Belief 

 

result in pressures up to 4.5 bar (may also occur with 

the immersion pump). Connected to the water tank and 

safe/the water pipe of the drain valve must be safe 

for drinking water, withstand pressure (up to 4.5 bar) 

and heat-

resistant water up to 80 °C.

 

If an immersion pump is used, a check valve must be 

installed between the pump and the first branch 

(Figure 15-1). Observe the flow direction when 

installing the check valve. 

Anti-freezing automatic waterproof device (Figure 15-

4, optional), a mechanical safety / drain valve. When 

there is a danger of frost it will automatically drain 

the water from the tank through the scupper. If there 

is excessive pressure in the system the pressure will 

be automatically released intermittently through the 

pressure relief valve (Figure 15-8, optional). 

 

 

 

 

External Temperature Sensor Installation 

Install inside the vehicle and measure the room 

temperature. The sensor installation location is 

determined by the RV manufacturer based on the 

specific conditions of the vehicle. When selecting the 

installation location, please note that the external 

temperature sensor should not be subjected to direct 

heat radiation. 

For optimum room temperature control, an external 

temperature sensor is installed above the entrance 

door. 

 

 

 

 

Make sure the external temperature sensor is always 

installed on the vertical wall. There must be free 

flowing air around it. 

Drill a hole with a diameter of 10 mm. Single wire 

terminal passes through the opening from the back and 

connect the end of the cable to the sensor with an 

insulated connector plug (no need to observe 

polarity). Slide into the external temperature sensor 

and connect the two ends of the cable and the two 

insulated connectors to the heater electronics (if 

necessary, extend the cable to a maximum length of 10 

meters, 2 x 0.5mm2 cable). 

The external temperature sensor provided must always 

be connected or the heater will switch to malfunction. 

LCD Control Switch Installation 

The gas heater must be operated with a dedicated LCD 

switch. See the relevant instructions for details. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electrical Connection 

Lay the wires to avoid scratches. If there is a sharp 

edge, if the metal panel is threaded, use a lead 

bushing or edge protection accessory. 

The connector cable must not be attached or in contact 

with metal surfaces, exhaust pipes or hot air ducts. 

Figure 16 

Figure 15 

Figure 17 

Содержание 4W2005 12C11

Страница 1: ...as Hot Water Warm Air Integrated Heater Technical Description Installation Operation and Maintenance Instructions Production Type Order No Liquefied gas electric heating DC12V 220VAC 4W2005 12C11 Version Oct 15 2018 ...

Страница 2: ... users should know through the instructions If you have questions or find something wrong please contact us directly When the user unpacks for the first time check the main unit and accessories against the packing list If you find any problems please contact the dealer immediately If there is a problem in use please contact the company s marketing department or our authorized customer service stat...

Страница 3: ...gas heating function is turned off first in the power adjustment phase In hot water working mode gas mode or electrical mode is used to heat the tank The tank temperature can be set to 40 C or 60 C Gas Mode The heater operates at the lowest power Stop heating immediately after reaching the set temperature Electrical Mode Manually select the 900W or 1800W heating mode according to the power supply ...

Страница 4: ...es not bear any responsibility for the following acts Modified heater and accessories Modification of exhaust lines and accessories Do not follow the operating installation instructions Do not use our company s special accessories Figure 1 1 LCD control switch 2 External temperature sensor 3 Recirculating air inlet minimum 150cm2 4 Heat pipe 5 Heat outlet 6 Smoking cowl Figure 2 ...

Страница 5: ...head self tapping nail M3 10 6_LCD control switch 7_Cross countersunk head flat tail self tapping nail M3 6 8_Cross head self tapping ST5 25 9_Heater 10_Controller cover 11_External temperature sensor lead wire 12_External temperature sensor 13_φ8 Elbow transition fitting 14_Rubber strip clamp 15_ Cross pan head self tapping screws ST5 16 16_φ8 Straight transition fitting 17_ Precision tube 18_ Fi...

Страница 6: ... installed area there is no ventilation window in the range of 300mm and there is no refueling port or tank respirator in the range of 500mm The exhaust cowl is mounted below the window that is close to or openable A window switch should be installed to ensure that the heater is turned off automatically when the window is opened Air Inlet Hose Installation The exhaust pipe is pass through the inta...

