6.6
Short-term power failure
Malfunction image
Close valves V1 / V2.
The current supply is interrupted.
No alarm is displayed.
Cause
Measure
Interruption of the voltage supply.
The valves close automatically.
When the power is restored, the time of
approx. 21 hours via the K1T (see E-plan
page 6) expires again.
At a reactor temperature b 130 °C
and + 150 °C, the RESET function of K1T
can be used (see chapter 6.10).
Exceeding the permissible voltage range.
This will trigger the fuses and interrupt the
voltage supply.
The valves close automatically.
When the power is restored, the time of
approx. 21 hours via the K1T (see E-plan
page 6) expires again.
At a reactor temperature b 130 °C
and + 150 °C, the RESET function of K1T
can be used (see chapter 6.10).