background image

39

Installation Recommendations

F6…, F7… Series Butterfly Valves

Flange Bolting Recommendations

Flange Detail for Ansi B16.5 Pipe Flanges

Flanges

Drilling

Bolting

A

B

C

D

Nominal 

Flange

Flange 

Diameter of

Diameter of

Number

Diameter

Pipe Size

Diameter

Thickness

Bolt Circle 

Bolt Holes

of Bolts

of Bolts

2”

6”

¾”

4¾”

4

2½”

7”

⁷⁄₈

5½”

¾”

¹⁄₈

3”

7½”

6”

4”

9”

¹⁵⁄₁₆

7½”

5”

10”

8½”

8

6”

11”

1”

9½”

⁷⁄₈

¾”

8”

13½”

1

¹⁄₈

11¾”

10”

16”

1

³⁄₁₆

14¼”

1”

⁷⁄₈

12”

19”

1¼”

17”

12

14”

21”

1

³⁄₈

18¾”

1

¹⁄₈

1”

16”

23½”

1

⁷⁄₁₆

21¼”

16

18”

25”

1

⁵⁄₈

22¾”

1¼”

1

¹⁄₈

20”

27½”

1

¹¹⁄₁₆

25”

20

24”

32”

1

⁷⁄₈

29½”

1

³⁄₈

1¼”

Pre-Installation Procedure
1. Remove any protective flange covers from the valve.
2. Inspect the valve to be certain the waterway is free from dirt

and foreign matter. Be certain the adjoining pipeline is free
from any foreign material such as rust and pipe scale or weld-
ing slag that could damage the seat and disc sealing surfaces.

3. Any actuator should be mounted on the valve prior to installa-

tion to facilitate proper alignment of the disc in the valve seat.

4. Check the valve identification tag for materials, and operating

pressure to be sure they are correct for the application.

WARNING! Personal injury or property damage may result

if the valve is installed where service condi-
tions could exceed the valve ratings.

5. Check the flange bolts or studs for proper size, threading, and

length.

6. These valves are designed to be installed between ANSI

Class 125/150 flanges.

7. Carefully follow installation using welded flanges: on page 30

of this document.

8. Follow ASME flange alignment standards:

Section 335.1.1 Alignment
a) Piping Distortions:

Any distortion of piping to bring into alignment for joint
assembly which introduces a detrimental strain in equip-
ment or piping components is prohibited.

b) Flange Joints:

Before bolting up, flange faces shall be aligned to the
design plane within 

¹⁄₁₆

in/ft measured across any diameter;

flange bolt holes shall be aligned within 

¹⁄₈

” maximum offset.

9. When observed during assembly, the flange faces shall be

parallel within 1°, and the force required to align pipe axes
shall not exceed 10 lb/ft per inch of NF bolts and nuts shall be
fully engaged.

Valve Installation Procedure
Position the connecting pipe flanges in the line to insure proper
alignment prior to valve installation. Spread the pipe flanges
apart enough to allow the valve body to be located between the
flanges without actually contacting the flange surfaces (See
Figure 1). Exercise particular care in handling the valve so as to
prevent possible damage to the disc or seat faces.

1. For Lug style valves:

a. Place the valve between the flanges.
b. Install all bolts between the valve and the mating flanges.

Hand tighten bolts as necessary.

2. Before completing the tightening of any bolts, the valve should

be centered between the flanges and then carefully opened 
and closed to insure free, unobstructed disc movement 
(see Figure 2).

3. Using the sequence shown in Figure 3, tighten the flange bolts

70103-00001D

-

03/08

-

Subject

to

change.

©

Belimo

Air

controls

(USA),

Inc.

Содержание F6 HS Series

Страница 1: ...Installation and Maintenance Instructions for Belimo F6 F7 HS HSU Series Butterfly Valves March 2008 70103 00001D...

Страница 2: ...lves should be stored in a weather protected area prior to installation Complete installation recommendations on page 38 Valve Size Cv Cv 10 Cv 20 Cv 30 Cv 40 Cv 50 Cv 60 Cv 70 Cv 80 Cv 90 F650HS U 2...

Страница 3: ...Aircontrols USA Inc A B D C BHC 10 0 10 0 A B C D F6 Dimensional Data Dimensions in inches F7 Dimensional Data Dimensions in inches Ordering Information Please note that HS series BF valves over 18 a...

Страница 4: ...22 00 8 50 8 10 UNCX1 75 50 50 F6150HSU 6 1058 2 19 9 00 22 50 9 50 8 10 UNCX2 00 50 Dimension A is compressed add 125 for relaxed state Maximum actuator ambient temperature is 122 F F6 HS Series Butt...

Страница 5: ...t placement of valves and actuators on the assembly 4 Dimension D allows for actuator removal without the need to remove the valve from the pipe 5 Weather shields are available dimensional data upon r...

