LCD Electronic Thermostat

EXT-CF230-D202-AF, EXT-CF230-D402-AF

Overview of Functions

Slim type EXT-CF230-D202-AF and EXT-CF230-D402-AF thermostat provides the 
foundation for modern fancoil applications.

Features

•  Large LCD with blue backlight
•  Stylish appearance with hidden buttons
•  For 2 or 3 wires on-off controlled devices in 2-pipe FCU system (EXT-CF230-D202-

AF)

•  For 2 wires on-off controlled devices in 4-pipe FCU system (EXT-CF230-D402-AF)
•  3 speed / auto-speed for fan controls
•  Defrost - low temperature protection
•  Temperature off-set adjustment
•  Temperature / setpoint display selection
• Memory rentention
•  Set point range adjustment
• °C display

Technical Data

Nominal Voltage

230 VAC

Nominal Voltage Range

85-260 VAC

Temperature Display Range

0…55°C [ <0°C : LO, >55°C : HI ]

Sensing Element & Control

NTC Thermistor, 100k ohm @ 25°C

System Switch

On/Off, Cooling/Heating

Fan Control Switch

High-Med-Low or Auto-speed

LCD Display

0.5 K increase/decrease

Setpoint Range

5…35°C

Body Material

Fire-retardant ABS

Electrical Ratings

Relay output contact 3A Resistive, 1A Inductive, 

250 VAC 50/60 Hz

Fan switch

3A Resistive, 1A Inductive, 
AC 250V 50/60 Hz

Control Signal

On/Off Control, 3-wires & spring return 2 wires
Cooling or Heating (2-pipe system)

Temperature Range

Operating: 0 to 45°C
Storage: 0 to 50°C

Protection Class

II 

Wiring Connections

Terminal wiring 0.5 ... 1.5 mm2

Agency Approval

LV Directive

CE according to 2006/95/EC

EMC

CE according to 2004/108/EC

Ambient Humidity

max. 95% r.h., non-condensing

Weight

140 g

Dimensions (L x H x D)

86 x 86 x 14 (mm)

Degree of Protection

IP 30

Basic Features

Modes

On/Off - Cooling 

 / Heating 

Fan speed

3 speed ( Low 

, Medium 

, High 

 ) / Auto 

Auto speed: difference between setpoint and ambient temperature, 
1 K - Low 

; 2 K - Medium 

; 3 K - High 

Defrost

Low temperature protection. When the unit in “OFF” status and 
ambient temperature lower than 5°C, it will switch on automatically 
in heat mode with “

” showing. When the temperature reached 

7°C, it will stop automatically.

Backlight

The backlight will light up 7 seconds whenever button is pressed. 
By pressing “

”, backlight light up 30 seconds.

Valve

When the valve is opening, the icon “

” displays.

Restart

When “RST” button is pressed, the thermostat will restart with last 
saved setting.

Memory

All last saved parameters will be kept after power failure or power off.

Dimension and Terminals

230 VAC Neutral N (comm)

Output for fan - High speed

Output for fan - Medium speed

Output for fan - Low speed

Output for actuator - Cool

Output for actuator - Heat

230 VAC Live L