MANUAL Operation:
For manual operation
u
has to be pushed for 3 seconds!
Selection of step by
p
,
q
. Number of selected step is shown in line 2 of
LCD. By pushing
u
selected step will switch on / off..
Manual operation will be left by
t
.
Important Information:
-
Menue Manual Operation cannot be opend in modes LIFO and
Combi-Filter. (
"
Referencebook!)
-
Discharging lock-time is also active during manual operation
(steps are locked a certain time after switching-off)
-
when voltage is out of tolerance all steps are disconnected.
-
THD U-alarm and overtemperature are locking switching-in steps in
manual operation.
-
Only steps with steptype AUTO can be switched!
-
After leaving manual operation menue, control continues from