Maintenance, troubleshooting, spare parts and dismantling
40
DRYPOINT® RA 1080-8800
Compressor outlet
temperature too
high.
Find out the reason for the fault:
1. Excessive thermal load – re-establish the nominal conditions.
2. The inlet air is too hot – re-establish the nominal conditions.
3. The ambient air temperature is too high or the room ventilation insufficient – ensure
sufficient ventilation.
4. The condenser is dirty – please clean it.
5. The fan does not work – see the corresponding section.
6. The fan runs continuously – ensure perfect functioning of the power contactor of the
fan (see KV1/KV2 on the electric diagram) and/or of the pressure transducer (see BHP
on the electric diagram) – (air-cooled).
7. The hot-gas bypass valve needs to be re-adjusted – contact a specialist to have the
nominal calibration re-established.
8. The temperature of the cooling water is too low – re-establish the nominal conditions
(water-cooled).
9. The adjusting valve for the cooling-water flow needs to be re-adjusted - contact a
specialist to have the nominal calibration re-established (water-cooled).
10. Refrigerant gas leak – contact a technician for refrigeration plants.
Condensation
pressure too high.
Find out the reason for the fault:
1. The ambient air temperature is too high or the air change insufficient in this area –
ensure sufficient ventilation (air-cooled).
2. The condenser filter is dirty – please clean or replace it (air-cooled).
3. The fan does not work – see the corresponding section (air-cooled).
4. The cooling water is too hot – re-establish the nominal conditions (water-cooled).
5. The cooling-water flow is insufficient – re-establish the nominal conditions (water-
cooled).
Condensation
pressure too low.
Find out the reason for the fault:
1. The fan runs continuously – ensure perfect functioning of the power contactor of the
fan (see KV1/KV2 on the electric diagram) and/or of the pressure transducer (see BHP
on the electric diagram).
2. The ambient temperature is too low – re-establish the nominal conditions.
3. Air flows through the condenser although the fan is switched off – protect the dryer
against wind or external air flows (not caused by the fan of the dryer).
4. The cooling-water temperature is too low – re-establish the nominal conditions (water-
cooled).
5. The adjusting valve for the cooling-water flow needs to be re-adjusted - contact a
technician for refrigeration plants to have the nominal calibration re-established (water-
cooled).
6. Refrigerant gas leak – contact a technician for refrigeration plants.
7. Compressor does not work – see specific point.
Содержание DRYPOINT RA 1080-8800
Страница 23: ...Technical data DRYPOINT RA 1080 8800 23 10 Technical data 10 1 Technical data DRYPOINT RA 1080 8800 3 400 50 ...
Страница 24: ...Technical data 24 DRYPOINT RA 1080 8800 10 2 Technical data DRYPOINT RA 1080 8800 3 460 60 ...
Страница 42: ...Maintenance troubleshooting spare parts and dismantling 42 DRYPOINT RA 1080 8800 ...
Страница 45: ...Appendices DRYPOINT RA 1080 8800 45 13 1 2 Dimensions DRYPOINT RA 2400 4400 ...
Страница 46: ...Appendices 46 DRYPOINT RA 1080 8800 13 1 3 Dimensions DRYPOINT RA 5400 6600 ...
Страница 47: ...Appendices DRYPOINT RA 1080 8800 47 13 1 4 Dimensions DRYPOINT RA 7200 8800 ...
Страница 49: ...Appendices DRYPOINT RA 1080 8800 49 13 2 2 Exploded diagram DRYPOINT RA 1080 2200 AC ...
Страница 50: ...Appendices 50 DRYPOINT RA 1080 8800 13 2 3 Exploded diagram DRYPOINT RA 2400 4400 AC ...
Страница 51: ...Appendices DRYPOINT RA 1080 8800 51 13 2 4 Exploded diagram DRYPOINT RA 5400 6600 AC ...
Страница 52: ...Appendices 52 DRYPOINT RA 1080 8800 13 2 5 Exploded diagram DRYPOINT RA 7200 8800 AC ...
Страница 53: ...Appendices DRYPOINT RA 1080 8800 53 13 2 6 Exploded diagram DRYPOINT RA 1080 2200 WC ...
Страница 54: ...Appendices 54 DRYPOINT RA 1080 8800 13 2 7 Exploded diagram DRYPOINT RA 2400 4400 WC ...
Страница 55: ...Appendices DRYPOINT RA 1080 8800 55 13 2 8 Exploded diagram DRYPOINT RA 5400 6600 WC ...
Страница 56: ...Appendices 56 DRYPOINT RA 1080 8800 13 2 9 Exploded diagram DRYPOINT RA 7200 8800 WC ...
Страница 71: ...Appendices DRYPOINT RA 1080 8800 71 ...
Страница 72: ...Appendices 72 DRYPOINT RA 1080 8800 ...
Страница 73: ...Declaration of conformity CE DRYPOINT RA 1080 8800 73 14 Declaration of conformity CE ...
Страница 74: ...Declaration of conformity CE 74 DRYPOINT RA 1080 8800 ...