Страница 6: ...06 3 7 15 27 44 70 105 115 F665HS U 2 196 0 10 6 12 25 45 75 119 178 196 F680HS U 3 302 0 20 9 18 39 70 116 183 275 302 F6100HS U 4 600 0 30 17 36 78 139 230 364 546 600 F6125HS U 5 1022 0 50 29 61 13...

Страница 7: ...Specifications see actuator section for details Type industrial electric Supply Voltages 24 VAC 10 120 VAC 10 230 VAC 10 Control Scheme 2 Position Floating Point 2 10 VDC 0 10 VDC 4 20mA MFT Master Va...

Страница 8: ...less Disc with Belimo SY Series Electric Actuation Maximum dimensions measured in inches MAX Close Off Valve Size GPM A B Max C Max D Max BHC Holes Lug Bolt Actuator Pressure psi F650HS 2 118 1 65 8 0...

Страница 9: ...utterfly Valves Full rated Resilient Seat 304 Stainless Disc with Belimo SY Series Electric Actuation Maximum dimensions measured in inches MAX Close Off Valve Size GPM A B C D Max BHC Holes Lug Bolt...

Страница 10: ...VAC factory set for 5 and 85 change of state Ambient Temperature 22 F to 150 F 30 C to 65 C Humidity Range up to 95 Housing Type IP67 NEMA 4 4X Housing Material die cast aluminum alloy Agency Listing...

Страница 11: ...SY12 120 SR MFT 3500Nm 31150 in lbs 58s 70s 4 0A Hand Wheel 56kg 123 5 lb Electrical Connection conduit connector screw terminals Overload Protection thermally protected 135 C cut out Motor Protectio...

Страница 12: ...SY12 230 SR MFT 3500Nm 31150 in lbs 58s 70s 2 2A Hand Wheel 56kg 123 5 lb Electrical Connection conduit connector screw terminals Overload Protection thermally protected 135 C cut out Motor Protectio...

Страница 13: ...nches mm Inches mm Inches mm SY1 6 10 155 3 94 100 4 25 108 8mm 8mm SY2 3 10 04 255 7 48 190 7 87 200 12 99 330 7 87 200 SY4 6 12 40 315 8 86 225 9 21 234 14 96 380 11 81 300 SY7 8 16 54 420 8 86 225...

Страница 14: ...see chart below Field adjustable if required Factory pre set and calibrated Do not adjust warranty voided LS2 Clockwise Decrease Closed Angle CLOSE Counter clockwise Increase Closed Angle LS1 Clockwi...

Страница 15: ...TION NOTES WARNING CAUTION APPLICATION NOTES INSTALLATION NOTES CAUTION APPLICATION NOTES INSTALLATION NOTES WARNING CAUTION APPLICATION NOTES INSTALLATION NOTES WARNING WARNING CAUTION APPLICATION NO...

Страница 16: ...L CLOSED Reverse Acting ON ON OFF ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON OFF ON 1 2 3 4 5 6 7 8 6 7 8 2 3 5 4 1 8 7 6 2 4 5 3 1 8 7 6 2 4 5 3 1 8 7 6 2 4 5 3 1 6 7 8 2 3 5 4 1 8 7 6 2 4...

Страница 17: ...2488 1866 SY1 SY2 SY3 SY4 SY5 SY6 SY7 SY8 SY9 SY10 SY11 SY12 wire gauge 0 3A 0 5A 0 5A 0 6A 0 7A 0 8A 1 6A 2 0A 1 6A 2 0A 1 6A 2 2A 18 5051 3030 3030 2525 2165 1894 947 758 947 758 947 689 16 7937 47...

Страница 18: ...Terminal 7 needs to be field wired to enable heater circuit 24 VAC Transformer Line Volts Open Close G Ground 1 Common 3 Open 4 Closed 5 Connect to 1 for fully open indication 6 Connect to 1 for full...

Страница 19: ...ibited Terminals 4 and 6 need to be wired separately Do not change sensitivity or dip switch settings with power applied 24 VAC Transformer Line Volts G Ground 4 Power Supply Com 5 Power Supply Hot 6...

Страница 20: ...n LS4 LS3 A E Closed Indication NOTES SY2 12 120SR MFT 230SR MFT Caution Power supply voltage SY Actuator Wiring Diagram SY1 5 24P and SY1 12 110P 220P Observe Class 1 and Class 2 wiring restrictions...

Страница 21: ...1 Common 3 Open 4 Closed 5 6 7 HTR A B C D E F LS3 A C Open Indication LS4 D F Closed Indication Contact Rating 5A 250 VAC Max SY2 5 24 K1 Open Close K1 B K1 A Actuator A Actuator B G Ground 1 Common...

