When operator assembly and wiring is completed, parameters and logic are programmed, self learning allows the operator 
to learn the stroke and self adjusts amperometric sensor thresholds.
First of all place the opening and closing mechanical stops:
-   manually  release  the  door  and  completely  close  it.  Place  the  closing  mechanical  stop  in  the  closed  position  on  the 

driving carrier and fix it.

-   completely open the door. Place the opening mechanical stop in the open position on the driving carrier and fix it.
For further information, please refer to the operator (JM4) manual.
Now the opening and closing positions can be memorized:
Enter  menu Auto and press the button < PGM > , PUSH will be displayed. 
Press again the button < PGM >: self-learning is beginning: PRG will be displayed, and the control panel completes at 
least two opening/closing cycles. 
When the procedure is completed OK will be displayed. 
This procedure can be followed from any position of the gate/door leaf and can be stopped at any moment by pressing 
keys <+> and <-> at the same time, or through the activation of STOP/PHOTO/PP/CLOSE inputs.
At the end of the self-setting, the PMO and PMC parameters, if previously modified, are shown as default values. If the 
procedure is not successful, the wording ERR appears. Check that no obstacles or frictions are present.
IMPORTANT: The torque value also includes changes in the  resistance of the door during movement. The entire stroke 
is divided in 64 opening points and 64 closing points where the optimal operating torque is read and memorised by the 
control unit.

PROGRAMMING

The programming of the various functions of the control unit is carried out using the LCD display on the control unit and 
setting the desired values in the programming menus described below.
The parameters menu allows you to assign a numerical value to a function, in the same way as a regulating trimmer.
The logic menu allows you to activate or deactivate a function, in the same way as setting a dip-switch.
Other special functions follow the parameters and logic menus and may vary depending on the type of control unit or the 
software release.

USE OF PROGRAMMING KEYS

Press <PG> key to gain access to the Main Menu (PAR>>LOG>>RADIO>>...). These keys can be selected by pr 
and – keys.
Select the Main menu with  <PG> key to enter the desired Function Menu .

t*GJTQSFTTFEUIF'VODUJPO.FOVDBOCFTDSPMMFEGSPNUPQUPCPUUPN
t*GJTQSFTTFEUIF'VODUJPO.FOVDBOCFTDSPMMFEGSPNCPUUPNUPUPQ
t*G1(LFZJTQSFTTFEQSFTFUUJOHUPCFNPEJmFEDBOCFFOUFSFE
t5IFQSFTFUWBMVFTDBOCFNPEJmFECZVTJOHBOELFZT
t5IFWBMVFJTQSPHSBNNFEJG1(LFZJTQSFTTFEBHBJO5IFXPSEi13(wBQQFBSTPOUIFEJTQMBZ

NOTES:
Simultaneously pressing <+> and <-> from inside a function menu allows you to return to the previous menu without mak-
ing any changes.
Hold down the <+> key or the <-> key to accelerate the increase/decrease of the values.
After waiting 30s the control unit quits programming mode and switches off the display.
Pressing <-> with the display turned off means an impulse of P.P.

PARAMETERS, LOGIC AND SPECIAL FUNCTIONS

In the charts following the single available functions are described in the plant. 

PARAMETERS (

PAR

)

MENU

FUNCTION

MIN-MAX-(Default)

MEMO

TCA

"VUPNBUJDDMPTVSFUJNF*UJTFOBCMFEPOMZXJUIi5$"w0/MPHJD

At the end of the preset time, the control unit controls a closure operation.

1-240-(40s) 

tsm

Braking during closure is adjusted. 
The value is expressed in percentage on the aggregate value of the stroke.
In the opening phase, braking is automatically preset by the control unit 
and no adjustment is required.

1-99-(20%)

FSTS

The opening and closing speed is adjusted.

1-99-(99)

sldS

Speed during braking is adjusted.

1-99-(20)

Содержание CP.J4 ESA

Страница 1: ...L8542920 04 2011 rev 0 CP J4 ESA UNIONE NAZIONALE COSTRUTTORI AUTOMATISMI PER CANCELLI PORTE SERRANDE ED AFFINI...

Страница 2: ...00mA max 24Vac dc SCA Service Light R A D I O F1 T A COM P P STOP PHOT OPEN CLOSE BAR BAR SCA SCA BLINK BLINK 24V 24V N L F2 1AT 230V F2 2AT 115V MOT L1 AUX N1 L1 N1 0V OUT ENC M M ENC ANT ANT SHIELD...

Страница 3: ...BLINK BLINK 24V 24V 8K2 4 2 3 SCA AUX1 0 BAR BAR SCA SCA BLINK BLINK 24V 24V SCA 24Vac 3W max 24Vac 1A max AUX1 1 II CH RADIO BAR BAR SCA SCA BLINK BLINK 24V 24V AUX1 2 SERVICE ZONE LIGHT Service Lig...

Страница 4: ...ssential characteristics of the product unchanged the manufacturer reserves himself the right to bring any change of technical constructive or commercial character without undertaking himself to updat...

Страница 5: ...push button Normally Open contact A timer clock can be connected for openings according to timeframes PHOT Photocell Input photocell is activated in the closing phase STOP STOP STOP button input N C...

Страница 6: ...red values in the programming menus described below The parameters menu allows you to assign a numerical value to a function in the same way as a regulating trimmer The logic menu allows you to activa...

Страница 7: ...ion of the opening operation 3 Area light The contact closes in the opening phase and remains closed for the entire TCA time It opens only with closed door 0 3 3 ATTENTION A wrong formulation of these...

Страница 8: ...BWJOHT GVODUJPO JT BDUJWBUFE PS EFBDUJWBUFE On Enabled energy savings After around 10 sec of non operation the po wer supply is cut off from the accessory output and the system switches to stand by Of...

Страница 9: ...paragraph SELF LEARNING PASSWORD CODE It allows to type in an access protection code to the programming of the control unit A four character alphanumeric code can be typed in by using the numbers fro...

Страница 10: ...ring the door leaf stoke If the error occurs during self learning of the radio transmitters this means that the memory of the receiver is no longer able to receive other transmitters or the transmitte...

Отзывы: