.  MAINTENANCE

7.1 Fault finding during commissioning

If  a  BA444DF-P  fails  to  function  during
commissioning the following procedure should be
followed:

Symptom

Cause

Check:

No Display

Instrument not

correctly

connected or

powered.

Between

terminals 1 & 2:

FISCO 9 & 17.5V

Ex ia   9 to 22V

Ex ic   9 & 32V

Displays 

‘no ConF’

No inputs are

enabled.

Configuration of

each input.

Displays

‘no dAtA’

No data being

received with the

current

configuration.

Addresses and

Index are correct.

That data has

DS-33 format.

Display shows

‘9.9.9.9.9’ with all

decimal points

flashing; all

bargraph

segments

activated and

bargraph scale

flashing.

Value 

over-range

Configuration.

and

decimal point

position.

Display shows 
‘-9.9.9.9.9’ with

all decimal points

flashing; no

bargraph

segments

activated and

bargraph scale

flashing.

Value 

under-range

Configuration

And

Decimal point

position.

Display

alternates

between value

and the word

‘bAd’.  Bargraph

flashes.

Status of fieldbus

variable has a

quality of ‘BAD’

or a fault state is

active.

Fieldbus

configuration.

Bargraph scale

flashes.

Process variable

is outside the

limits defined for

the bargraph.

Bargraph

configuration.

All display

segments
activated.

Display is

initialising.

This is normal

operation, after a

few seconds the

model number

followed by the

firmware version
will be displayed

prior to entering

the display mode.

7.2  Fault finding after commissioning

ENSURE PLANT SAFETY BEFORE

STARTING MAINTENANCE

Live  maintenance  is  permitted  on  intrinsically
safe equipment  installed in a hazardous area,
but  only  certified  test  equipment  should  be
used  unless  a  gas  clearance  certificate  is
available.

If  a  BA444DF-P  fails  after  it  has  been
functioning correctly, the table shown in section
7.1 may help to identify the cause of the failure.

If this procedure does not reveal the cause of the
fault,  it  is  recommended  that  the  instrument  is
replaced. 

7.3  Servicing

We recommend that faulty BA444DF-P PROFIBUS
PA Indicators are returned to BEKA associates or
to our local agent for repair.

7.4 Routine maintenance

The  mechanical  and  electrical  condition  of  the
instrument  should  be  regularly  checked.    Initially
annual  inspections  are  recommended,  but  the
inspection frequency should be adjusted to suit the
environmental conditions.

7.5  Guarantee

Instruments which fail within the guarantee period
should be returned to BEKA associates or our local
agent.  It is helpful if a brief description of the fault
symptoms is provided.

7.6  Customer comments

BEKA  associates  is  always  pleased  to  receive
comments from customers about our products and
services.    All  communications  are  acknowledged
and  whenever  possible,  suggestions  are
implemented.

14

Содержание PROFIBUS PA BA444DF-P

Страница 1: ...Issue 5 16th December 2015 BA444DF P PROFIBUS PA Intrinsically safe Field mounting 8 variable Fieldbus Indicator Issue 5...

Страница 2: ...ions 6 4 Description of listener menu functions 6 4 1 Scan fieldbus segment 6 4 2 List configured input parameters 6 4 3 Enter address display parameters 6 4 4 Enable selected input 6 4 5 Enter source...

Страница 3: ...There is an alternative version of the fieldbus display order code BA444DF P for use on FOUNDATION fieldbus networks 1 1 Documentation This instruction manual describes ATEX system design and install...

Страница 4: ...ure classification of T1 450oC T2 300oC T3 200oC T4 135oC At an ambient temperature between 40 and 70o C Note the guaranteed operating temperature range of the BA444DF P Fieldbus Indicator is 20 to 70...

Страница 5: ...t should be equal to or less than Uo 22V dc Io 250mA dc Po 1 2W The segment can provide an additional 13mA to power the Fieldbus Indicator The equivalent capacitance Ci of the BA444DF P Fieldbus Indic...

Страница 6: ...entries 5 2 Installation Procedure Fig 2 illustrates the instrument installation procedure a Remove the instrument terminal cover by unscrewing the two captive A screws b Mount the instrument on a fl...

Страница 7: ...Fig 3 Dimensions and terminal connections 7...

Страница 8: ...ng the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digits are set as required operating the E button wil...

Страница 9: ...ed by the BA444DF P listener are not known In the SCAn function pressing the P button causes the BA444DF P listener to search the fieldbus segment to which it is connected for all data sources The hex...

Страница 10: ...rs Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 6 4 3 Enb Enable selected input En...

Страница 11: ...rce address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a lis...

Страница 12: ...ode irrespective of the numeric value When positioned as required operating the E button will enter the selection and return to the dP prompt in the edit sub menu 6 4 9 Configuration of bargraph displ...

Страница 13: ...sed access code will be activated when the transmitter is returned to the display mode If the access code is lost please contact BEKA associates 6 4 12 Change from fieldbus listener to fieldbus node t...

Страница 14: ...nds the model number followed by the firmware version will be displayed prior to entering the display mode 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live ma...

Страница 15: ...lf adhesive escutcheon ensure that the gasket is correctly positioned before reassembling the instrument enclosure 8 2 Tag plate The BA444DF P can be supplied with a blank or custom laser marked stain...

Страница 16: ...efer to over 5mm thick EN 60079 14 At an ambient temperature between 20 and 60o C The Indicator may be connected to any intrinsically safe segment providing The device powering the fieldbus segment is...

Страница 17: ...name and location IECEx dust approval information is also shown non European certification information may also be included The label includes boxed areas which should be marked by the installer to s...

Страница 18: ...mply with the Canadian Electrical Code C22 2 and with BEKA associates Control Drawing CI410 12 which is attached to this Appendix The FM and cFM entity parameters are identical to the ATEX parameters...

Страница 19: ...19...

Страница 20: ...20...

Страница 21: ...21...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...24...

Страница 25: ...25...

Страница 26: ...allation requirements for both gas and dust approvals The ATEX installation requirements specified in the main section and in Appendix 1 of this manual may therefore be used for IECEx installations bu...

Отзывы: