Relevant information for use in Ex zone 2 according to ATEX 94/9/EC
This product may be operated in EX zone 2 only if the product label is marked accordingly.
The following information applies when operating this equipment in EX zone 2 (ATEX 94/9/EC):
II 3G
Ex nA IIC T5 Gc
KEMA 09ATEX0139 X
Temperature Code T5
Standard types:
Ambient Ta: 0 … +60 °C
EEC types:
Ambient Ta: –20 … +60 °C
List of Standards
EN 60079-0 : 2012 + A11:2013
EN 60079-15 : 2010
Special conditions for safe use
䊳
The modules shall be installed in a suitable enclosure in accordance with EN60079-15, taking into account the
environmental conditions under which the equipment will be used.
䊳
When the temperature under rated conditions exceeds 70 °C at the cable or conduit entry point, or 80 °C at the
branching point of the conductors, the temperature specification of the selected cable shall be in compliance with the
actual measured temperature values.
䊳
Installation, addition, removal or replacement of modules, connectors or fuses shall only take place when the system
supply and the field supply are switched off, or when the area is known to be non-hazardous.
䊳
Do not open when energized.
Power supply:
24 V DC (18 ... 30 V DC), 195 ... 130 mA
Fault relay contacts:
max. 60 V DC / 42 V DC, 1 A, max. 30 W (resistive load)