BEKA BA678C Скачать руководство пользователя страница 25

9.3.3  Alarm selection:  ALr1  or  ALr2

As shown in Fig 11, each of the two alarms has an
identical set of sub-functions enabling each alarm to
be independently conditioned. ‘ALr1 provides access
to the alarm 1 sub-functions and ‘ALr2’ provides
access to the alarm 2 sub-functions.

The following

sections 9.3.4 to 9.3.12 describe each of these sub-
functions in detail

9.3.4  Alarm enable:  EnbL

This sub-function allows the alarm to be enabled or
disabled

without

altering

any

of

the

alarm

parameters. To check or change the sub-function
select 'EnbL' from the alarm sub-menu using the

or

button and press

P

which will reveal the current

setting. The function can be changed by pressing
the

or

button followed by the

E

button to enter

the selection and return to the ‘EnbL’ prompt in the
alarm menu.

9.3.5 Setpoint adjustment:   SP1 

The setpoint of each alarm relates to the transmitter
digital display and may be positioned anywhere in the
transmitter display range.  

To adjust the setpoint select 'SP1' from the alarm
menu and press

P

which will reveal the existing

alarm setpoint with one digit flashing. The flashing
digit may be adjusted using the

or

push button

and the

P

button to move control to the next digit.

When the required setpoint has been entered press

E

to enter the new setpoint and return to the ‘SP1’

prompt in the alarm menu.

Note:

If, when configured for a voltage or resistance

input, the displayed decimal point has been set to
autorange, it may be necessary to manually position
the decimal point before adjusting ‘SP1’ or ‘SP2’.
This can be achieved by repeatedly operating the

P

button until the activated decimal point flashes, the
decimal point can then be positioned using either the

or

button.

Pressing the

P

button again will

return control to one of the digits.

9.3.6 Alarm function:   hi.Lo

Each alarm can be independently conditioned as a
high or low alarm.

To check or change the alarm

function select 'Hi.Lo' from the alarm menu using the

or

button and press

P

to reveal the current

setting. The function may be changed by pressing
the

or

button, pressing the

E

button will enter

the setting and return the display to the ‘Hi.Lo’ prompt
in the alarm menu.

9.3.7 Alarm output status:   no.nC

This sub-function allows the alarm output to be open
or closed in the non-alarm condition. When deciding
which is required, care must be taken to ensure that
the alarm output is fail safe.    See Fig 8.

‘no’

Alarm output open in non-alarm condition

‘nC’ Alarm output closed in non-alarm condition

CAUTION

When

the

transmitter

supply

is

removed both alarm outputs will be
open

irrespective

of

conditioning.

Therefore for fail safe operation both
alarm outputs should be conditioned
to be open in the alarm condition.

To check or change the alarm output status select
'no.nC' from the alarm menu using the

or

button

and press

P

to reveal the current setting.

The

function can be changed by pressing the

or

button followed by the

E

button to enter the setting

and return to the ‘no.nC’ prompt in the alarm menu.

9.3.8  Hysteresis:   HStr

Hysteresis is shown in the same units as the
transmitter digital display.
To adjust the hysteresis, select 'HStr' from the alarm
menu using the

or

button and press

P

which

will reveal the existing figure with one digit flashing.
The flashing digit can be adjusted using the

or

push buttons, and the

P

button to move control to the

next digit. When the required hysteresis has been
entered, press

E

to enter the new setting and return

to the ‘HStr’ prompt in the alarm menu.

e.g. A BA678C transmitter with a high alarm set at
90.0 and hysteresis of 10.0 will perform as follows:

The alarm will be activated when the display
equals or exceeds 90.0, but will not be 
deactivated until the display falls below 80.0.

Note:

If, when configured for a voltage or resistance

input, the displayed decimal point has been set to
autorange, it may be necessary to manually position
the decimal point before adjusting ‘HStr’. This can be
achieved by repeatedly operating the

P

button until

the activated decimal point flashes, the decimal point
can then be positioned using either the

or

button.

Pressing the

P

button again will return

control to one of the digits.

25

Содержание BA678C

Страница 1: ...Issue 9 4th July 2019 BA678C Panel mounting indicating temperature transmitter Issue 9...

Страница 2: ...BLANK PAGE 2...

