32 / 44 EN
Free match split type air conditioner / Installation Manual
A
Warning:
After confirmation of the above conditions, follow these guidelines when performing
wiring:
•
Always have an individual power circuit specifically for the air conditioner. Always
follow the circuit diagram posted on the inside of the control cover.
•
Screws fastening the wiring in the casing of electrical fittings may come loose during
transporation. Because loose screws may cause wire burn-ou, check that the screws
are tightly fastened.
•
Check the specifications for the power source.
•
Confirm that electrical capacity is sufficient.
•
Confirm that starting voltage is maintained at more than 90 percent of the rated
voltage marked on the name plate.
•
Confirm that the cable thickness is as specified in the power source specifications.
•
Always install an earth leakage circuit breaker in wet or moist areas.
•
The following can be caused by a drop in voltage: vibration of a magnetic switch,
damaging the contact point, broken fuses, and disturbance of normal functioning.
•
Disconnection from a power supply must be incorporated into the fixed wiring.
It must have an air gap contact separation of at least 3mm in each active (phase)
conductors.
•
Before accessing terminals, all supply circuits must be disconnected.
8
Wiring