Start-up
DRYPOINT® RA 1080-8800
21
9.2 Initial
start-up
Note!
The dryer
must not be started up more than six times an hour
. Wait at least five minutes prior to
every restart.
The user is responsible for the compliance with these provisions. Irreparable damage can be caused by
starting up the device too often.
The method below should be applied during the first start-up, after longer downtimes or subsequent to
maintenance works.
The start-up must be carried out by certified skilled personnel.
Processing sequence (observe Section 11.1 "Control panel")
Ensure that all steps of the "Installation" chapter have been carried out.
Ensure that the connection to the compressed-air system is in accordance with the provisions and that the lines are
fixed and supported properly.
Ensure that the condensate drain pipe is fixed in accordance with the provisions and that it is connected with a
collection system or a container.
Ensure that the bypass system (if available) is open and that the dryer is isolated.
Ensure that the manual valve of the condensate outlet is open.
Ensure that the cooling-water flow and the temperature are in accordance with the provisions (water-cooled).
Remove any packaging material and other items which may block the space around the dryer.
Switch on the main switch.
Switch on the main switch on the control panel (pos. 1).
The display of the DMC24 shows
.
When the alarm LED flashes
and the display of the DMC24 shows
and
, the current phases
are not connected correctly. Change two of the three phases at the supply mains (see Section
8.7).
Wait at least two hours before starting the dryer (the crankcase heater of the compressor needs to heat up the
compressor oil).
Press the
button for at least two seconds to start the dryer: If the compressor was out of operation for a
sufficient period of time, it will start immediately. If this is not the case, the display shows the countdown of the
seconds until the compressor restarts and the
LED flashes (max. delay five minutes).
Make sure that the consumption complies with the values of the name plate.
Ensure that the direction of rotation of the fan corresponds to the arrows on the condenser (air-cooled).
Wait until the dryer stabilises at the preset value.
Slowly open the air inlet valve.
Slowly open the air outlet valve.
Slowly close the central bypass valve of the system (if installed).
Check the pipes for air leakage.
Ensure that the drain discharges at regular intervals – wait for the first interventions.
CAUTION!
Please observe the direction of rotation of the compressor!
In this system, the direction of rotation of the compressor is supervised by a reverse-phase
protector (RPP).
When this guard is triggered, the alarm will be activated at the DMC24 (the alarm LED flashes
and
the display of the DMC24 shows
and
). In the event that the compressor does not run, the
direction of rotation must be changed by interchanging two phases. These modifications must only be
carried out by a qualified electrician.
Do not by-pass the RPP protector: If the device is operated with the incorrect direction of rotation,
the compressor will fail immediately. This will void the guarantee.
Содержание DRYPOINT RA 1080-8800
Страница 23: ...Technical data DRYPOINT RA 1080 8800 23 10 Technical data 10 1 Technical data DRYPOINT RA 1080 8800 3 400 50 ...
Страница 24: ...Technical data 24 DRYPOINT RA 1080 8800 10 2 Technical data DRYPOINT RA 1080 8800 3 460 60 ...
Страница 42: ...Maintenance troubleshooting spare parts and dismantling 42 DRYPOINT RA 1080 8800 ...
Страница 45: ...Appendices DRYPOINT RA 1080 8800 45 13 1 2 Dimensions DRYPOINT RA 2400 4400 ...
Страница 46: ...Appendices 46 DRYPOINT RA 1080 8800 13 1 3 Dimensions DRYPOINT RA 5400 6600 ...
Страница 47: ...Appendices DRYPOINT RA 1080 8800 47 13 1 4 Dimensions DRYPOINT RA 7200 8800 ...
Страница 49: ...Appendices DRYPOINT RA 1080 8800 49 13 2 2 Exploded diagram DRYPOINT RA 1080 2200 AC ...
Страница 50: ...Appendices 50 DRYPOINT RA 1080 8800 13 2 3 Exploded diagram DRYPOINT RA 2400 4400 AC ...
Страница 51: ...Appendices DRYPOINT RA 1080 8800 51 13 2 4 Exploded diagram DRYPOINT RA 5400 6600 AC ...
Страница 52: ...Appendices 52 DRYPOINT RA 1080 8800 13 2 5 Exploded diagram DRYPOINT RA 7200 8800 AC ...
Страница 53: ...Appendices DRYPOINT RA 1080 8800 53 13 2 6 Exploded diagram DRYPOINT RA 1080 2200 WC ...
Страница 54: ...Appendices 54 DRYPOINT RA 1080 8800 13 2 7 Exploded diagram DRYPOINT RA 2400 4400 WC ...
Страница 55: ...Appendices DRYPOINT RA 1080 8800 55 13 2 8 Exploded diagram DRYPOINT RA 5400 6600 WC ...
Страница 56: ...Appendices 56 DRYPOINT RA 1080 8800 13 2 9 Exploded diagram DRYPOINT RA 7200 8800 WC ...
Страница 71: ...Appendices DRYPOINT RA 1080 8800 71 ...
Страница 72: ...Appendices 72 DRYPOINT RA 1080 8800 ...
Страница 73: ...Declaration of conformity CE DRYPOINT RA 1080 8800 73 14 Declaration of conformity CE ...
Страница 74: ...Declaration of conformity CE 74 DRYPOINT RA 1080 8800 ...