Страница 3: ...ermometer type r tYPE 6 1 13 Decimal point position dP 6 1 14 Lower input display in Lo 6 1 15 Higher input display in Hi 6 3 Configuration defaults 7 Configuration example 8 Maintenance 8 1 Fault fin...

Страница 4: ...diagram of the BA678C Indicating Temperature Transmitter The input which may be from a resistance thermometer thermocouple or a dc voltage or resistance is digitised and transferred to the instrument...

Страница 5: ...the sum of the voltage drops caused by the transmitter load and the cable resistance is less than the minimum supply voltage For the transmitter loop shown in Fig 2 Minimum operating voltage of BA678...

Страница 6: ...at an ambient temperature between 20 C and 70 C Please consult BEKA associates if high vibration is anticipated Fig 3 shows the overall dimensions of the BA678C and the panel cut out To achieve an IP6...

Страница 7: ...tion and custom linearisation to be performed Details of the HART communication are contained in the BA47X 67X Indicating Temperature Transmitter HART Interface Guide which may be downloaded from www...

Страница 8: ...smitter input Selects one of the following inputs Thermocouple tHC 3 wire RTD 3rtd 4 wire RTD 4rtd Differential RTD d_rtd Voltage Volt 3 wire resistance 3rES 4 wire resistance 4rES See section 6 2 1 T...

Страница 9: ...Access code for configuration menu Enters four digit configuration menu access code Default code 0000 disables this function See section 6 2 9 For Voltage and Resistance Inputs see Fig 7 Transmitter...

Страница 10: ...e has been selected press E to enter the selection and return to the t tYPE prompt in the configuration menu 6 2 3 Units of digital display dEG The transmitter digital display may be in one of four un...

Страница 11: ...play the ZEro function in the sub menu pressing P again will reveal the existing transmitter input at which the transmitter output current is 4mA Input is shown in units which depend upon how the tran...

Страница 12: ...will return control to one of the digits 6 2 9 Access code for configuration menu CodE Access to the configuration menu may be protected by a four digit security code which must be entered to gain ac...

Страница 13: ...d using either the or button Pressing the P button again will return control to one of the digits 6 2 13 Higher input display in Hi This function which only appears in the menu when the transmitter is...

Страница 14: ...14...

Страница 15: ...15...

Страница 16: ...16...

Страница 17: ...site Function Factory default Transmitter input InPut 3 wire RTD Sensor type t tYPE Pt100 Units of digital display dEG C Display resolution rESn Low Sensor fault FAuLt Off 4 20mA output CAL 0 0 to 10...

Страница 18: ...to enter the selection and return to the InPut prompt in the configuration menu Step 2 Select resistance thermometer type See Fig 6 and section 6 2 10 Using the or button select the r tYPE prompt fro...

Страница 19: ...eveal the existing bargraph justification Using the or button scroll through the options and select LEFt which will start the bargraph on the left hand side of the display Press E to enter the selecti...

Страница 20: ...e digital display Bargraph is over or under range with scale flashing bargraph displaying all or just one segment Input is outside specified range for bargraph Reconfigure bargraph display Digital dis...

Страница 21: ...e fitted with a blank escutcheon around the liquid crystal display If specified when the instrument is ordered this can be supplied printed with units of measurement and a scale for the horizontal bar...

Страница 22: ...ing Temperature Transmitter HART Interface Guide which may be downloaded from www beka co uk manuals for details Alternatively configuration may be performed using the configuration menu which is acce...

Страница 23: ...high or low function See section 9 3 6 no nC Normally open or normally closed output Determines whether the single pole alarm output is open or closed in the non alarm condition See section 9 3 7 HSt...

Страница 24: ...24...

Страница 25: ...al the current setting The function may be changed by pressing the or button pressing the E button will enter the setting and return the display to the Hi Lo prompt in the alarm menu 9 3 7 Alarm outpu...

Страница 26: ...ed 9 3 11 Access Setpoint ACSP This function controls a separate menu that provides direct access to the alarm setpoints when the BA678C transmitter is in the operational mode The function enables an...

Страница 27: ...be displayed Pressing the or button will toggle between the two alarm setpoint prompts SP1 and SP2 If an incorrect security code is entered or a button is not pressed within ten seconds the transmitt...

Отзывы: