LifeGuard® 

LG

2-

Series

Use - Enclosure Front

Apply Power

To apply power, close the customer-supplied circuit breaker / disconnect on the line side of 

the LifeGuard panel. If there are no ground faults present on the system, the green POWER 

ON LED will light.

Perform Test (Trip Level Option

 F)

To perform a test on

 fixed

 

6-mA 

models with trip level option

 F:

 

• Push TEST for at least two seconds.
• The unit will trip, the green POWER ON LED will go out, and the red CIRCUIT TRIPPED LED 

will illuminate. Power to connected loads will be interrupted.

• An internal self-test will initiate, taking approximately ten 

s

econds.

• Push RESET for at least one second.
• If the internal self-test has completed, the unit will reset, the red CIRCUIT TRIPPED LED 

will go out, and the green POWER ON LED will illuminate. Power will be restored to the 
load.

Perform Test (Trip Level Option 

A)

To perform a test on

 field-adjustable

 models with trip level option 

A:

• Push TEST for at least two seconds.
• The unit will trip, the green POWER ON LED will go out, and the red CIRCUIT TRIPPED LED 

will illuminate. Power to connected loads will be interrupted.

• Push RESET for at least one second.
• The unit will reset, the red CIRCUIT TRIPPED LED will go out, and the green POWER ON 

LED will illuminate. Power will be restored to the load.

green

POWER LED / RESET button:  
Illuminates when the panel has power and 

is

 not 

tripped /  
RESET button: Resets the panel if faults have been 
cleared (momentary push).

red

TRIPPED LED / TEST button:  
Illuminates when tripped / 
TEST button: Performs a functional test 
 (hold for at least 2 seconds).

POWER

ON

Push to Reset

  CIRCUIT

  TRIPPED

   Push to Test

OPERATION

The green POWER ON lamp

illuminates when power is available to the 

load.

The red CIRCUIT TRIPPED lamp illumi-

nates when power is removed from the 

load..

If the unit trips, clear the fault and press

Reset to resume operation.

TESTING  

Unit must be tested at least

once per month 

   Press Test for > 2 seconds.

   Unit must trip.

   Press Reset for > 1 second. 

   Unit should reset, restoring power to

   the load.

USA & Mexico

800-356-4266

[email protected]

Canada

800-243-2438

[email protected]

Latin America

+56 2 2933 4211

[email protected]

Technical Support:

®

Содержание LifeGuard LG2 Series

Страница 1: ...Quickstart EN LG_D00393_00_Q_XXEN 12 2020 LifeGuard LG2 Series Protection Panels ...

Страница 2: ...onsibility is assumed by Bender for any consequences arising from use of this document Use of this document This quick start applies to standard LifeGuard models with lighted push button front panels as pictured above as well as open panels with no enclosure Standard model Installation Mounting NEMA 4X Polycarbonate Enclosure enclosure code P The standard enclosure for LifeGuard protection panels ...

Страница 3: ...ssional electrician licensed in accordance with local laws and regulations must perform this installation The enclosure must be penetrated in order to bring the line and load conductors to the protective circuit Bender recommends making these penetrations on the bottom of the enclosure and the use of NEMA 4X minimum fittings to maintain the environmental rating of the enclosure The specifics of th...

Страница 4: ...d wires to the ground lug on the backplate Do not route the ground wire through the current transformer Voltage Conductors not including ground Referenced Wiring Diagram 120VAC 1ph 2w L1 N FigureW1 208VAC 3ph 3w L1 L2 L3 FigureW2 208 120VAC 3ph 4w L1 L2 L3 N FigureW3 240 120VAC 1ph 3w L1 L2 N FigureW4 480VAC 3ph 3w L1 L2 L3 FigureW2 480 277VAC 3ph 4w L1 L2 L3 N FigureW3 600VAC 3ph 3w L1 L2 L3 Figu...

Страница 5: ...be mounted in a location sufficient to protect live electrical equipment Use four 10 screws for mounting It should be placed X inches away from other equipment This vertical clearance X minimum depth of enclosure measured from the installed backplate of the backplate is 7L4 5L3 3L2 1L1 8T4 6T3 4T2 2T1 Note 1 Note 1 B D A C CT Type A x B C x D 100 A 8 25 x 10 25 210 x 260 8 88 x 10 88 225 x 276 100...

Страница 6: ...green POWER ON LED will go out and the red CIRCUIT TRIPPED LED will illuminate Power to connected loads will be interrupted Push RESET for at least one second The unit will reset the red CIRCUIT TRIPPED LED will go out and the green POWER ON LED will illuminate Power will be restored to the load green POWER LED RESET button Illuminates when the panel has power and is not tripped RESET button Reset...

Страница 7: ...el option A have field adjustable ground fault current trip level and trip time The factory defaults are 30 mA and 0 s These models have a CTUB101 CTBC35P current sensor which has a three position potentiometer that must be set to the correct position depending on the RCMA420 D 2 ground fault current trip setting For trip settings up to 100 mA the potentiometer must be rotated to the left position...

Отзывы: