5.  CONFIGURATION

The BA644DF-F 8 variable FOUNDATION™
fieldbus indicator may be configured as a fieldbus
node or as a fieldbus listener.  When used as a
fieldbus node the indicator is configured via the
fieldbus host.  For detailed node conditioning
information please refer to the BEKA
FOUNDATION™ fieldbus Interface Guide which
may be downloaded from www.beka.co.uk

As a fieldbus listener the BA644DF-F is not visible
to the fieldbus host and can only be configured via
the front panel push buttons using the menu
shown in Fig 6.

Throughout this manual the four BA644DF-F push
buttons are identified 

P  E

   

 

 and legends

displayed by the fieldbus indicator are shown
within inverted commas  e.g. ‘CodE’ and ‘LiSt’.

5.1  Configuration menus

The configuration menu is separated into two
sections, fieldbus node and fieldbus listener.  Both
contain the ‘tYPE’ function that enables transfer
between the two.   Unless otherwise requested
when ordered, all FOUNDATION™ fieldbus
BA644DF-F indicators are supplied as fieldbus
nodes but can easily be reconfigured on-site.

5.2  Node configuration menu

The node configuration menu is shown in Fig 4.
Access to the menu is obtained by operating the 

P

and 

E

 buttons simultaneously.  If the BA644DF-F

is not protected by an access code the first
parameter 'rESEt’ will be displayed*.  If the
instrument is protected by an access code, ‘CodE’
will be displayed first.  Pressing 

P

 will allow the

four digit security code to be entered digit by digit
using the 

 or 

 button to adjust the flashing digit

and 

P

 to move control to the next digit.  When the

correct code has been entered, pressing 

E

 will

cause the first parameter ‘rESEt’ to be displayed*.
If an incorrect code is entered, or no button is
pressed for ten seconds, the BA644DF-F will
automatically return to the display mode.

If the indicator displays ‘SCAn’ it is conditioned

as a fieldbus listener, see section 5.3.13 to change
it to a fieldbus node.

5.2.1  Reset the indicator to node factory
          defaults           ‘rESEt’

The BA644DF-F may be reset to the factory
defaults that are shown below:

Security Code

0000 (disabled)

Device address

Unconfigured

Last variable

8

For each of the eight inputs:

Decimal point

XXX.XX

Bar Type

Left

Bar lower limit

0.0

Bar Upper limit

100.0

Gain

1.0

Offset

0.0

 To reset the BA644DF-F select ‘rESEt’ in the
configuration menu by operating the 

 or 

button.   To enter the function press 

P

 which will

reveal ‘0000’ with the left hand digit flashing.  To
prevent accidental use of this function, ‘5urE’ must
be entered to confirm that the instrument is to be
reset.

Using the 

 or 

 button set the flashing digit to ‘5’

and press the 

P

 button to move control to the next

digit which should be set to ‘u’.  When the four
letters of ‘5urE’ have been entered operating the 

E

button will reset the BA644DF-F to the factory
defaults.

CAUTION

All the instrument’s node configuration
and links will be lost when it is reset.

5.2.2  Change from node to listener   ‘tYPE’

This function enables the instrument to be
changed from a fieldbus node to a fieldbus listener.
Select ‘tYPE’ in the node configuration menu using
the 

 or 

 button. To enter the function press 

P

which will show that the instrument is configured
as a fieldbus node, to change to a fieldbus listener
press the 

 or 

 button which will toggle the

display to ‘LStnr’   To prevent accidental  changes
this request must be confirmed by operating the 

P

button and entering  ‘5urE’.  The instrument will
display ‘0000’ with the first digit flashing, using the

 or 

 button set the flashing digit to ‘5’ and press

the 

P

 button to move control to the next digit which

should be set to ‘u’.  When the four letters of ‘5urE’
have been entered, operating the 

E

 button will

cause the instrument to restart as a fieldbus
listener in the display mode.

CAUTION

All the instrument’s node configuration
and links will be lost when it is changed
from a fieldbus node to a fieldbus
listener.

Содержание FOUNDATION BA644DF-F

Страница 1: ...Issue 4 4th March 2014 BA644DF F FOUNDATION fieldbus Field mounting 8 variable Fieldbus Indicator Issue 4...

Страница 2: ...display parameters 5 3 6 Enable selected input 5 3 7 Enter Device Address 5 3 8 Enter Variable Identity 5 3 9 Decimal point position 5 3 10 Configuration of bargraph 5 3 11 Scale numeric display 5 3...

Страница 3: ...protocol is shown on a label inside the terminal cover The F order code suffix also indicates the protocol but is not shown on the instrument identification label There is an alternative version of t...

Страница 4: ...arth terminal should be connected to the potential equalising network The BA644DF F enclosure is supplied with a bonding plate to ensure electrical continuity between the three conduit cable entries 4...

Страница 5: ...5 Fig 3 Dimensions and terminal connections...

Страница 6: ...nditioned as a fieldbus listener see section 5 3 13 to change it to a fieldbus node 5 2 1 Reset the indicator to node factory defaults rESEt The BA644DF F may be reset to the factory defaults that are...

Страница 7: ...the P button causes the BA644DF F indicator to search the fieldbus segment to which it is connected for all publishers Fig 5 shows how the indicator displays the hexadecimal Device Address and Variabl...

Страница 8: ...vice Address and Variable Identity Parameters can not be changed from within this function See section 5 3 4 Edit Enter addresses and display parameters Contains six sub functions that enable known fi...

Страница 9: ...9...

Страница 10: ...isplayed pressing E will allocate the selected process variable to the selected input and return the display to the Device Address and Variable Identity from which another process variable may be sele...

Страница 11: ...function pressing P again will reveal the existing bargraph justification The or button will scroll through the four options when the required justification is displayed pressing E will enter the sele...

Страница 12: ...ration menu using the or button To enter the function press P which will show that the instrument is configured as a fieldbus listener to change to a fieldbus node press the or button which will toggl...

Страница 13: ...nfiguration All display segments activated Display is initialising This is normal operation after a few seconds the model number followed by the firmware version will be displayed prior to entering th...

Страница 14: ...After adding the required legends or fitting a new pre printed self adhesive escutcheon ensure that the gasket is correctly positioned before reassembling the instrument enclosure 7 2 Tag plate The BA...

Отзывы: