800-543-9038
USA
866-805-7089
CANADA
203-791-8396
LATIN AMERICA / CARIBBEAN
59
Indicates an action or condition that may cause
irreversible damage to the actuator(s) or
associated equipment.
Equipment damage!
Power consumption and input impedance must
be observed.
CAUTION
Indicates a potentially hazardous situation which, if
not avoided, may result in minor or moderate injury.
It may also be used to alert against unsafe practices.
Warnings and Cautions appear at appropriate
sections throughout this manual. Read these carefully.
Hazard Identification
A
B
C
D
E
F
LS3
A-C
(Open Indication)
LS4
D-F
(Closed Indication)
Contact Rating: 5A 250 VAC Max.
SY2...12-120MFT
SY2...12-230MFT
Actuators: SY2...12-120MFT SY2...12-230MFT
NOTES SY2...12-120MFT (230MFT)
•
Caution:
Power supply voltage.
Use of feedback is optional.
APPLICATION NOTES
Recommended twisted shielded pair for control wiring.
Ground shielded wire at control panel chassis.
Tape back ground at actuator.
Observe class 1 and class 2 wiring restrictions.
INSTALLATION NOTES
Power Supply Com – 120 VAC (N) / 230 VAC (L1)
Power Supply Hot – 120 VAC (H) / 230 VAC (L2)
ŏ
1
Y
U5
C1
ŏ
2
C2
B
A
1
9
8
10
3
2
Internal Use Only
Internal Use Only
Internal Use Only
Not Used -
Not Used -
Internal Use Only
Internal Use Only
Internal Use Only
Internal Use Only
Internal Use Only
Feedback
Control Signal (-)
Feedback Signal (+)
Feedback Signal (-)
Control Signal (+)
SYx-230MFT
Address
Adaption
PC Tool
Service Jack
SYx-120MFT
L
N
Power Supply Com – 120 VAC (N) / 230 VAC (L1)
Power Supply Hot – 120 VAC (H) / 230 VAC (L2)
ŏ
1
Y
U5
C1
ŏ
2
C2
B
A
1
9
8
10
3
2
Internal Use Only
Internal Use Only
Internal Use Only
Not Used -
Control Signal
Not Used -
Internal Use Only
Internal Use Only
Internal Use Only
Internal Use Only
Internal Use Only
Feedback
Control Signal (-)
Feedback Signal (+)
Feedback Signal (-)
Control Signal (+)
SYx-230MFT
Address
Adaption
PC Tool
Service Jack
SYx-120MFT
L
N
G
PE
G
PE
Actuator A
Actuator B
Y1
Y2
Y1
Y2
35
36
35
36
36
35
W552_2
Isolation relays are required in parallel applications.
The reason parallel applications need isolation relays is that the
motor uses two sets of windings, one for each direction. When
one is energized to turn the actuator in a specific direction a
voltage is generated in the other due to the magnetic field created
from the first. It’s called back EMF.
This is OK with one actuator because the voltage generated in the
second winding isn’t connected to anything so there is no flow;
it has no magnetic effect on the motor.
On parallel applications without isolation, this EMF voltage
energizes the winding it is connected to on the other actuators in
the system, the actuators are then trying to turn in both directions
at once. The EMF voltage is always less than the supply voltage
due to the resistance of the windings, so while the actuator still
turns in the commanded direction, the drag from the other
reduces the torque output and causes overheating.
Wiring for Control Valves
Proportional, Multiple Wiring, 120/230V
O
50904 - 02/12 -
S
ubject to change.
©
Belimo Air
controls
(U
S
A
), Inc.