17
TGH 1360E
5 Setting and operation
Operation as well as all the settings are carried out by means of the software
using 5 function keys.
UP-key DOWN-key LEFT-key RIGHT-key ENTER-key
When operating under normal conditions, the main screen displays the currently
applicable measuring values. For changing parameters or settings, the main
menue has to be selected.
Once the power supply is switched on, the welcome screen appears displaying
the manufacturer's name (BENDER), the device type, and the firmware version.
ENTER
The welcome screen is displayed for about 5 seconds and then automatically
changes to the main screen. If the ENTER-key is activated within this time, the
main screen will be displayed immediately.
The picture above shows a main screen typical for IR5002 during operation.
U- = 564 V
The currently applicable measuring value of the negative pole-
to-earth voltage is 564 V
U
N
= 620 V
The current measured value of the nominal system voltage
is 620 V
RF- = 100k
Ω
The negative pole-to-earth insulation resistance is 100 k
Ω
(calculated value)
RF+ = 10 k
Ω
The positive pole-to-earth insulation resistance is 10 k
Ω
(calculated value)
AL- = 100 k
Ω
The pre-set response value for the negative fault is 100 k
Ω
AL+ = 10 k
Ω
The pre-set response value for the positive fault is 10 k
Ω
Menue:
Press the RIGHT-key to change to the respective menu
08:37
System time of the IR5002 (real time clock)
Function keys
Welcome screen
Main screen
*******BENDER*******
*A-ISOMETER IR500
2
*
*VERSION L2.0/05.96*
ENTER
U- = 564 V UN = 620 V
RF- = 100k
Ω
RF+ = 10k
Ω
AL- = 100k
Ω
AL+ = 10k
Ω
Menue:
08:37