Modbus register assignment of the ISOMETER®
46
isoEV425_D00126_09_M_XXEN/03.2019
3012
RW
Memory function
for alarm mes-
sages
(Fault memory)
"M"
UINT 16
---
0 = Inactive
1 = Active
3013
RW
Operating mode
of relay 1 "r1"
UINT 16
---
0 = n.o.
1 = n.c.
3014
RW
Operating mode
of relay 2 "r2"
UINT 16
---
0 = n.o.
1 = n.c.
3015
RW
Bus address "Adr"
UINT 16
---
0 / 3 … 90
3016
RW
Baud rate "Adr 1"
UINT 16
---
0 = BMS
1 = 1.2 k
2 = 2.4 k
3 = 4.8 k
4 = 9.6 k
5 = 19.2 k
6 = 38.4 k
7 = 57.6 k
8 = 115.2 k
3017
RW
Parity "Adr 2"
UINT 16
---
0 = 8N1
1 = 8O1
2 = 8E1
3 = 8N2
3018
RW
Start-up delay "t"
during device
start
UINT 16
s
0 …10
3019
RW
Response delay
"ton" for relays K1
and K2
UINT 16
s
0 … 99
Register
Property
Description
Format
Unit
Value range