Free match split type air conditioner / Installation Manual
8.2 Outdoor unit wiring
A
Warning:
Before performing any electrical or wiring work, turn off the main power to the system.
1. Prepare the cable for connection
a. You must first choose the right cable size before preparing it for connection. Be sure to use
H07RN-F cables.
Table 8.1: Minimum cross-sectional area of power and signal cables north america
Rated current of appliance (A)
AWG
≤ 7
18
7 - 13
16
13 - 18
14
18 - 25
12
25 - 30
10
Table 8.2: Other regions
Rated current of appliance (A)
Nominal cross-sectional area (mm²)
≤ 6
0.75
6 - 10
1
10 - 16
1.5
16 - 25
2.5
25- 32
4
32 - 45
6
b. Using wire strippers, strip the rubber jacket from both ends of signal cable to reveal about
15cm (5.9”) of the wires inside.
c. Strip the insulation from the ends of the wires.
d. Using a wire crimper, crimp u-lugs on the ends of the wires.
C
Note:
While connecting the wires, please strictly follow the wiring diagram (found inside
the electrical box cover).
8
Wiring