5 Configuration and startup
5.4 Configuration of the LioN-P
EtherNet/IP modules
MSB
LSB
Bit
15 14 13 12 11 10 9 8
7 6 5 4 3 2 1 0
Word 8
Failsafe port X1, channel A (pin 4), value range 0...2, default value 0
Word 9
Failsafe port X1, channel B (pin 2), value range 0...2, default value 0
:
:
Word 14 Failsafe port X8, channel A (pin 4), value range 0...2, default value 0
Word 15 Failsafe port X8, channel B (pin 2), value range 0...2, default value 0
Table 28: Failsafe values for the 8DI/8DO module
5.4.2.3 QuickConnect Configuration
This parameter is provided by all LioN-P modules. QuickConnect (QC)
enables the module to perform the start-up process faster. Through the
activation of this parameter, particularly quick start-up of EtherNet/IP
communication is possible.
If you enable QuickConnect, the LioN-P module accepts a TCP connection
within 350 ms after being switched on. Then the control system establishes
a connection. The LioN-P module achieves a start-up time of 400 to 500 ms.
To use QuickConnect, the network must be in a star or line topology and the
LioN-P module must have a static IP address. Ring topologies and DHCP/
BOOTP are not supported. Please note that no automatic check is performed
for IP addresses that are assigned more than once in the same network.
If QuickConnect is activated, the following parameters for the Ethernet
interface of the LioN-P module are fixed:
D
100 Mbit/s transmission speed
D
Full duplex connection
D
Auto-negotiation and auto-MDIX deactivated
Manual LioN-P EtherNet/IP
Version 2.0 11/2017