Functions with basic values (conventional mode)
Override control with AC 24 V with relay contacts
Override control with AC 24 V with rotary switch
a
b
c
0%
ZS 50%
100%
Y
a
b
c
~
T
Y (DC 0...10 V)
e.g. 1N 4007
1 2 3 5
Y U
~
T
e.g. 1N 4007
1 2 3 5
Y U
0% ZS 50% 100%
Y
(DC 0...10 V)
Control remotely 0...100% with
positioner SG..
Minimum limit with positioner SG..
1 2 3 5
Y U
– +
T
~
SGA24
SGF24
SGE24
Y Z
1 2 3 4
– +
T
~
1 2 3 5
Y U
SGA24
SGF24
SGE24
Y Z
1 2 3 4
Y (DC 0...10 V)
100
0
Y [V]
10
min
0
[%]
– +
T
~
– +
T
~
Follow-up control (position-dependent)
Control with 4...20 mA via external resistor
1
3
2
5
– +
T
~
1
3
2
5
Y
U
DC
(0)2…10
V
DC
2…10
V
Y U
Y U
U
1
3
2
5
4…20
mA
DC 2…10
V
500 Ω
(+)
(–)
U
Y
– +
T
~
Caution:
The operating range must be set to
DC 2...10 V.
The 500 Ω resistor converts the
4...20 mA current signal to a voltage
signal DC 2...10 V
Functional check
1
3
2
5
– +
T
~
U
Y
Procedure
1. Apply 24 V to connection 1 and 2
2. Disconnect connection 3:
- with upwards direction of motion:
closing point at top
- with downwards direction of
motion: closing point at bottom
3. Short circuit connections 2 and 3:
- Actuator runs in the opposite
direction
NV24A-MP-TPC
Globe valve actuator, modulating, communicative, AC/
DC 24 V, 1000 N
Functions
NV24A-MP-TPC • en-gb • 2020-01-22 • subject to changes
5