MS4604F1010
230 VAC
On/Off
30
FSLF230
*
MS4604F1210
230 VAC
On/Off
30
2
FSLF230-S
*
MS4609F1010
230 VAC
On/Off
80
FSNF230
MS4609F1210
230 VAC
On/Off
80
2
FSNF230-S
MS4620F1005
230 VAC
On/Off
175
FSAF230A
MS4620F1203
230 VAC
On/Off
175
2
FSAF230A-S
MS4709F1014
230 VAC
On/Off
80
FSNF230 US
MS4809F1012
230 VAC
On/Off
80
FSNF230 US
MS7520A2015
24 VAC
2-10V, 4-20mA
175
FSAFB24-SR US
MS8104F1010
24 VAC
On/Off
30
FSLF24
*
MS8104F1210
24 VAC
On/Off
30
FSLF24
*
MS8109F1010
24 VAC
On/Off
80
FSNF24
MS8109F1210
24 VAC
On/Off
80
2
FSNF24-S
MS8120F1002
24 VAC
On/Off
175
FSAF24A
MS8120F1200
24 VAC
On/Off
175
2
FSAF24A-S
MS8209F1003
24 VAC
On/Off
80
FSNF24 US
MS8309F1001
24 VAC
On/Off
80
FSNF24 US
S20230-F
230 VAC
On/Off
175
FSAF230A
S20230-F-SW2
230 VAC
On/Off
175
2
FSAF230A-S
S2024-F
24 VAC
On/Off
175
FSAF24A
S2024-F-SW2
24 VAC
On/Off
175
2
FSAF24A-S
SPH2 Aux Switch
**
32003532-002 Aux Switch
**
* Use FSNF series if damper is > 4 sq.ft.
** Use -S model of proper voltage.
Nominal sq.ft. per UL555S testing. Temp
Actuator
<4
350°F
FSLF
36” w x 24” h also.
<12
350°F
FSNF
Multisections also.
<16
250°F
FSNF
Multisections also.
<18
350°F
FSAF*A
Multisections also.
The FSTF series actuators were introduced in 2013. They are 18 in-lb and designed for
under 1.5 sq.ft. of fire and smoke damper. Use on larger dampers only when replacing
an existing FSTF on a fire and smoke damper.
The FSLF is recommended for small dampers.
Belimo actuators pass
UL555S at the same damper
sizes as the Honeywell.
NOTE. Although an actuator may operate a larger sized damper
use the UL listed sizing. Call for assistance.
Gear Train Motors and Linkages - Replacements with Belimo March 2018
7