Страница 7: ...6 screws Figure 8 9 Use 2 screws to fix the exhaust cowl Fix the exhaust pipe on the side wall with mounting clip Connect Air Inlet Pipe to The Heater 20mm at the end of the exhaust pipe should be compressed do not straighten Try to insert the exhaust pipe on exhaust port as deep as possible fix the clip on top tighten Place the air intake pipe Figure 9 3 over the air inlet port Figure 9 5 Set on ...

Страница 8: ...iquefied gas supply When the gas pipe is cut off clean the port flash and burrs The paving of the pipe must make the heater easy to disassemble for maintenance work Use high pressure air to purge internal debris before installing the gas pipe The turning radius of the gas pipe is not less than R50 and it is recommended to use elbow pipe to pass the joint of right angle The gas interface Figure 13 ...

Страница 9: ...ternal temperature sensor should not be subjected to direct heat radiation For optimum room temperature control an external temperature sensor is installed above the entrance door Make sure the external temperature sensor is always installed on the vertical wall There must be free flowing air around it Drill a hole with a diameter of 10 mm Single wire terminal passes through the opening from the b...

Страница 10: ... the housing with a cable tie to eliminate tension all cables must be securely connected and must not be loose or disconnected due to vibrations causing a fire hazard DC12V Power Supply the heater s electrical wiring switches and control equipment must be in locations that would not adversely affect its operation under normal operating conditions The heater has reverse polarity protection If the c...

Страница 11: ...Belief 9 Figure 21 ...

Страница 12: ... the overheat switch will immediately cut off the gas supply If the gas heater is to meet the heating needs during driving a safety shut off device should be installed If without a safety shut off device the liquefied gas tank valve must be shut off before the driving 12V Fuse replace only with the exact same fuse T10A 12V Fuse Fuse and Wire harness must be replaced by professionals authorized by ...

Страница 13: ...ning liquefied gas tank valve Water tank filled with water when needed Switch Off the Heater Use a dedicated LCD switch to operate After the heater is turned off the combustion supporting fan and the heating fan will continue to operate for a few minutes depending on the temperature of the furnace In case of freezing hazard the water tank must be emptied Close the circulating water pump Turn on th...

Страница 14: ...fault Check vehicle power supply system 11 Under voltage fault Check vehicle power supply system 21 Warm air outlet temperature sensor disconnection Check if the sensor is in good condition 22 Warm air outlet temperature sensor short circuit Check if the sensor is in good condition 23 Water temperature sensor disconnection Check if the sensor is in good condition 24 Water temperature sensor short ...

Страница 15: ...tion air blower 82 Combustion support blower boot failure a Check the blower motor lead wire b Check combustion air blower 83 Combustion support blower spindle speed too low Check combustion air blower motor 84 Warm air blower motor disconnection Check warm air blower motor 85 Warm air blower motor boot failure Check the blower motor lead wire Check warm air blower motor 86 Warm air blower spindle...

Страница 16: ...ells of gas Long term halt When the heater is not used for a long time it should be run every 4 weeks for about 10 minutes each time to prevent the mechanical components such as solenoid valves and combustion air fans from malfunctioning get stuck The air inlet and outlet of the heater must be kept free from clogging and dirt so that the warm air duct is unobstructed to prevent overheating Heater ...

Страница 17: ...transition fitting 1C 14RN 1 12011103100 15 φ8 Elbow transition fitting 1C9 14RN 1 12011103200 16 φ10 Hose transition fitting φ10 1 12011103000 17 Hose water transition fitting 20411 16 06T 2 12011103300 18 φ10 Steel water pipe elbow transition fitting 1C9 16RN 2 12011103400 19 Nylon cable tie 4 200 10 21990000000 20 Intake and exhaust combine cowl φ110 108 1 12011101900 21 Intake and exhaust comb...

Страница 18: ...Belief 16 ...

Страница 19: ...rd Date Repaired Items and Reason Month Day Year Month Day Year Month Day Year Month Day Year Month Day Year Month Day Year Month Day Year Month Day Year Month Day Year Month Day Year Month Day Year Month Day Year Month Day Year ...

Страница 20: ...Science and Technology Co Ltd Phone 0451 82530666 0451 86676788 0451 86676988 Fax 0451 82537683 Address No 9 Xingnan Road Nangang District Harbin China E mail haoke sales bilaifu com Website www bilaifu com Postcode 150086 ...

Отзывы: