4.  INSTALLATION

4.1 Location

The BA644DF-F FOUNDATION™ fieldbus
indicator is housed in a robust IP66 glass
reinforced polyester (GRP) enclosure incorporating
an armoured glass window and stainless steel
fittings.  It is suitable for exterior mounting in most
industrial environments, including offshore and
wastewater treatment installations.  Please consult
BEKA associates if high vibration is anticipated.

The BA644DF-F enclosure is surface mounting.
Accessory kits described in sections 7.3 of this
manual enable the instrument to be mounted onto
a vertical or horizontal pipe.

The field terminals and the two mounting holes are
located in a separate compartment with a sealed
cover allowing the instrument to be installed
without exposing the display assembly.

The BA644DF-F earth terminal is connected to the
carbon loaded GRP enclosure. If this enclosure is
not bolted to a post or structure connected to the
plant potential equalising network, the instrument’s
earth terminal should be connected to the potential
equalising network.

The BA644DF-F enclosure is supplied with a
bonding plate to ensure electrical continuity
between the three conduit / cable entries.

4.2 Installation Procedure

Fig 2 illustrates the instrument installation
procedure.

a. Remove the instrument terminal cover by

unscrewing the two captive 'A' screws.

b. Mount the instrument on a flat surface and

secure with two M6 screws through the 'B'
holes.  Alternatively use one of the mounting
kits described in section 7.3

c.  Remove the temporary hole plug and install

a cable gland or conduit entry with required
ingress protection.  If more than one entry is
required, replace one or both IP66 stopping
plugs with a cable gland or conduit entry
having the required ingress protection.

d. Connect the field wiring to the terminals as

shown in Fig 3.

e.  Replace the instrument terminal cover and

evenly tighten the two 'A' screws.

Fig 2   BA644DF-F installation procedure

4.3  EMC

The BA644DF-F complies with the requirements of
the European EMC Directive 2004/108/EC.  For
specified immunity, all wiring should be in
screened twisted pairs with the screens earthed at
one point.

Содержание FOUNDATION BA644DF-F

Страница 1: ...Issue 4 4th March 2014 BA644DF F FOUNDATION fieldbus Field mounting 8 variable Fieldbus Indicator Issue 4...

Страница 2: ...display parameters 5 3 6 Enable selected input 5 3 7 Enter Device Address 5 3 8 Enter Variable Identity 5 3 9 Decimal point position 5 3 10 Configuration of bargraph 5 3 11 Scale numeric display 5 3...

Страница 3: ...protocol is shown on a label inside the terminal cover The F order code suffix also indicates the protocol but is not shown on the instrument identification label There is an alternative version of t...

Страница 4: ...arth terminal should be connected to the potential equalising network The BA644DF F enclosure is supplied with a bonding plate to ensure electrical continuity between the three conduit cable entries 4...

Страница 5: ...5 Fig 3 Dimensions and terminal connections...

Страница 6: ...nditioned as a fieldbus listener see section 5 3 13 to change it to a fieldbus node 5 2 1 Reset the indicator to node factory defaults rESEt The BA644DF F may be reset to the factory defaults that are...

Страница 7: ...the P button causes the BA644DF F indicator to search the fieldbus segment to which it is connected for all publishers Fig 5 shows how the indicator displays the hexadecimal Device Address and Variabl...

Страница 8: ...vice Address and Variable Identity Parameters can not be changed from within this function See section 5 3 4 Edit Enter addresses and display parameters Contains six sub functions that enable known fi...

Страница 9: ...9...

Страница 10: ...isplayed pressing E will allocate the selected process variable to the selected input and return the display to the Device Address and Variable Identity from which another process variable may be sele...

Страница 11: ...function pressing P again will reveal the existing bargraph justification The or button will scroll through the four options when the required justification is displayed pressing E will enter the sele...

Страница 12: ...ration menu using the or button To enter the function press P which will show that the instrument is configured as a fieldbus listener to change to a fieldbus node press the or button which will toggl...

Страница 13: ...nfiguration All display segments activated Display is initialising This is normal operation after a few seconds the model number followed by the firmware version will be displayed prior to entering th...

Страница 14: ...After adding the required legends or fitting a new pre printed self adhesive escutcheon ensure that the gasket is correctly positioned before reassembling the instrument enclosure 7 2 Tag plate The BA...

Отзывы: