5.  INSTALLATION

5.1 Location

The  BA444DF-P  PROFIBUS  PA  indicator  is
housed in a robust IP66 glass reinforced polyester
(GRP) enclosure incorporating an armoured glass
window and stainless steel fittings.  It is suitable for
exterior mounting in most industrial environments,
including  offshore  and  wastewater  treatment
installations.    Please  consult  BEKA associates  if
high vibration is anticipated.

The  BA444DF-P  enclosure  is  surface  mounting.
Accessory  kits  described  in  sections  8.3  of  this
manual enable the instrument to be mounted onto
a vertical or horizontal pipe.

The field terminals and the two mounting holes are
located in a separate compartment with a sealed
cover  allowing  the  instrument  to  be  installed
without exposing the display assembly.

The BA444DF-P earth terminal is connected to the
carbon loaded GRP enclosure. If this enclosure is
not bolted to a post or structure connected to the
plant potential equalising network, the instrument’s
earth  terminal  should  be  connected  to  the
potential  equalising  network  as  recommenced  in
EN 60079-14.

 

The  BA444DF-P  enclosure  is  supplied  with  a
bonding  plate  to  ensure  electrical  continuity
between the three conduit / cable entries.

5.2 Installation Procedure

Fig  2  illustrates  the  instrument  installation
procedure.

a.

Remove  the  instrument  terminal  cover  by
unscrewing the two captive 'A' screws.

b.

Mount  the  instrument  on  a  flat  surface  and
secure  with  two  M6  screws  through  the  'B'
holes.  Alternatively use one of the mounting
kits described in section 8.3 

c.

Remove the temporary hole plug and install a
cable  gland  or  conduit  entry  with  required
ingress protection.  If more than one entry is
required, replace one or both IP66 stopping
plugs  with  a  cable  gland  or  conduit  entry
having the required ingress protection.

d.

Connect  the  field  wiring to the  terminals  as
shown in Fig 3.  

e.

Replace  the  instrument  terminal  cover  and
evenly tighten the two 'A' screws. 

CAUTION installation in Zone 0

When  installed  in  a  Zone  0  potentially
explosive  atmosphere  requiring  EPL  Ga
apparatus,  the  instrument  shall  be  installed
such that even in the event of rare incidents, an
ignition  source  due  to  impact  or  friction
between  the  aluminium label  and iron/steel  is
excluded.

No special conditions apply when the indicator is
installed in Zone 1 or in Zone 2.

Fig 2   BA444DF-P installation procedure

5.3  EMC 

The BA444DF-P complies with the requirements of
the  European  EMC  Directive  2004/108/EC.    For
specified immunity, all wiring should be in screened
twisted pairs with the screens earthed at one point
in the safe area.   

6

Содержание PROFIBUS PA BA444DF-P

Страница 1: ...Issue 5 16th December 2015 BA444DF P PROFIBUS PA Intrinsically safe Field mounting 8 variable Fieldbus Indicator Issue 5...

Страница 2: ...ions 6 4 Description of listener menu functions 6 4 1 Scan fieldbus segment 6 4 2 List configured input parameters 6 4 3 Enter address display parameters 6 4 4 Enable selected input 6 4 5 Enter source...

Страница 3: ...There is an alternative version of the fieldbus display order code BA444DF P for use on FOUNDATION fieldbus networks 1 1 Documentation This instruction manual describes ATEX system design and install...

Страница 4: ...ure classification of T1 450oC T2 300oC T3 200oC T4 135oC At an ambient temperature between 40 and 70o C Note the guaranteed operating temperature range of the BA444DF P Fieldbus Indicator is 20 to 70...

Страница 5: ...t should be equal to or less than Uo 22V dc Io 250mA dc Po 1 2W The segment can provide an additional 13mA to power the Fieldbus Indicator The equivalent capacitance Ci of the BA444DF P Fieldbus Indic...

Страница 6: ...entries 5 2 Installation Procedure Fig 2 illustrates the instrument installation procedure a Remove the instrument terminal cover by unscrewing the two captive A screws b Mount the instrument on a fl...

Страница 7: ...Fig 3 Dimensions and terminal connections 7...

Страница 8: ...ng the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digits are set as required operating the E button wil...

Страница 9: ...ed by the BA444DF P listener are not known In the SCAn function pressing the P button causes the BA444DF P listener to search the fieldbus segment to which it is connected for all data sources The hex...

Страница 10: ...rs Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 6 4 3 Enb Enable selected input En...

Страница 11: ...rce address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a lis...

Страница 12: ...ode irrespective of the numeric value When positioned as required operating the E button will enter the selection and return to the dP prompt in the edit sub menu 6 4 9 Configuration of bargraph displ...

Страница 13: ...sed access code will be activated when the transmitter is returned to the display mode If the access code is lost please contact BEKA associates 6 4 12 Change from fieldbus listener to fieldbus node t...

Страница 14: ...nds the model number followed by the firmware version will be displayed prior to entering the display mode 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live ma...

Страница 15: ...lf adhesive escutcheon ensure that the gasket is correctly positioned before reassembling the instrument enclosure 8 2 Tag plate The BA444DF P can be supplied with a blank or custom laser marked stain...

Страница 16: ...efer to over 5mm thick EN 60079 14 At an ambient temperature between 20 and 60o C The Indicator may be connected to any intrinsically safe segment providing The device powering the fieldbus segment is...

Страница 17: ...name and location IECEx dust approval information is also shown non European certification information may also be included The label includes boxed areas which should be marked by the installer to s...

Страница 18: ...mply with the Canadian Electrical Code C22 2 and with BEKA associates Control Drawing CI410 12 which is attached to this Appendix The FM and cFM entity parameters are identical to the ATEX parameters...

Страница 19: ...19...

Страница 20: ...20...

Страница 21: ...21...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...24...

Страница 25: ...25...

Страница 26: ...allation requirements for both gas and dust approvals The ATEX installation requirements specified in the main section and in Appendix 1 of this manual may therefore be used for IECEx installations bu...

Отзывы: