![Bender ISOMETER isoUG425 Скачать руководство пользователя страница 36](http://html.mh-extra.com/html/bender/isometer-isoug425/isometer-isoug425_quick-start-manual_2731686036.webp)
36
isoUG425_D00220_02_Q_DEEN / 05.2018
Connection
Connection type ................................................................................................................................Push-wire terminal
Nominal current ....................................................................................................................................................≤ 10 A
Conductor sizes .............................................................................................................................................AWG 24-14
Stripping length ....................................................................................................................................................10 mm
Rigid......................................................................................................................................................... 0.2…2.5 mm²
Flexible without ferrules ....................................................................................................................... 0.75…2.5 mm²
flexible with ferrules, with/without plastic collar................................................................................ 0.25…2.5 mm²
Multiple conductor, flexible withTWIN ferrule with plastic sleeve ....................................................... 0.5…1.5 mm²
Opening force........................................................................................................................................................... 50 N
Test opening, diameter....................................................................................................................................... 2.1 mm
Other
Operating mode ........................................................................................................................... Continuous operation
Mounting..................................................................................................... Cooling slots must be ventilated vertically
Degree of protection, built-in components (DIN EN 60529) ................................................................................. IP30
Degree of protection, terminals (DIN EN 60529) ................................................................................................... IP20
Enclosure material .................................................................................................................................... Polycarbonate
DIN rail mounting acc. to................................................................................................................................. IEC 60715
Screw fixing ......................................................................................................................... 2 x M4 with mounting clip
Weight.................................................................................................................................................................≤ 150 g