Страница 22: ...6 Control Signal 7 Control Signal 8 Internal Use Only 9 Internal Use Only 10 Internal Use Only 11 Feedback 12 Feedback Feedback B G Ground 4 Power Supply Com 5 Power Supply Hot 6 Control Signal 7 Con...

Страница 23: ...5 5 G PE G PE Actuator B Actuator A Address Adaption Y1 Y2 Address Adaption Y1 Y2 1 1 F6 F7 HS HSU Butterfly Valves SY Actuator Wiring Diagrams SY2 5 24SR MFT Multiple Wiring W552 SY Actuator Wiring...

Страница 24: ...Supply Hot 6 Control Signal 7 Control Signal 8 Internal Use Only 9 Internal Use Only 10 Internal Use Only 11 Feedback 12 Feedback Feedback A Control Signal Actuator B Actuator A 120 and 230 VAC N L1 H...

Страница 25: ...ed wire at control panel chassis Tape back ground at actuator Observe class 1 and class 2 wiring restrictions INSTALLATION NOTES Power Supply Com 120v N 230v L1 Power Supply Hot 120v H 230v L2 1 Y U5...

Страница 26: ...may also be powered by 24 VDC 5 Meets cULus or UL and CSA requirements without the need of an electrical ground connection Equipment damage Actuators may be connected in parallel Power consumption an...

Страница 27: ...ve Electrical Components During installation testing servicing and troubleshooting of this product it maybe necessary to work with live electrical components Have a qualified licensed electrician or o...

Страница 28: ...ators with plenum rated cable do not have numbers on wires use color codes instead Actuators with appliance cables are numbered 3 Actuators may also be powered by 24 VDC 5 Meets cULus or UL and CSA re...

Страница 29: ...lectrical Components During installation testing servicing and troubleshooting of this product it maybe necessary to work with live electrical components Have a qualified licensed electrician or other...

Страница 30: ...y also be used to alert against unsafe practices Warnings and Cautions appear at appropriate sections throughout this manual Read these carefully Hazard Identification INSTALLATION NOTES APPLICATION N...

Страница 31: ...lectrical Components During installation testing servicing and troubleshooting of this product it maybe necessary to work with live electrical components Have a qualified licensed electrician or other...

Страница 32: ...h plenum rated cable do not have numbers on wires use color codes instead Actuators with appliance cables are numbered 3 Actuators may also be powered by 24 VDC 5 Meets cULus or UL and CSA requirement...

Страница 33: ...lectrical Components During installation testing servicing and troubleshooting of this product it maybe necessary to work with live electrical components Have a qualified licensed electrician or other...

Страница 34: ...ted cable do not have numbers on wires use color codes instead Actuators with appliance cables are numbered 3 Actuators may also be powered by 24 VDC 5 Meets cULus or UL and CSA requirements without t...

Страница 35: ...lectrical Components During installation testing servicing and troubleshooting of this product it maybe necessary to work with live electrical components Have a qualified licensed electrician or other...

Страница 36: ...to live electrical components could result in death or serious injury On Off 1 Neutral Blk 2 Hot Red Wht N Blk H Line Volts 2 5 120 VAC 230 VAC On Off On Off Control 24 VAC DC Power AF24 US AF24 S US...

Страница 37: ...ied licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks Failure to follow all electrical safety precautions when exposed t...

Страница 38: ...with piping ends TACK weld the flanges to the piping in several places Do NOT seam weld at this time Remove the lug bolts and carefully remove the valve body from the flanges Seam weld the entire fla...

Страница 39: ...allation using welded flanges on page 30 of this document 8 Follow ASME flange alignment standards Section 335 1 1 Alignment a Piping Distortions Any distortion of piping to bring into alignment for j...

Страница 40: ...to the fully closed position checking the actuator travel stop settings for proper disc alignment The valve should be operated to assure that no binding is taking place 6 The valve is now ready for op...

Страница 41: ...Operator Manual or Automatic already attached to the valve shaft 4 Never remove the Operator from the valve while the valve is in the pipeline under pressure 5 Always be sure that the disc is cracked...

Страница 42: ...42 70103 00001D 03 08 Subject to change Belimo Aircontrols USA Inc Notes Work Pad...

Страница 43: ...lis MN 55426 4267 Phone 952 920 0131 With branches in MN RSD Total Control 26021 Atlantic Ocean Drive Lake Forest CA 92630 Phone 949 380 7878 With branches in CA NV OR AK AZ ID UT WA Saint Louis Boile...

Страница 44: ...06810 Suite 101 Toll Free 800 543 9038 Sparks NV 89434 203 791 9915 Toll Free 800 987 9042 Fax 800 228 8283 775 857 4243 800 ACTUATE Fax 800 987 8875 203 791 9919 775 857 4255 South Customer Service...

Отзывы: