To enter the ‘oFFSt’ function press 

P

 which will

reveal the existing offset with one digit flashing.
Again the flashing digit may be changed by
operating the 

 or 

 button and the 

P

 button will

move control to the next digit or to the decimal
point. When ‘oFFSt’ has been set to the required
value operating the 

E

 button will enter the selection

and return to the ‘oFFSt’ prompt in the sub-menu.
Three operations of the 

E

 button will return to the

‘Edit’ function in the listener configuration menu.

5.3.12 Access code for listener configuration
           menu.        ‘CodE’

Access to the listener menu may be protected by a
four digit security code which must be entered to
gain access.  New instruments are supplied
configured with the default code 0000 which
disables this protection and allows unrestricted
access to the configuration menu.

To enter a new access code select ‘CodE’ in the
listener configuration menu by operating the 

 or

 button.   To enter the function press 

P

 which will

reveal the current access code with one digit
flashing. The code may be changed using the 

 or

 button to adjust the flashing digit and the 

P

button to move control to the next digit.  When the
required code has been selected, press 

E

 to enter

the selection and return to the ‘CodE’ prompt in the
listener configuration menu.    The revised access
code will be activated when the indicator is
returned to the display mode.

If the access code is lost please contact BEKA
associates.

5.3.13 Change from listener to node  ‘tYPE’

This function enables the instrument to be
changed from a fieldbus listener to a fieldbus node
by selecting ‘tYPE’ in the listener configuration
menu using the 

 or 

 button.  To enter the

function press 

P

 which will show that the

instrument is configured as a fieldbus listener, to
change to a fieldbus node press the 

 or 

 button

which will toggle the display to ‘nodE’   To prevent
accidental  changes this request must be
confirmed by operating the 

P

 button and entering

‘5urE’.  The instrument will display ‘0000’ with the
first digit flashing, using the 

 or 

 button set the

flashing digit to ‘5’ and press the 

P

 button to move

control to the next digit which should be set to ‘u’.
When the four letters of ‘5urE’ have been entered,
operating the 

E

 button will cause the instrument to

restart as a fieldbus node in the display mode.

CAUTION

All the instrument’s listener configuration
will be lost when it is changed from a
fieldbus listener to a fieldbus node.

5.3.14  Reset the indicator to listener factory
            defaults  ‘rESEt’

The BA644DF-F indicator may be reset to the
listener factory defaults shown below:

Security Code

0000 (disabled)

For each of the eight inputs:

Input enable

Off

Decimal point

Auto (maximum resolution)

Bar Type

Left

Bar lower limit

0.0

Bar Upper limit

100.0

Gain

1.0

Offset

0.0

To reset the BA644DF-F indicator to the listener
factory defaults select ‘rESEt’ in the listener
configuration menu by operating the 

 or 

button.   To enter the function press 

P

 which will

reveal ‘0000’ with the left hand digit flashing.  To
prevent accidental use of this function, ‘5urE’ must
be entered to confirm that the instrument is to be
reset.

Using the 

 or 

 button set the flashing digit to ‘5’

and press the 

P

 button to move control to the next

digit which should be set to ‘u’.  When the four
letters of ‘5urE’ have been entered operating the 

E

button will reset the BA644DF-F to the factory
defaults.   Any existing configuration and
addresses will be lost when the indicator is reset.

Содержание FOUNDATION BA644DF-F

Страница 1: ...Issue 4 4th March 2014 BA644DF F FOUNDATION fieldbus Field mounting 8 variable Fieldbus Indicator Issue 4...

Страница 2: ...display parameters 5 3 6 Enable selected input 5 3 7 Enter Device Address 5 3 8 Enter Variable Identity 5 3 9 Decimal point position 5 3 10 Configuration of bargraph 5 3 11 Scale numeric display 5 3...

Страница 3: ...protocol is shown on a label inside the terminal cover The F order code suffix also indicates the protocol but is not shown on the instrument identification label There is an alternative version of t...

Страница 4: ...arth terminal should be connected to the potential equalising network The BA644DF F enclosure is supplied with a bonding plate to ensure electrical continuity between the three conduit cable entries 4...

Страница 5: ...5 Fig 3 Dimensions and terminal connections...

Страница 6: ...nditioned as a fieldbus listener see section 5 3 13 to change it to a fieldbus node 5 2 1 Reset the indicator to node factory defaults rESEt The BA644DF F may be reset to the factory defaults that are...

Страница 7: ...the P button causes the BA644DF F indicator to search the fieldbus segment to which it is connected for all publishers Fig 5 shows how the indicator displays the hexadecimal Device Address and Variabl...

Страница 8: ...vice Address and Variable Identity Parameters can not be changed from within this function See section 5 3 4 Edit Enter addresses and display parameters Contains six sub functions that enable known fi...

Страница 9: ...9...

Страница 10: ...isplayed pressing E will allocate the selected process variable to the selected input and return the display to the Device Address and Variable Identity from which another process variable may be sele...

Страница 11: ...function pressing P again will reveal the existing bargraph justification The or button will scroll through the four options when the required justification is displayed pressing E will enter the sele...

Страница 12: ...ration menu using the or button To enter the function press P which will show that the instrument is configured as a fieldbus listener to change to a fieldbus node press the or button which will toggl...

Страница 13: ...nfiguration All display segments activated Display is initialising This is normal operation after a few seconds the model number followed by the firmware version will be displayed prior to entering th...

Страница 14: ...After adding the required legends or fitting a new pre printed self adhesive escutcheon ensure that the gasket is correctly positioned before reassembling the instrument enclosure 7 2 Tag plate The BA...

Отзывы: