FAQ during Commissioning:
1)
No indication AUTO
PFC is stopped
Cause: manual operation, SETUP/100/PFC = OFF or HOLD,
temperature is too high, current < 15mA, voltage oder THD U is out
of tolarance.
2)
Indication U ALARM
"
voltage out of tolerance
Check settings for nominal voltage (SETUP/Un) and
voltage transformer (SETUP/Pt)
3)
Indication I Lo ALARM
"
current < 15mA
Cause: connection error of CT; short-link of CT is not removed; CT-
ration is too big compared to real current; no current
4)
Indication EXPORT
"
kW export
if there is no real kW export, voltage and current connection of BLR-
CX has to be checked!
"
chapter wrong connection
5)
Wrong Cos
j
indication
"
wrong connection
voltage and current connection of BLR-CX has to be checked!
"
chapter wrong connection
6)
Exits are connected and immediately disconnected
"
chapter stepsize detection / defective capacitors
7)
Frequent switching operations
size of capacitors is not completely detected
"