27
TGH 1360E
Wiring and commissioning
monitored system
supply voltage
UN = DC 350 - 800 V
US = DC 110 V /AC 100 - 240 V
P1
H1
H2
RS485
RS232
S1 S2 S3 S4 S5
Coupling
device
AG500
2
AK1/L+
AK1/L-
AK1/U+
AK1/U-
T1
T2
A
B
RxD
TxD
SGND
RTS
CTS
Sub-D
K1
K2
K3
PE
PE2 S
PE
E1 E2 EG
M+ M-
external
digital
input
optional:
analog
output
0 ... 20 mA
L+
L-
L1/L+ N/L-
IR500
2
Designation
Terminal designation
Explanation
P1
LC display, 4 lines á 20 characters
H1
Alarm LED red, alarm L+
H2
Alarm LED yellow, alarm L-
K1
11,12,11,14
Alarm relay alarm L+, 1 change-over contact
K2
21,22,21,24
Alarm relay alarm L-, 1 change-over contact
K3
31,32,31,34
Alarm relay system fault, 1 change-over contact
S1
UP key
S2
DOWN key
S3
RIGHT key
S4
LEFT key
S5
ENTER key
E1
E1
Digital input 1, measurement suppression
E2
E2
Digital input 2, (without function at the moment)
EG
EG
Earth terminal of digital inputs 1, 2
L+
L+
System coupling L+
L-
L-
System coupling L-
AK1/L+
AK1/L+
Output L+ of coupling device AG5002
AK1/L-
AK1/L-
Output L- an of coupling device AG5002
AK1/U+
AK1/U+
Input U+ of coupling device AG5002
AK1/U-
AK1/U-
Input U- of coupling device AG5002
T1
T1
Positive input, temperature measuring of coupling
device AG5002
T2
T2
Negative input, temperature measuring of coupling
device AG5002
PE
PE
Coupling PE (earth)
PE2
PE2
Control earth (connection monitoring)
S
PE
Connection for cable shielding
A
A
Output A RS485 interface
B
B
Output B RS485 interface
M+
M+
Analog (0 ... 20 mA, linear)
M-
M-
Analog output - (0 ... 20 mA, linear)
RxD, TxD
RxD, TxD
Output RS232 interface on the terminal strip
SGND
SGDN
and on 9-pole Sub-D connector (f)
RTS, CTS
RTS, CTS