COM462RTU_D00010_04_M_XXDE / 06.2021 17
COMTRAXX® COM462RTU
Menu level 2
Menu level 3
Factory setting
Description
1. Interface
1. Address
2
Set the BMS address of COM462RTU: 1…99
(internal BMS bus)
2. Interval
2 s
Set the cycle time 1…3s for the sequence:
• Querying alarms in the BMS bus
• Querying new bus devices
• Offering the BMS master function
3. Failure monitoring
5
Number of BMS bus cycles until a BMS device
failure is signalled. The setting is only effec-
tive when the COM462RTU has the master
function on the BMS bus (address 1).
Adjustable cycles: 1…10
2. Modbus
1. Address
2
Set the Modbus RTU address for COM462RTU:
2…247
2. Baud rate
19200
Set the baud rate
3. Parity
even
Set the parity
4. Control
off
Switch on or switch off the control commands
via Modbus
3. Language
1. English
Deutsch
Selection of the operating language
2. Deutsch
3. Français
4. Clock
1. Format
d.m.y
Date format: m-d-y/d.m.y
2. Date
01.01.2010
Date
3. Time
00:00
Time
4. Summertime
off
Select Central European Summer Time:
off = Function switched off
DST = Automatic switchover, USA, CDN
CEST = Automatic switchover, Central Europe
on = Set time zone +1 h
5. Password
1. Password
000
Enter/change password: 0…999
2. Status
off
Enable/disable password protection for
parameter setting via the buttons of the
COM462RTU
6. Service
For authorised Bender Service personnel only.