Approvals
cUL508 and CSA C22.2 No. 142-M1987
Please note the important information in: ”Relevant information for North America“, below.
ISA 12.12.01 (replaces UL 1604) und CSA C22.2, No. 213-M1987
Hazardous Locations Class1 Div 2 Groups A, B, C und D
Please note the important information in: ”Relevant information for North America“, below.
ATEX Directive 94/9/EC Zone 2 3G
Please note the important information in: ”Relevant information for use in Ex zone 2 according to ATEX 94/9/EC“, see page
5.
Note:
:
Only the certifications indicated on the label attached to each device are applicable.
Relevant information for use in Hazardous Locations according to ISA 12.12.01:
䊳
Only for connection with a Class 2 power supply.
䊳
For use in Class 2 Circuits.
䊳
Use class 1 wire only.
䊳
Use 60/75 or 90 °C copper(CU)wire only.
Additional Information for Use in Hazardous Locations:
This product may be operated in hazardous locations only if the product label is marked accordingly.
The following information applies when operating this equipment in hazardous locations:
Products marked ”Class I, DIV 2, Group A, B, C and D“ are suitable for use in Class I Division 2 Groups A, B, C, D,
Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate
indicating the hazardous location temperature code. When combining products within a system, the most adverse
temperature code (lowest ”T“ number) may be used to help determine the overall temperature code of the system.
Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time
of installation.
䊳
The peripheral equipment must be suitable for the location in which it is used.
䊳
Restrictions to the fault contacts of 7 pole connector for use in Hazardous Locations:
V < 30 V I < 90 m A L
i
= 0.5 µH typ. C
i
= 20 pF typ.
䊳
The tightening torque for field wiring terminals is max. 4.4 lb in (0.5 Nm).
z
Observe the Control Drawing 000144944DNR on page 6.
Technical Data
Operating voltage
NEC Class 2 power source 18 to 32 V DC (typ. 24 V DC) safety
extra-low voltage (SELV/PELV) (redundant inputs decoupled),
5 A max., buffer time min. 10 ms at 24 VDC
Current input
for +18 VDC
195 mA
for +32 VDC
130 mA
Switched on peak value
220 mA max.
Power consumption
2.6 W
Ambient temperature
OZD Profi 12M ... PRO without “EEC“ feature“
0 °C to +60 °C
OZD Profi 12M G12(-1300) EEC PRO
1)
–20 °C to +60 °C
(IEC 60068-2-1, IEC 60068-2-2)
Relative humidity
OZD Profi 12M ... PRO without “EEC“ feature
< 95 %,
non-condensing
OZD Profi 12M G12(-1300) EEC PRO
1)
100 %,
condensing
2)
(IEC 60068-2-3)
Protection class
IP 20
1) The DIP switches on the OZD Profi 12M G12(-1300) EEC PRO may also only be operated at ambient temperatures between
0 °C and +60 °C.
2) Protect the device against dripping water that may form.