Reference Manual 
 
Power Analyzer EMM5 

 

Rev. 11 

 

 

2018-07 

 

10 

 

Whenever a capital "M" is used as key symbol in any submenu, pressing the key will switch straight to 

the main menu. 

 

4.2

 

Measurement 

This menu contains all measured values. The values are organised in several pages, which can be displayed on the LCD. 

With the right key the user can additionally select between the active value ("TRMS"), minimum ("MIN") and maximum 

("MAX"). For some measurement values the MIN / MAX selection is not possible. 

The navigation through the values is quite easy: You can use the "

" and "

" keys to select the different pages. Press 

one of the keys repeatedly to see all the values. If the last page is reached, the EMM5 continues with the first page. 

Each value is displayed with its name (ULL, ULN, I, ...), its origin (L1, L2, L3, N) and the unit (V, A,...).  

In addition to the measurement display, shows the EMM54 the rotation field of the system. The indicator for this is in 

the row and shows “

“ for a clockwise rotation field and “

“ for anti clockwise rotation field. The rotation field can 

also be used as an alarm source. 

The EMM5 features an auto range-function: If a certain value becomes too big, the display automatically switches the 

unit prefixes. For example: If the voltage exceeds 1000V, the display switches to 1.00 kV.  

In the top right corner of the display, the status of all assembled output relays is shown. The relays are represented by 

numbers.  A  dark  number  on  bright  ground  shows  a  deactivated  relay,  a  bright  number  on  dark  ground  shows  an 

activated relay.  

Devices with option –DM shows in the upper left corner the currently used tariff. The digital input is indicated by a “D”, 

the active or inactive state is indicated as with output relays.  

Use the “M”-key to switch back to the main menu at any time. 

4.3

 

Auto-roll 

This menu also contains all measured values. The values are organised in several “pages”, which can be displayed on 

the LCD. This menu has a timer-controlled auto-roll mechanism. Every 10 seconds the display is automatically switched 

to the next page. Additionally the keys "

" and "

" keys can be used to select the different pages.  

4.4

 

Harmonics 

The  EMM5  calculates  harmonics  for  the  seven  input  channels  (U-L1,  U-L2,  U-L3,  I-L1,  I-L2,  I-L3,  I-N).  Harmonics  are 

displayed regarding EN 61000-2-4 from the fundamental wave (1st harmonic) up to the 62nd harmonic. The harmonics 

are given in percent, each harmonic is standardized to the TRMS value. The harmonics are displayed in two columns: 

Содержание EMM5

Страница 1: ...nual Power Analyzer EMM5 Rev 11 2018 07 Beluk GmbH Taubenstrasse 1 86956 Schongau Germany Tel 49 0 8861 2332 0 Fax 49 0 8861 2332 22 E Mail blr beluk de Web http www beluk de Reference Manual POWER AN...

Страница 2: ...updates 14 12 04 CE 03 features of new software V1 05 18 03 05 ATh 04 features of new software V1 06 08 12 05 ATh 05 features of new software V1 07 connection diagrams added 28 02 06 ATh 06 features...

Страница 3: ...3 phase measurement with neutral conductor and four current transformers four wire measurement 19 5 2 3 phase measurement without neutral conductor with three current and three voltage transformers t...

Страница 4: ...erformed on the input data from all channels 3 voltage channels 4 current channels This provides information about the harmonic contents which distort the sine waveforms of currents and voltages The f...

Страница 5: ...o small or even disconnected the device will not be able to do any measurements This mechanism is also used to provide the frequency reading The data collection circuitry for the voltage channels uses...

Страница 6: ...hese further calculations are possible THD U THD for each voltage channel from the harmonics 1 62 THD I THD for each current channel from the harmonics 1 62 Pth Ith Exponentially damped values for cur...

Страница 7: ...alarms Each of them continuously compares one of the measured values to an assigned limit and if necessary triggers the alarm Each of the alarms provides the following features Alarm source can be an...

Страница 8: ...the reverse display bright number on dark ground shows an activated relay The message ALARM xx in the centre of the display shows the number of the active alarm The number appears instead of xx in thi...

Страница 9: ...ntrast set up menu in this case so an additional possibility to set the contrast is included in the introduction screen press one of the two keys in the middle repeatedly to change contrast If no chan...

Страница 10: ...lue becomes too big the display automatically switches the unit prefixes For example If the voltage exceeds 1000V the display switches to 1 00 kV In the top right corner of the display the status of a...

Страница 11: ...rmonic alarms should use the THD as source which contains information of all harmonics of one source in one single value 4 5 Work This submenu contains the work accumulators These accumulators count c...

Страница 12: ...ible settings the setup menu is divided into more submenus to provide easy and logical access to all the set up possibilities The available submenus are PARAMETER This menu provides the possibility to...

Страница 13: ...te it by pressing the key PT RATIO This sets up the device to work with a voltage measurement transformer Enter the transformer ratio The range is 1 4000 If no transformer is used and the EMM5 is dire...

Страница 14: ...are of reactive nature reactive power cp the display shows ind or cap for the trigger setting This has to be interpreted as more inductive than limit or more capacitive than limit LIMIT The limit val...

Страница 15: ...lose if P sum 20W relay 2 will close when P sum 20W This setting contains the dead zone of 20W The on delay of 1sec and off delay of 0 5 sec for both relays prohibits them from being closed at the sam...

Страница 16: ...lse outputs Select one pulse output with the and keys and after pushing the value can be adjusted The range is between 1 and 10000 pulses Mwh or Mvarh The adjusted value should be selected in the way...

Страница 17: ...ry For the DI can be adjusted if the synchronization is done via a positive edge HIGH or negative edge LOW When synchronization via the DI the time interval to be terminated since this time will be us...

Страница 18: ...torage cells full the recording starts again at memory cell one As additional information will be stored the values listed in the following table Page 1 Page 2 Page 3 Record 1 64 Indicates in which me...

Страница 19: ...wer systems with or without the neutral conductor Below measurements in systems with L1 L2 L3 and N PEN are called four wire measurement Measurements in systems without N are called three wire measure...

Страница 20: ...Rev 11 2018 07 20 5 2 3 phase measurement without neutral conductor with three current and three voltage transformers three wire measurement 5 3 3 phase measurement with two current and three voltage...

Страница 21: ...nalyzer EMM5 Rev 11 2018 07 21 5 4 3 phase measurement with two current transformers three wire measurement 5 5 3 phase measurement with three current transformers and measured neutral conductor curre...

Страница 22: ...ltage max 250V DC switching current max 100mA switching frequency max 4Hz tON 50ms tOFF 50ms Digital Input On request Fan control temperature measurement on rear side of device programming of relay ou...

Отзывы: