3

Approvals

cUL508 and CSA C22.2 No. 142-M1987

Please note the important information in: ”Relevant information for North America“, below.

ISA 12.12.01 (replaces UL 1604) und CSA C22.2, No. 213-M1987

Hazardous Locations Class1 Div 2 Groups A, B, C und D 
Please note the important information in: ”Relevant information for North America“, below.

ATEX Directive 94/9/EC Zone 2 3G

Please note the important information in: ”Relevant information for use in Ex zone 2 according to ATEX 94/9/EC“, see page
5.

Note:

Only the certifications indicated on the label attached to each device are applicable.

Relevant information for use in Hazardous Locations according to ISA 12.12.01:

Only for connection with a Class 2 power supply.

For use in Class 2 Circuits.

Use class 1 wire only.

Use 60/75 or 90 °C copper(CU)wire only.

Additional Information for Use in Hazardous Locations:
This product may be operated in hazardous locations only if the product label is marked accordingly. 
The following information applies when operating this equipment in hazardous locations:

Products marked ”Class I, DIV 2, Group A, B, C and D“ are suitable for use in Class I Division 2 Groups A, B, C, D,
 Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate
indicating the hazardous location temperature code. When combining products within a system, the most adverse
 temperature code (lowest ”T“ number) may be used to help determine the overall temperature code of the system.
 Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time
of installation.

The peripheral equipment must be suitable for the location in which it is used.

Restrictions to the fault contacts of 7 pole connector for use in Hazardous Locations:
V < 30 V     I < 90 m A   L

i

= 0.5 µH typ.   C

i

= 20 pF typ.

The tightening torque for field wiring terminals is max. 4.4 lb in (0.5 Nm).

z

Observe the Control Drawing 000144944DNR on page 6.

Technical Data

Operating voltage

NEC Class 2 power source 18 to 32 V DC (typ. 24 V DC) safety 
extra-low voltage (SELV/PELV) (redundant inputs decoupled), 
5 A max., buffer time min. 10 ms at 24 VDC  

Current input

for +18 VDC

195 mA

for +32 VDC

130 mA

Switched on peak value

220 mA max. 

Power consumption

2.6 W

Ambient temperature

OZD Profi 12M ... PRO without “EEC“ feature“

0 °C to +60 °C 

OZD Profi 12M G12(-1300) EEC PRO

1)

–20 °C to +60 °C

(IEC 60068-2-1, IEC 60068-2-2)

Relative humidity

OZD Profi 12M ... PRO without “EEC“ feature

< 95 %, 

non-condensing

OZD Profi 12M G12(-1300) EEC PRO

1)

100 %, 

condensing

2)

(IEC 60068-2-3)

Protection class

IP 20

1) The DIP switches on the OZD Profi 12M G12(-1300) EEC PRO may also only be operated at ambient temperatures between 

0 °C and +60 °C.

2) Protect the device against dripping water that may form.

Содержание Hirschmann OZD Profi 12M Pro Series

Страница 1: ...07 CLASS 1 LASER PRODUCT LIGHT EMITTING DIODE CLASS 1LED PRODUCT Certified Usage Please observe the following Warning The device may only be employed for the purposes described in the catalog and technical description and only in conjunction with external devices and components recommended or approved by Hirschmann The product can only be operated correctly and safely if it is transported stored i...

Страница 2: ... Tel 49 0 1805 14 1538 E Mail HAC Support Belden com FCC RULES This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation Note This equipment has been tested and found to comply with the limit...

Страница 3: ...the hazardous location temperature code When combining products within a system the most adverse temperature code lowest T number may be used to help determine the overall temperature code of the system Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation 䊳 The peripheral equipment must be suitable for the loca...

Страница 4: ...orrect assignment can result in destruction of the repeater Limit values of relay contact Max switching voltage 60 V DC 42 V AC Max switching current 1 0 A Max switching capacity 30 W resistive load 䊳 The voltage connected to the relay must correspond to a safety extra low voltage SELV to IEC EN 60 950 and must comply with NEC Class 2 regulations as stipulated by UL CSA Analog Voltage Outputs The ...

Страница 5: ...accordance with EN60079 15 taking into account the environmental conditions under which the equipment will be used 䊳 When the temperature under rated conditions exceeds 70 C at the cable or conduit entry point or 80 C at the branching point of the conductors the temperature specification of the selected cable shall be in compliance with the actual measured temperature values 䊳 Installation additio...

Страница 6: ...6 ...

Страница 7: ...ules 䡺 OZD Profi 12M P11 PRO 䡺 OZD Profi 12M G11 PRO 䡺 OZD Profi 12M G11 1300 PRO 䡺 OZD Profi 12M P12 PRO 䡺 OZD Profi 12M G12 PRO 䡺 OZD Profi 12M G12 1300 PRO 䡺 OZD Profi 12M G12 EEC PRO 䡺 OZD Profi 12M G12 1300 EEC PRO We apply the following network topology 䡺 Line topology with optical cable monitoring 䡺 Star 䡺 Line topology without optical cable monitoring 䡺 Redundant optical ring We use the fo...

Страница 8: ...er Strasse 45 51 72654 Neckartenzlingen Germany Tel 49 0 1805 14 1538 E Mail HAC Support Belden com Internet http www hirschmann com We reserve the right to make technical modifications Hirschmann Automation and Control GmbH 2015 All Rights Reserved ...

Отзывы: