![Bender ISOMETER isoUG425 Скачать руководство пользователя страница 19](http://html.mh-extra.com/html/bender/isometer-isoug425/isometer-isoug425_quick-start-manual_2731686019.webp)
19
isoUG425_D00220_02_Q_DEEN / 05.2018
Insulation monitoring device for unearthed
DC systems (IT systems) up to 120 V
Software version: D476 V2.xx
www.bender.de/en/service-support/downloads
1. Intended use
The ISOMETER® monitors the asymmetrical insulation resistance
R
F
of une-
arthed DC main circuits (IT systems) with nominal system voltages of
DC 12. . .120 V. The maximum permissible system leakage capacitance
C
e
is
50 uF
In the case of an insulation fault on a power conductor, the
measured residual voltage is evaluated to determine the
insulation resistance R
F
. Only asymmetrical insulation faults
can be detected using the passive measurement method
employed in this ISOMETER®. Equally large insulation faults
between the positive and negative power conductors to
earth (i.e. symmetrical faults) are not detected .
In the event of an alarm message, the insulation fault should
be eliminated as quickly as possible.